background image

T9901125-1-1  UK 

 

Page | 5  

 

Table 1

3.3 Remote 

Control 

Settings 

 
 
On the back of the PCB inside the Ecopower/Ecopower Plus 
Remote Control you will find four DIP switches (see Fig 6) that 
provide optional features detailed in Table 1 below. 
 
 
 
 
 
 
 

DIP 

Feature 

Explanation 

Default 

Notes 

Reset on power-up 

On restoring power after an 
electrical interruption all Remote 
Control settings are retained 

ON 

WARNING!

 – Fans start 

on their own after power 
is restored 

Stop fan on cold 

Fans are switched off when 
heating level is achieved (AUTO 
mode only) 

OFF  

Never blow cold 

Air curtain always heats in 
AUTO mode 

OFF 

Will not go to ambient 
mode 

4 Room 

air 

temperature control 

Enables the room air sensor in 
the Remote Control 

OFF 

Disables all other 
temperature sensors 

 
 
 

 

 

4.1 Remote 

Control 

Switch 

(for Ambient units)

 

 
 
 
 
 
 
 
 
 
 
 

1  On/Off 

Turns the air curtain fans On or Off. 
 

2, 3 & 4  Fan speed 

Switch fan speed between Low, Medium and High respectively. 

 

 

4. 

REMOTE CONTROL OPERATION 

1

Fig 6 

Содержание Ecopower

Страница 1: ...T9901125 1 1 UK Page 1 INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS English Controls EcoPower ...

Страница 2: ...TS 3 3 REMOTE CONTROL INSTALLATION 4 4 REMOTE CONTROL OPERATION 5 Thermoscreens Ltd St Mary s Road Nuneaton Warwickshire England CV11 5AU Email sales thermoscreens com http www thermoscreens com Tel 44 0 24 7638 4646 Fax 44 0 24 7638 8578 1 CONTENTS Page ...

Страница 3: ...ontrollers is supplied 2 DELIVERY CONTENTS NOTE If any parts are missing or damaged contact your place of purchase Ecopower Remote Control for Electric and Water Heated units Remote Control Switch for Ambient units Ecopower Plus Remote Control for Electric and Water Heated units Supplied with 6m RJ Control Cable OR ...

Страница 4: ...low Step 2 Feed one end of the RJ control cable through the back case secure it then screw the back case to the wall using suitable fixings not supplied see Fig 3 Step 3 Connect the RJ plug to the RJ socket on the PCB in the Remote Control Step 4 Refit the front case 3 2 Ecopower Plus Controller Wall Mounting Step 1 Place a slotted screwdriver to each slot on the bottom edge of controller see Fig ...

Страница 5: ...etained ON WARNING Fans start on their own after power is restored 2 Stop fan on cold Fans are switched off when heating level is achieved AUTO mode only OFF 3 Never blow cold Air curtain always heats in AUTO mode OFF Will not go to ambient mode 4 Room air temperature control Enables the room air sensor in the Remote Control OFF Disables all other temperature sensors 4 1 Remote Control Switch for ...

Страница 6: ...ing up or down with the heating level controls The heating level scale shows the level selected Automatic mode Heat output is controlled automatically according to Inlet air temperature or Room air temperature This is dependent on the settings made in Section 3 3 Remote Control Settings DIP switch 4 5 6 7 Fan speed Switch fan speed between Low Medium and High respectively The appropriate LED illum...

Отзывы: