ThermoPlus Air KACSE 012 TO 144 Series Скачать руководство пользователя страница 2

 

 

 

MAN-KACS-001E 

 

 

temperatures and pressures which occur during 
normal operation of system (temperature between 
4

o

 C (40

o

 F) and 43

o

 C (110

o

 F); and pressures up 

to 1380 kPa (200 PSI). 

  When hoses are connected they must not be 

subjected to any stress in tension or by twisting or 
kinking. 

  Hoses available as an accessory to the unit are 

provided with hexagonal surfaces on the fittings 
as are the water fittings on units. Use a properly 
sized wrench on the hexagonal surface to tighten 
connections. 

Never use

 a wrench on the hose or 

sleeve that crimps the fitting into the hose. 

 

Do not over-tighten connections

. Turn in the 

mating threads by hand or with a wrench until 
snug, then tighten with a wrench beyond the point 
just enough to seal the joint (for tapered pipe 
threads this would be an additional 1/2 to one full 
turn; for union or flare connections no more than 
1/4 of a turn). 

  Before pressurising the system, closely inspect 

the hose and fittings to be sure there are no cuts, 
abrasions, twists or kinks. Hoses must not be in 
contact with any sharp edge while in use. 

  Hose supplier will not take responsibility for hose 

leakage, failure or damage resulting from water 
leaks. 

 

WIRING - LINE VOLTAGE

 

Check main power voltage. Refer to unit wiring 
diagram and make changes (if required) to permit the 
unit to operate on the available supply voltage. 
Connect power as per the unit wiring diagram, 
conforming to the local and national electrical code 
requirements. 
 

CONNECTION AND LOCATION OF THERMOSTAT

 

Wiring the thermostat to the unit should be done as 
per the wiring diagram (inside the panel of the electri-
cal box on the vertical units and on the inside of the 
service panel for horizontal units). Thermostat must 
be absolutely level when installed and located to best 
sense the actual room temperature. Avoid false 
sensing heat or cold from sunlight, open doors or 
window drafts, supply air outlets, fireplaces, ovens, 
etc. 
 
 

HIGH PRESSURE PROTECTION

 

Your unit is protected against excessive high 
pressure by a pressure limiting control. If the pressure 
rises above 500 psi (3447 kPa), the pressure switch 

will shut down the unit. 
 

RESET UNIT

 

To restart, 

the unit must

 be turned "OFF" at the 

thermostat or at the main power switch. Then switch 
to "ON" position; the unit will start functioning. If not, 
call a technician to solve the problem. Repeated 
resetting on unit without getting the fault corrected will 
cause compressor failure. 
 

START UP INSTRUCTIONS

 

  After installation of unit and the ductwork, water 

and condensate connections, the wiring in 
accordance with preceding instructions, the unit is 
ready for start-up. Check all wire connections to 
the unit and to external control devices for 
tightness. 

  Set temperature on the thermostat below room 

temperature and start the unit. After operating for 
five(5) minutes, air supply should have a 
minimum temperature drop of 10-12

o

 C (18-22

o

 

F). Use a surface temperature device or any other 
device to check the temperature of supply water 
and return water. The 

minimum temperature

 rise 

should be 6

o

 C (10

o

 F). 

  If the above conditions are not met, one or more 

of the following problems exist: low air flow, low 
water flow, or unit is possibly defective. 

 

MAINTENANCE AND SERVICE

 

  Do not operate the split air conditioner without the 

air filter in place. Filters should be serviced 
regularly, 

at least every three months

  Dirty filters will result in inefficient performance. 

  Check the air coil and fan wheel yearly for 

cleanliness and clean if necessary.  

 
 

NOTICE  

  Hot gas by pass 

  To be adjusted to 55 psi 