For In-Line Splice Connection and End Termination Applications
Terminator
TM
ZS/ZE
In Line Splice/End Termination Kit
INSTALLATION PROCEDURES
Страница 1: ...For In Line Splice Connection and End Termination Applications TerminatorTM ZS ZE In Line Splice End Termination Kit INSTALLATION PROCEDURES...
Страница 2: ...nstallation must comply with Thermon requirements and be installed in accordance with the regulations as per the norm EN IEC 60079 14 for hazardous areas where applicable or any other applicable natio...
Страница 3: ...or with GRW G provided in PETK 3 3 Slide expediter toward pipe and route cable through support base entry 4 Insert banding guide into expediter and snap into place 5 Mount expediter to pipe using pipe...
Страница 4: ...n office nearest you visit us at www thermon com Thermon Inc Printed in U S A Information subject to change 10 Snap on crimp insulators 11 Slide silicone caps over crimp insulators 13 Completed splice...