Installation Instructions

3

4

Locate bus connection and cable as shown.  Cut end
of cable at angle to aid in piercing grommet.  Leave
additional cable for expansion loop.  See pages 11-12
for multiple cable installation tips.

 1.

Insert cable into expediter.  If mounted on bottom of
pipe, punch out weep hole.

 2.

Slide expediter toward pipe and route cable through
support base entry.

 3.

Insert banding guide into expediter and snap into place.

 4.

Mount expediter to pipe using pipe band.  Do not band
over cable.

 5.

Cut off end of cable.

 6.

Содержание Terminator ZP-S

Страница 1: ...llation Instructions Terminator ZP S For Power Connection 1 3 Cables In Line Splice Connection T Splice Connection or End Termination 1 2 Cables Applications for use with HPT power limiting and FP con...

Страница 2: ...rformance ratings are based on the use of Thermon specified parts only User supplied power connection fittings must be European certified for EEx e or UL Listed or certified for AEx e North America on...

Страница 3: ...n loop See pages 11 12 for multiple cable installation tips 1 Insert cable into expediter If mounted on bottom of pipe punch out weep hole 2 Slide expediter toward pipe and route cable through support...

Страница 4: ...rim ends of braid 8 9 Cut and remove primary insulation jacket 10 Cut and remove heating element and fiberglass overlay FP cable only Push any remaining heating element wire under the primary insulati...

Страница 5: ...cable back through expediter Tighten cap securely Tape cable expansion loop to pipe 16 Using dimple molded into side of junction box base to locate center of hole drill for user supplied power connec...

Страница 6: ...et screws shall be tightened to a torque value of 1 4 Nm 12 4 lb in See page 13 for wiring details 21 Install junction box lid and twist hand tight Insert screwdriver into ratchet slots located on sid...

Страница 7: ...oop A1 Insert two cables into expediter A2 Locate bus connection and cable as shown Cut end of cable at angle to aid in piercing grommet Leave additional cable for expansion loop B1 Insert three cable...

Страница 8: ...Power Connection 1 to 3 Cables C1 In Line Splice and T Splice C2 End Termination 1 to 2 Cables Remove jumpers for 2 cable terminations C3 13 14 Wiring Details...

Страница 9: ...Thermon Manufacturing Company 100 Thermon Drive P O Box 609 San Marcos Texas 78667 0609 Phone 512 396 5801 Fax 512 396 3627 1 800 820 HEAT www thermon com Form No 50820 08 25 04...