1
IP66 NEMA/Type 4X -60°C
≤
Ta
≤
+55°C
Ordinary & Hazardous Locations
Class I, Division 2, Groups A, B, C, & D, Zone 2 IIC
Class II, Division 2, Groups F & G, Class III
Listed Heat Tracing Cable System 137M
Kit Contents . . .
Tools Required . . .
The following installation procedures are suggested guidelines
for the installation of termination connection systems. They are
not intended to preclude the use of other methods and good
engineering or field construction practices.
Receiving, Storing and Handling . . .
1. Inspect materials for damage incurred during shipping.
2. Report damages to the carrier for settlement.
3. Identify parts against the packing list to ensure the proper
type and quantity has been received.
Dimensions . . .
Certifications/Approvals . . .
Installation Precautions . . .
• To minimize the potential for arcing and fire caused by product
damage or improper installation use ground-fault protection.
The National Electrical Code (NEC) and Canadian Electrical Code
(CEC) require ground-fault protection of equipment for each
branch circuit supplying electric heat tracing.
• Installation must comply with Thermon requirements and be in-
stalled in accordance with the NEC, CEC, or any other applicable
national and local codes.
• Component approvals and performance ratings are based on
the use of Thermon specified parts only.
• De-energize all power sources before opening enclosure.
• Keep ends of heating cable and kit components dry before and
during installation.
Terminator
TM
DS/DE
Item
Quantity
Description
1
1
Expediter Assembly
Threaded Grommet Compressor
Grommet
Support Base with O-Ring
2
1
Splice Cap
3
1
Banding Guide
4
1
Banding
1
2
2
4
3
4
3
5
Order Separately . . .
SCTK Splice Connection Termination Kits (per cable)
SCTK-1D
for BSX, RSX, TSX, VSX
SCTK-2D
for KSX, HTSX,
SCTK-3D
for HPT, FP
Item
Quantity
Description
1
2
Splice Connection Boots
2
1
Large Wire Nut
3
2
Medium Wire Nuts
4
2
Small Wire Nuts
5
1
RTV Tube
6
1
GRW-G Grommet (SCTK-3D only)
6
1