Thermokon SR-MDS Скачать руководство пользователя страница 3

Issue Date: 16.11.2020

  

 

Page 3 / 5 

 

 

 

Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0  fax: -400  

www.thermokon.com

  

[email protected]

 

 

SR-MDS_Datasheet_en-us.docx   © 2020 

» 

TECHNICAL DATA 

Measuring values 

(type-dependent)

 

Brightness, motion, optional temperature 

Radio technology 

EnOcean (IEC 14543-3-10), transmission power <10 mW 
EEP A5-08-01 

Power supply 

SR-MDS (Temp)

 

flex. 15..240 V =/~,  

SR-MDS (Temp) BAT

 

3x battery LS14250, 3,6 V 

Power consumption 

typ. 0,8 W (24 V =) | 1,2 VA (24 V ~) 

Measuring range 

temperature 

(type-dependent)

 

+32..+123,8 °F 

(0..+51 °C)

 

Measuring range light 

0..47,4 fc 

(0..510 Lux)

 

Accuracy temperature 

(type-dependent)

 

±0,5 K (typ. at 70 °F) 

Accuracy light 

±3 fc 

Transmission interval 

WakeUp time = 100 sec. (default) 

every 100 sec. at change of brightness >1 fc in case of detected motion, every 1000 sec. at change of 

brightness <1 fc in case of no motion detected, every 100 sec. at change of brightness <1 fc in case of 

detected motion, every 10 sec. at change of brightness >1 fc in case of detected motion, immediately at 

status 

change from no motion to motion, status change from motion to no motion after ≈ <200 sec.

 

Detection range 

Ø=16 ft. 

(5 m)

 at a sensor height of approx. 8 ft. 

(2,5 m)

 

Sensor 

PIR (passive infrared) 

Enclosure 

ABS, pure white 

Protection 

IP20 according to EN 60529 

Connection electrical 

terminal, max. 1,5 mm², plugable 

Ambient condition 

-10..+50 °C, max. 85% rH non-condensing 

Notes 

appropriate for constant light control 

» 

COMMISSIONING AND TRANSMISSION TIME INTERVAL SETTING 

To ensure that the measured values of the sensors are correctly evaluated at the receiver, it is necessary to teach the devices into the receiver. 

This is done automatically using the "Learn" button on the sensor or manually by entering the 32bit sensor ID and a special "teach-in procedure" 

between transmitter and receiver. Details are described in the respective software documentation of the receiver. 

To access the Learn button, turn the sensor cover counterclockwise 

and remove the cover. 
The learn button is located on the bottom of the motion sensor.  The 

exact positioning is shown in the figure on the right.  
 
 

 
Setting of transmission time 

 

Before opening the device, disconnect it from the power supply! 

Factory default: T_wake up: 100, T_intervall: 10 

Transmission time = 100 seconds (T_wake up) x 10 (T_intervall)  

= 1000 seconds = approx.16 minutes 

Note fort he battery operated device: 

The transmission frequency 

also has a direct influence on the operating energy available in the 

energy storage device and thus on the discharge time of the energy 

storage device during operation. 

 

 