Issue Date: 06.04.2021
Page 10 / 12
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Deutschland · tel: 02778/6960-0 · fax: -400 ·
LCF02-5DO_Datasheet_en.docx © 2021
3= inverted PWM (0%= 100%PWM .. 100% = 0% PWM)
Inputs
Address
Access Description
Resolution / Unit
Default
336
0x0150
Read-write
Configuration external input 1
0 = No function
1 = Occupancy sensor (Open = Occupied)
2 = Occupancy sensor (Closed =Occupied)
3 = Window contact (Open = Window Open)
4 = Window contact (Closed = Window Open)
5 = Disable heating (Open = Heating disabled)
6 = Disable heating (Closed = Heating Disabled)
7 = Disable cooling (Open = Disable Cooling)
8 = Disable cooling (Closed = Disable Cooling)
9 = Dew Point Sensor (Open = Dewpoint crossed, disable
cooling)
10 = Dew Point Sensor (Closed = Dewpoint crossed,
disable cooling)
0
337
0x0151
Read-write
Configuration external input 2
0 = No function
1 = Occupancy sensor (Open = Occupied)
2= Occupancy sensor (Closed =Occupied)
3 = Window contact (Open = Window Open)
4 = Window contact (Closed = Window Open)
5 = Disable heating (Open = Heating disabled)
6 = Disable heating (Closed = Heating Disabled)
7 = Disable cooling (Open = Disable Cooling)
8 = Disable cooling (Closed = Disable Cooling)
9 = Dew Point Sensor (Open = Dewpoint crossed, disable
cooling)
10 = Dew Point Sensor (Closed = Dewpoint crossed, disable
cooling)
0
338
0x0152
Read-write
Configuration Sensor Input
0= none
1 = Change Over Temp sensor (NTC10K)
2 = Ext. Temp sensor (NTC10K)
3 = Temperature Limiter
0
339
0x0153
Read-write
ESI (Energy Savings Input) - ON delay
ON delay for ESI. Delays Energy stop by n seconds
1.0
s
0
340
0x0154
Read-write
OCC input - OFF delay
0…65535 -> 0…65535 seconds
1.0
s
1800