Controller operating manual
15.11.2020 – Version 1.1
TCS.2 series –
thermofin
®
control system 2
nd
generation
Page: 122/162
Operating manual - translation into English © thermofin GmbH
Editable from … to:
0 … 100 %
Factory setting:
80 %
Delay winter operation OFF:
Defines a delay in minutes in which both the temperature
(winter operation OFF >) and the “RPM Winter operation OFF”
must have exceeded the set changeover limit in order to
deactivate winter operation. This delay prevents winter
operation from being switched on and off continuously when
the changeover values are reached.
Editable from … to:
0 … 600 min
Factory setting:
10 min
Current status:
Winter or summer operation active
Allows switching between summer and winter operation using
the switch symbol. This function is intended for commissioning
and test purposes. If the ambient temperature falls below the
lower temperature limit, it is no longer possible to switch off
winter operation for safety reasons.
Display of ambient temperature
Currently measured ambient temperature. Useful for commissioning and adjusting the settings.
Display of main valves
Status display of the main valve positions. The following symbols are used as indicators in the
display:
Valve is OPEN
Valve is CLOSED
Valve is OPENING
Valve is CLOSING