MULTIFUNCTIONAL UNITS RLC – Installation and maintenance manual
MUMRLCHEAT_REV01_1012_UK
Pag. 17 di 31
8.3.2
Water-water unit connection scheme (geothermal applications)
T
T
T
VR
VR
RB
RB
VR
P3
P1
P1
ET
VASO DI ESPANSIONE
- EXPANSION VESSEL
- CLIMATIZATION WATER TANK
SERBATOIO UTENZE CLIMATIZZAZIONE
SU
SR
SERBATOIO UTENZE ACS
- SANITARY WATER TANK
- RECOVERY
RECUPERO
REC
EWR
EVAPORATORE/CONDENSATORE
-EVAPORATOR / CONDENSER
- TEMPERATURE PROBE
SONDA DI TEMPERATURA
T
M
VALVOLA MISCELATRICE A 3 VIE
- 3 WAY MIXING VALVE
- SHUTT OFF VALVE
VALVOLA DI INTERCETTAZIONE
R
SF
VALVOLA DI SFIATO
- VENT VALVE
F
RACCOGLITORE IMPURITA'
- STEEL MESH STRAINER
- FILLING GROUP
GRUPPO DI RIEMPIMENTO
GR
SC
SCARICO
P2
POMPA SECONDARIO
- SECONDARY PUMP
- PRIMARY PUMP
POMPA PRIMARIO
P1
- SAFETY VALVE
VALVOLA DI SICUREZZA
SV
- DRAINAGE
P3
POMPA SOLARE TERMICO
- SOLAR THERMAL PUMP
T
M
DEHUMIDIFIER
DEUMUDIFICATORE
M
T
EWR
REC
PRS
PRS
VALVOLA PRESSOSTATICA
- PRESSURE REGULATOR
For units with geothermal source, a system for regulating the condensation or evaporation pressure must always be mounted. The best
regulation system is a variable flow system checking the condensation pressure during summer mode and the evaporation pressure
during winter mode. The controller has a 0-10 V signal configured for this function.
Another solution is the use of a pressure control valve operating in chiller mode and a two-way valve that allows to work with full flow in
heat pump mode.
The geothermal source pump must be controlled by the unit and it is turned off when it is not required its activation as for example
during c recovery operation mode. During other operationg modes the groundwater pump is off and will start again before the
activation of the compressor. To avoid flow switch alarms due to late flow reading it is recommended to install the flow switch
immediately downstream of the pump
.