Service settings manual
42
Para-
meter
Function
Parameter description
Setting range
Default
value
F2.17 SWITCH-ON
IMPULSE / CIRCU-
LATION PUMP
RUNNING TIME
This function activates output for setted time. After setted time
expires, the output is switched off, regardless to other switch-on
or switch-off commands.
This setting is especially useful for control of support pump in
Drain-back systems.
Setting 0 means there is no delay and the output should activate
immedately and stay activated for the whole time of switch-on
command.
0 ÷ 3600 s
0
F2.18 SWITCH-ON DE-
LAY / CIRCULATI-
ON PUMP STAND-
BY TIME
This function delays activation of output for setted time. Output is
activated when setted delay time expires.
REMARK: If delay time is longer as time of switch-on period the
output won't activate.
Setting 0 means there is no delay and the output should activate
immedately and stay activated for the whole time of switch-on
command.
0 ÷ 3600 s
0
F2.19 MIN/MAX TEMPE-
RATURE LIMITATI-
ON
Setting how the programmed output responds if selected tem-
perature sensor (F1.20) achieves its min. or max. temperature
(min. and max. temperatures are set in P2 parameters). This
function is used when it is necessary to respect min. or max.
temperature limitations of particular sensor.
0- NO
1- T<T
MIN
fi
OFF
2- T>T
MAX
fi
ON
3- T<T
MIN
fi
OFF,
T>T
MAX
fi
ON
4- T<T
MIN
fi
ON
5- T>T
MAX
fi
OFF
6- T<T
MIN
fi
ON,
T>T
MAX
fi
OFF
0
F2.20 SENSOR FOR MIN/
MAX TEMPERATU-
RE LIMITATION
Selection of sensor for the MIN/MAX temperature
limitation.
1- T1 2- T2
3- T3 4- T4
5- T5 6- T6
5
A1343_3
MJ/OD
06/2018
Содержание SGC36HV
Страница 2: ...A1343_3 MJ OD 06 2018 ...
Страница 4: ...A1343_3 MJ OD 06 2018 ...
Страница 180: ...NOTES NOTIZEN POZNÁMKY 180 A1343_3 MJ OD 06 2018 ...
Страница 181: ...NOTES NOTIZEN POZNÁMKY 181 A1343_3 MJ OD 06 2018 ...
Страница 182: ...NOTES NOTIZEN POZNÁMKY 182 A1343_3 MJ OD 06 2018 ...
Страница 183: ...A1343_3 MJ OD 06 2018 ...