Thermo Products Thermo Pride AC14241B1 Скачать руководство пользователя страница 9

All installations and services must be performed by qualified personnel.

 

G. ELECTRICAL 

 

All wiring must conform to the provisions of local codes or, in the absence of local codes, with the provisions of the National 
Electrical Code, "Latest Edition" and this instruction manual. An equivalent type wire must be used if any of the original wire 
supplied with the unit needs to be replaced. 
 
Reference Table A for unit electrical characteristics.  Bring proper service to the unit through a circuit breaker or fused disconnect 
switch, in accordance with local codes. In the case of a single phase 230 VAC unit, the neutral wire should be brought to the unit 
in order to provide ground service. A ground wire must be connected to the unit at the screw or pressure connector marked 
"ground". 
 
The best fuse size is the smallest fuse that will allow the equipment to operate continuously without any nuisance trips. This type 
of fuse will give the equipment maximum protection. A time delay type fuse; such as Fustat® or Fusetron®, will prevent nuisance 
trips due to the starting current (locked rotor amps, LRA). 

 

FUSE SIZING - TABLE A 

Recommendations 

Compressor 

Fuse or HACR 

Circuit Breaker

Unit Model 

Voltage/ 

Phase/ Hertz  RLA

4

 LRA

5

 

Fan 

Motor 

FLA 

Minimum 

Circuit 

Ampacity 

AMPS 

Min. 

Copper 

Wire Size 

(AWG) 

Min. 

AMPS 

Max. 

AMPS

AC14241B1 

208-230/1/60 12.1  56 

0.8 

15 

#14 

20 

25 

AC14301B1 

208-230/1/60 13.6  67 

0.8 

18 

#14 

20 

30 

AC14361B1 

208-230/1/60 16.4  83 

0.8 

22 

#12 

25 

35 

AC14421B1 

208-230/1/60 18.4  95 

1.6 

25 

#10 

30 

40 

AC14481B1 

208-230/1/60 20.4  109  1.6 

27 

#10 

30 

45 

AC14601B1 

208-230/1/60 32.1  148  1.6 

42 

#6 

45 

70 

AC14483B1 

208-230/3/60 13.9  88 

1.6 

19 

#14 

20 

30 

AC14603B1 

208-230/3/60 19.3  123  1.6 

26 

#10 

30 

45 

 NOTE:

  Recommended wire sizes are for copper conductors only. 

 

*Use (as minimum) type "T" or "TW" wire. 60 C. 

 
 

Local and/or national electrical codes dictate which wire size you must use!  
 For 

example: 

 

1

If a 25 or 30 amp fuse is used, a minimum wire size of 10 AWG must accompany it. 

 

2

If you fuse to maximum sizes, your wire size must be adjusted accordingly.  

 

3

12 AWG wire may be used only with a 20 amp or smaller fuse size. 

 

4

R.L.A.=Compressor running load amps. 

 

5

L.R.A.=Compressor locked rotor amps. 

6

F

.L.A.=Full load amps of condenser blower motors.   

 

In the event a fuse blows, investigate for the cause. Do not put in a larger fuse and do not exceed maximum fuse size listed on 
name plate. The name plate is located just above the valve connection on the outside surface of the outdoor unit.  

 
NOTICE:

 Before the Air Conditioning unit is started, the following points must be checked by the installer and/or electrician

.

 

 
1). Check every electrical connection of "PUSH-ON" or "SCREW-ON" type terminals to insure it is secured tightly on its proper 
post. 
 
2). Review wiring diagram for proper routing. 
 
3). All wiring must comply with NEC or local codes for wire sizes. Also, it is suggested that the next larger size wire to be used 
when long runs in excess of 100 ft. are experienced.  Reference the following wiring diagrams when wiring or servicing. 
 
A loose terminal will cause poor flow of electrical power to the compressor and result in very high current draw. This can lead to 
blown fuses, burned wires, burned contact points and a premature compressor failure. Each electrical contact has been factory 
checked, however, connections may loosen up due to vibration in transit.  Please be certain that all electrical connections are tight. 

Содержание Thermo Pride AC14241B1

Страница 1: ...contains your assembly instructions and guarantee This device is potentially dangerous if improperly installed We recommend installation by qualified heating air conditioning contractors Please read...

Страница 2: ...TUBING INSTALLATION 5 D TUBING SIZE REFERENCE CHART 6 E INSTALLATION OF TUBING LINES TO SERVICE VALVES 7 F DUCT SYSTEM 8 G ELECTRICAL 9 INITIAL START UP OF OUTDOOR CONDENSING UNIT 12 AND HOW TO MEASUR...

Страница 3: ...sing unit is designed and built with a totally enclosed hermetic scroll compressor which offers the advantages of simplicity quiet operation and reduced condenser size The entire air conditioning syst...

Страница 4: ...aded locations on the north side of a home or office are generally best if practical Mount the unit on a sturdy base at least one inch above the ground Be sure to use well tamped gravel fill beneath t...

Страница 5: ...Any horizontal runs of suction line should have minimum 1 2 pitch towards the outdoor condensing unit for every 10 feet of line 2 A trap is necessary in the suction line at the indoor evaporator coil...

Страница 6: ...1 1 8 5 8 NOTES For line lengths over 25 adjust charge accordingly per foot of variation from chart 65 oz per foot for 3 8 and 3 4 line set 674 oz per foot for 3 8 and 7 8 line set 694 oz per foot for...

Страница 7: ...crons or lower when all joints and fittings are leak free The service valves on the condenser may then be opened to release the refrigerant to the system Verify proper system performance See condensin...

Страница 8: ...e CFM capacity for square inch areas based on 10 W C static pressure SP loss on the supply systems To insure the necessary air handling capacity of a duct system each of the system s components trunk...

Страница 9: ...B1 208 230 3 60 13 9 88 1 6 19 14 20 30 AC14603B1 208 230 3 60 19 3 123 1 6 26 10 30 45 NOTE Recommended wire sizes are for copper conductors only Use as minimum type T or TW wire 60 C Local and or na...

Страница 10: ...OPERLY SWAP POWER WIRES SPECIFICATIONS INPUTS R R C C Secondary of control transformer 18 30 VAC Y R From Thermostat LPC1 LPC2 Low Pressure Switch HPC HPC High Pressure Switch OUTPUTS CC Compressor Co...

Страница 11: ...gize the compressor contactor and initiate the DELAY ON BREAK timer The compressor contactor will remain de energized until the DELAY ON BREAK time has expired The DELAY ON BREAK time is 180 seconds H...

Страница 12: ...he system should run for at least 10 minutes before rechecking All Thermo Pride outdoor condensing units are equipped with gauge ports to connect both liquid and suction line pressure gauges Refrigera...

Страница 13: ...migration during off cycle These situations are detrimental to the life of a compressor USER INFORMATION The following maintenance points should be reviewed periodically to assure that the air conditi...

Страница 14: ...FICATIONS Unit Model AC14241B1 AC14301B1 AC14361B1 AC14421B1 AC14481B1 3B1 AC14601B1 3B1 Capacity BTU H 25 200 29 500 36 000 41 800 47 200 58 000 Evaporator CFM 800 1 000 1 200 1 400 1 600 2 000 R22 o...

Страница 15: ...All installations and services must be performed by qualified personnel 15...

Отзывы: