Thermo Products Thermo Pride AC14241B1 Скачать руководство пользователя страница 1

MAC-178 

ECN4610-MA  

AIR CONDITIONING 

 

 

 

14 SEER

 

 

INSTALLATION & SERVICE MANUAL 

 
 
 

 

 

Thermo Products, LLC. 

North Judson, Indiana 

 

 

              

 

Do Not Destroy: 

 

This envelope contains your assembly instructions and guarantee. 

 

This device is potentially dangerous if improperly installed. 

 

We recommend installation by qualified heating & air conditioning contractors. 

 

Please read the enclosed instructions carefully, before & during installation. 

 

Please keep these instructions as permanent reference near appliance. 

• • IMPORTANT • • 

Содержание Thermo Pride AC14241B1

Страница 1: ...contains your assembly instructions and guarantee This device is potentially dangerous if improperly installed We recommend installation by qualified heating air conditioning contractors Please read...

Страница 2: ...TUBING INSTALLATION 5 D TUBING SIZE REFERENCE CHART 6 E INSTALLATION OF TUBING LINES TO SERVICE VALVES 7 F DUCT SYSTEM 8 G ELECTRICAL 9 INITIAL START UP OF OUTDOOR CONDENSING UNIT 12 AND HOW TO MEASUR...

Страница 3: ...sing unit is designed and built with a totally enclosed hermetic scroll compressor which offers the advantages of simplicity quiet operation and reduced condenser size The entire air conditioning syst...

Страница 4: ...aded locations on the north side of a home or office are generally best if practical Mount the unit on a sturdy base at least one inch above the ground Be sure to use well tamped gravel fill beneath t...

Страница 5: ...Any horizontal runs of suction line should have minimum 1 2 pitch towards the outdoor condensing unit for every 10 feet of line 2 A trap is necessary in the suction line at the indoor evaporator coil...

Страница 6: ...1 1 8 5 8 NOTES For line lengths over 25 adjust charge accordingly per foot of variation from chart 65 oz per foot for 3 8 and 3 4 line set 674 oz per foot for 3 8 and 7 8 line set 694 oz per foot for...

Страница 7: ...crons or lower when all joints and fittings are leak free The service valves on the condenser may then be opened to release the refrigerant to the system Verify proper system performance See condensin...

Страница 8: ...e CFM capacity for square inch areas based on 10 W C static pressure SP loss on the supply systems To insure the necessary air handling capacity of a duct system each of the system s components trunk...

Страница 9: ...B1 208 230 3 60 13 9 88 1 6 19 14 20 30 AC14603B1 208 230 3 60 19 3 123 1 6 26 10 30 45 NOTE Recommended wire sizes are for copper conductors only Use as minimum type T or TW wire 60 C Local and or na...

Страница 10: ...OPERLY SWAP POWER WIRES SPECIFICATIONS INPUTS R R C C Secondary of control transformer 18 30 VAC Y R From Thermostat LPC1 LPC2 Low Pressure Switch HPC HPC High Pressure Switch OUTPUTS CC Compressor Co...

Страница 11: ...gize the compressor contactor and initiate the DELAY ON BREAK timer The compressor contactor will remain de energized until the DELAY ON BREAK time has expired The DELAY ON BREAK time is 180 seconds H...

Страница 12: ...he system should run for at least 10 minutes before rechecking All Thermo Pride outdoor condensing units are equipped with gauge ports to connect both liquid and suction line pressure gauges Refrigera...

Страница 13: ...migration during off cycle These situations are detrimental to the life of a compressor USER INFORMATION The following maintenance points should be reviewed periodically to assure that the air conditi...

Страница 14: ...FICATIONS Unit Model AC14241B1 AC14301B1 AC14361B1 AC14421B1 AC14481B1 3B1 AC14601B1 3B1 Capacity BTU H 25 200 29 500 36 000 41 800 47 200 58 000 Evaporator CFM 800 1 000 1 200 1 400 1 600 2 000 R22 o...

Страница 15: ...All installations and services must be performed by qualified personnel 15...

Отзывы: