All installations and services must be performed by qualified service personnel.
48
Is LED light on ignition
control module flashing?
Check all wiring for
loose connections.
No
Troubleshooting Complete.
Yes
Does the circulating air
blower turn off after
thermostat is satisfied
within 180 seconds?
Yes
Yes
Does burner shut off
when thermostat is
satisfied?
Check DIP switch settings
on ignition control module
against those on connection
diagram. Reset if necessary.
No
Check for short in wire to
thermostat. Replace
thermostat if necessary.
No
Yes
No
Yes
Does system run until
thermostat is satisfied?
If LED Light Flashes:
1 Flash, then pause............System lockout
2 Flashes, then pause........Pressure switch stuck closed
3 Flashes, then pause........Pressure switch stuck open
4 Flashes, then pause........Open high limit, aux. limit, or roll-out switch
6 Flashes, then pause........115 Volt AC power reversed
7 Flashes, then pause........Low flame sense signal
8 Flashes, then pause........Check ignitor or improper grounding
Continuous flashing............Flame has been sensed when no flame
(no pause) should be present (no call for heat)
Содержание MDA1-100N
Страница 55: ...All installations and services must be performed by qualified service personnel 51...
Страница 56: ...All installations and services must be performed by qualified service personnel 52 REPLACEMENT PARTS LIST MDA1...
Страница 57: ...All installations and services must be performed by qualified service personnel 53...
Страница 58: ...All installations and services must be performed by qualified service personnel 54 APPENDIX F WIRING DIAGRAM...
Страница 59: ...All installations and services must be performed by qualified service personnel 55...
Страница 62: ......