C.  ADJUSTMENT OF BTU INPUT RATE: 

 
The orifice for this furnace was sized: 1) for natural gas having a heating value of 
1025 BTU per cubic foot and a specific gravity of .65, or 2) for liquefied propane 
gas  with  a  heating  value  of  2500  BTU  per  cubic  foot  and  a  specific  gravity  of 
1.55.  The  information  plate  inside  the  furnace  vestibule  will  specify  which  gas 
your  furnace  is  orificed  for.  If  the  furnace  is installed  at  an  altitude  that is  more 
than  2,000  feet  above  sea  level,  it is  mandatory  that  the  input  to  the  burner  be 
reduced  4.0%  for  every  1,000  feet  that  it  is  above  sea  level.  If  the  furnace  is 
installed at an elevation of 5,000 feet, its input must be reduced 20.0%. Example: 
a  furnace  rated  at  75,000  BTU  at  sea  level  must  be  reduced  to  a  firing  rate  of 
60,000  (75,000  x  .80  =  60,000)  at  an  elevation  of  5,000  feet.  If  the  furnace  is 
installed  at  an  elevation  of  2,000  feet  or  less,  no  reduction  in  input  is  required. 
Your  gas  supplier  or  Thermo  Products  will  supply  you  with  the  correct  orifice 
sizing information. 
 
To check the input of your natural gas furnace, allow the unit to operate for 10 to 
15 minutes and proceed as follows: 
 

1. Call your gas supplier and ask for the BTU content (heating value) of one 

cubic  foot  of  the  gas,  supplied  to  the  installation  area.  An  alternate 
approach  is  to  assume  a  value  of  1025  BTU/Cu  Ft  which  is  the  national 
average. 

 

2.  With all other gas appliances turned off and using a stopwatch, clock the 

time  required  for  the  (small)  dial  on  the  gas  meter  to  make  one  full 
revolution.    The  meter  dial  will  state  the  cubic  feet  of  flow  for  one 
revolution usually one, two or five. 

 

FORMULA: 

BTU/Cu Ft x Number of Cu Ft x 3600 Seconds = Input BTU/hr 

                                 Seconds for one revolution 

 
EXAMPLE:

 1025 BTU/Cu Ft x 2 Cu Ft x 3600 = 73,505 BTU Input 

                                   100.40 Seconds 
 

Check  the  model  number  of  the  furnace,  the  input  rate,  the  type  of  gas, 
and  the  manifold  pressure  on  the  rating  label  located  in  the  burner 
vestibule.  If using the above example, the furnace is a CMA2-75N model 
and the input rate is 73,505 BTU/hr.  The input rate would be acceptable 
because it was  2% of the listed input of 75,000. 

 

3.  Make  sure  that  the  gas  supply  pressure  to  the  furnace  is  within  the 

allowable  range  of  5.5"  to  14"  WC  pressure  on  natural  gas  and  11.0"  to 
14.0" WC on propane gas.  The pressure to the furnace must be checked 
while  the  furnace  burner  and  any  other  gas  appliances  on  the  same 
supply system are operating, using the 1/8 in. NPT manifold pressure tap. 

Содержание CMA4-50D36N

Страница 1: ...ires B timents 3 Site Constructed Residential 3 Site a construit R sidentiel Single Story Dwellings Habitations tage unique PLEASE READ THESE INSTRUCTIONS PRIOR TO INSTALLATION INITIAL FIRING AND BEFO...

Страница 2: ......

Страница 3: ...Location Guidelines 27 Installation of Outside Exhaust Intake Terminations 27 Connecting the Furnace to Roof Vent Intake Terminations 28 Condensate Drain Line and Trap Assembly 30 Electrical Wiring 31...

Страница 4: ...ocations of Direct Vent Terminations When Sidewall Venting 25 Minimum Clearances Between Vent Terminal and Various Building Features 26 Construction Details of Sidewall Vent and Air Intake Termination...

Страница 5: ...ice agency or fuel supplier c AVERTISSEMENT Une installation un r glage un entretien ou une maintenance incorrects peuvent provoquer des blessures ou des dommages mat riels Reportez vous ce manuel Pou...

Страница 6: ...FORMATION This and the following page contain reproductions of the various warning and instruction labels placed on the Thermo Pride Condensing Gas Furnaces Please read and comply with the contents of...

Страница 7: ...This and the previous page contain reproductions of the various safety and instruction labels placed on the Thermo Pride Condensing Gas Furnaces Please read and comply with the contents of these label...

Страница 8: ...This and the previous page contain reproductions of the various safety and instruction labels placed on the Thermo Pride Condensing Gas Furnaces Please read and comply with the contents of these label...

Страница 9: ...nstall furnace with a duct system that has an external static pressure within the allowable range referenced in specifications 7 Make sure supply air ducts are completely sealed to the furnace casing...

Страница 10: ...r mastics Vapors from such products can form acid compounds when burned in a gas flame Should acid compounds form in your furnace it may reduce the life of the furnace Because of the potential of odor...

Страница 11: ...e the specific gravity of LP gas allows it to accumulate at floor level at a dangerous concentration Heat exchanger oil will burn off on initial firing creating an unpleasant odor To prevent this odor...

Страница 12: ...AFUE 95 ANNUAL FUEL UTILIZATION EFFICIENCY DIMENSIONS CABINET SIZE WIDTH 18 DEPTH 25 3 4 HEIGHT 57 SUPPLY AIR OUTLET WIDTH 12 DEPTH 12 ELECTRICAL SUPPLY 115 VOLTS 60HZ 1 PH FUSE OR HACR BREAKER 15 AMP...

Страница 13: ...EL UTILIZATION EFFICIENCY DIMENSIONS CABINET SIZE WIDTH 18 3 4 DEPTH 25 3 4 HEIGHT 76 1 8 SUPPLY AIR OUTLET WIDTH 12 DEPTH 12 ELECTRICAL SUPPLY 115 VOLTS 60HZ 1 PH FUSE OR HACR BREAKER 15 AMPS TOTAL C...

Страница 14: ...TION EFFICIENCY DIMENSIONS CABINET SIZE WIDTH 18 3 4 DEPTH 25 3 4 HEIGHT 76 1 8 SUPPLY AIR OUTLET WIDTH 12 DEPTH 12 ELECTRICAL SUPPLY 115 VOLTS 60HZ 1 PH FUSE OR HACR BREAKER 15 AMPS TOTAL CURRENT AMP...

Страница 15: ...t drain knock out 330355 1 330355 1 Grommet vinyl 3 8 350040 1 350040 1 Grommet vinyl 7 8 350009 1 350009 1 Screw 8 x 1 2 Tek 300208 6 300208 6 Coil trim panel 619113 1 619113 1 Bushing UB 875 350750...

Страница 16: ...oducts in the primary heat exchanger The installation must conform with local codes or in the absence of local codes with the National Fuel Gas Codes ANSI Z223 1 or latest edition and with these instr...

Страница 17: ...truction heater Listed below are definitions of COMBUSTIBLE MATERIAL and NON COMBUSTIBLE MATERIAL COMBUSTIBLE MATERIAL Material made of or surfaced with wood compressed paper plant fibers plastics or...

Страница 18: ...rnace may be installed on a combustible floor when utilizing either the No 70 counterflow floor base or CE111S coil cabinet for below the floor duct systems or the cottage base for floor level air dis...

Страница 19: ...el CE111S Note Coil cabinet cannot be utilized as a cottage base CE111S Figure 1B Cottage Base Model 01COT BASE For CMA4 models only NOTE Serves as a plenum for single story applications with exposed...

Страница 20: ...models only Use the base bottom panel as a template to mark floor opening locations see Figure 2 Cut a square opening in the floor for the supply air connector duct Cut the opening 1 inch larger than...

Страница 21: ...other hand This assures a tight connection between the base assembly and the connector duct and that the distribution duct will be full size Use high temperature tape and or high temperature silicone...

Страница 22: ...A4 SERIES CMC2 SERIES Figure 4 D CLOSET INSTALLATION 1 The return air opening into the closet is to have a minimum free area of 250 sq in see Figure 5 a The return air opening may be located in the to...

Страница 23: ...free area of openings in the floor or ceiling registers serving the return duct system must be at least 350 square inches At least one register must be located where it is not likely to be covered by...

Страница 24: ...installed within six feet of the gas equipment it serves A union or flanged connection shall be provided directly up stream of the burner to allow burner removal Unions must be of a ground joint type...

Страница 25: ...e concentric vent kit NOTE All CMA CMC furnaces must be installed with outside combustion air 3 The flue vent pipe and combustion air pipe must be at least as large as the exhaust vent air intake pipe...

Страница 26: ...r intake collar on the burner box The screw securing the sleeve or coupling to the collar is sufficient 7 Use the two radiator hose clamps to connect both the exhaust vent and combustion air vent pipe...

Страница 27: ...tion to the top of the furnace Access is gained by removal of two screws in the upper right and left of the furnace The top front access panel is then removed by pulling forward Once the vent connecti...

Страница 28: ...air intake pipe must be supported every 4 feet After making sure the length of the piping is correct glue all connections in place except the connection to the burner box If the combustion air piping...

Страница 29: ...ion Air Intake RH view NOTICE If exterior sidewall building materials are subject to degradation from contact with flue gases or moisture a minimum 24 inch diameter shield shall be fabricated from sta...

Страница 30: ...shall be located at least 3 feet above any forced air inlet located within 10 feet Refer to Figure 9 for a depiction of the minimum required clearances between vent terminations and building features...

Страница 31: ...ion of pressure regulators relief valves or any other equipment d The vent terminal shall be installed a minimum of 14 inches from any obstruction and 3 feet from an inside corner of an L shaped struc...

Страница 32: ...son for restriction or blockage from foreign material in the exhaust vent or in the air intake piping Clean the air intake and vent terminations when necessary I Installation Of Outside Exhaust Intake...

Страница 33: ...hrough the existing roof jack or thru the 3 ceiling roof flashing plate Concentric vent utilizing existing roof jack as a chase Two kits are available depending on the flue pipe diameter of the existi...

Страница 34: ...air intake shall be installed upwind of the vent outlet when exposed to prevailing winds The exhaust vent and combustion air intake can be a minimum of 3 in and a max of 24 in apart see Figures 11 12...

Страница 35: ...Figure 13 Continue installing PVC pipe to exhaust vent and combustion air intake termination as described previously Figure 13 K CONDENSATE DRAIN LINE AND TRAP ASSEMBLY 1 Figure 14 illustrates the ty...

Страница 36: ...the white wire e Connect the ground wire to the green wire f Reinstall and secure the junction box cover with the original mounting screws NOTICE The hot surface igniter and operation of this furnace...

Страница 37: ...Wire Diameter Maximum Recommended Thermostat Wire Length AWG Feet 24 55 22 90 20 140 18 225 Once the furnace is installed check the thermostat anticipator for proper nominal setting 1 Connect a multi...

Страница 38: ...33 4 BLOWER MOTOR SPEED WIRING Figure 15...

Страница 39: ...External Static Pressure in WC 0 1 0 2 0 3 0 4 0 5 0 6 0 7 Low 53 55 57 59 63 71 78 ML 42 44 45 48 51 53 59 MH 35 37 38 40 42 45 49 High 31 33 34 36 38 41 44 Speed Tap Static Pressure Blower Motor Cu...

Страница 40: ...urrent Draw Amps vs External Static pressure in WC 0 1 0 2 0 3 0 4 0 5 0 6 0 7 Low 3 1 3 0 2 9 2 8 2 7 2 6 2 5 ML 3 9 3 8 3 6 3 5 3 3 3 2 3 1 MH 4 8 4 6 4 4 4 2 4 1 4 0 3 8 High 5 7 5 5 5 4 5 2 5 1 5...

Страница 41: ...External Static Pressure in WC 0 1 0 2 0 3 0 4 0 5 0 6 0 7 Low 53 55 57 59 63 71 78 ML 42 44 45 48 51 53 59 MH 35 37 38 40 42 45 49 High 31 33 34 36 38 41 44 Speed Tap Static Pressure Blower Motor Cu...

Страница 42: ...urrent Draw Amps vs External Static pressure in WC 0 1 0 2 0 3 0 4 0 5 0 6 0 7 Low 3 1 3 0 2 9 2 8 2 7 2 6 2 5 ML 3 9 3 8 3 6 3 5 3 3 3 2 3 1 MH 4 8 4 6 4 4 4 2 4 1 4 0 3 8 High 5 7 5 5 5 4 5 2 5 1 5...

Страница 43: ...WC 0 1 0 2 0 3 0 4 0 5 0 6 0 7 Low 63 69 78 88 101 114 132 ML 50 53 56 61 67 73 79 MED 44 46 48 51 54 58 63 MH 37 38 40 41 43 45 47 High 31 32 33 34 35 35 37 Speed Tap Static Pressure Blower Motor Cu...

Страница 44: ...nal Static pressure in WC 0 1 0 2 0 3 0 4 0 5 0 6 0 7 Low 2 4 2 5 2 5 2 6 2 6 2 7 2 7 ML 2 8 2 9 3 0 3 0 3 1 3 1 3 2 MED 3 6 3 7 3 7 3 8 3 8 3 9 3 9 MH 4 2 4 2 4 3 4 3 4 4 4 5 4 5 High 4 8 4 9 5 0 5 0...

Страница 45: ...nused speeds should then be reconnected to the module in the park positions Refer to figure 15 Refer to section II for blower speed and air flow performance for A C installation 5 FIELD WIRING AND REP...

Страница 46: ...SES ADEQUATE DIFFERENTIAL PRESSURE CONTACTS CLOSE CONTROL BOARD ENERGIZED INDUCER ENERGIZED AFTER IGNITOR WARM UP THE GAS VALVE IS ENERGIZED TO OPEN IF FLAME IS NOT DETECTED THE GAS VALVE IS DE ENERGI...

Страница 47: ...PROOF OF FLAME LOSS INDUCER STARTS 5 SECOND POST SURGE AND OPTIONAL HUMIDIFIER ARE DE ENERGIZED THE DELAY TO FAN OFF PERIOD BEGINS 120 SECONDS IF SYSTEM IS IN LOCKOUT THE MODULE WILL RESET ITSELF AFTE...

Страница 48: ...CTIONS Turn off power to furnace before it is placed into service The gas piping system must have been leak tested by a qualified heating contractor in accordance with State Local and National Codes i...

Страница 49: ...as follows 1 Call your gas supplier and ask for the BTU content heating value of one cubic foot of the gas supplied to the installation area An alternate approach is to assume a value of 1025 BTU Cu...

Страница 50: ...s that shown on the rating label if a gas meter is not available for natural gas or the unit is installed on an unmetered propane gas supply Shut off the gas supply to the furnace Remove the pressure...

Страница 51: ...ture rise through the furnace must fall within a range of 40 F to 70 F for CM 50 s and 50 F to 80 F for CM 75 s If the outlet or supply duct temperature is too high you should check to make sure that...

Страница 52: ...t above room temperature calling for heat e When temperatures are reached in furnace at limit control setting with blower out of operation burner should shut off f Shut off electrical power IMPORTANT...

Страница 53: ...ury property damage and may void the limited warranty on the furnace 6 Review with and encourage the user to read the label reproductions and all warnings and instructions in this manual 7 Recommend t...

Страница 54: ...or loosely sealed joints carbon build up Also inspect the outside vent and combustion air terminals and ensure that they are clear and unobstructed 2 CONDENSATE LINE TRAP ASSEMBLY The condensate line...

Страница 55: ...nnect b Clean the coil with a vacuum cleaner by going through the blower pan opening being careful not to bend or damage any of the fins c Once all components are cleaned they must be re installed to...

Страница 56: ...furnace VIII TROUBLESHOOTING NOTICE BEFORE TROUBLESHOOTING FAMILIARIZE YOURSELF WITH THE START UP AND CHECKOUT PROCEDURE ALL INSTALLATION AND SERVICES MUST BE PERFORMED BY QUALIFIED HEATING CONTRACTOR...

Страница 57: ...power to control pushbutton switch pressed or control fault LED steady ON Any color Control hardware fault detected Slow Green flash No call for heat no active errors Slow Orange flash Call for heat...

Страница 58: ...ERLY No CORRECT WIRE CONNECTIONS No Yes Yes No Yes IS THE INDUCER BLOWER OPERATING Yes TROUBLESHOOTING GUIDE THE SYSTEM IS STARTED BY SETTING THE THERMOSTAT TO CALL FOR HEAT THE FOLLOWING SHOULD HELP...

Страница 59: ...CONTROL CHECK THE INTEGRATED CONTROL DIAGNOSTIC LED LAMP RESET BY INTERRUPTING POWER TO CONTROL FOR MORE THAN ONE SECOND IF LED STAYS ON CONTINUOUSLY REPLACE INTEGRATED CONTROL IS THERE VOLTAGE PRESE...

Страница 60: ...CIRCULATING AIR BLOWER TERMINALS CIR N HEAT FOR PROPER VOLTAGE REPLACE THE INTEGRATED CONTROL No No Yes DOES THE CIRCULATING AIR FAN COME ON WHEN ENERGIZED No DOES BLOWER SPIN FREELY No CONFIRM IF EI...

Страница 61: ...AND CORRECT IF NECESSARY DOES BURNER SHUT OFF WHEN THERMOSTAT IS SATISFIED No No No Yes Yes Yes Yes Yes IS LED LIGHT ON INTEGRATED CONTROL FLASHING DOES THE CIRCULATING AIR BLOWER TURN OFF AFTER THER...

Страница 62: ...57 APPENDIX A REPLACEMENT PARTS...

Страница 63: ...58...

Страница 64: ...59...

Страница 65: ...60...

Страница 66: ...61 APPENDIX B WIRING DIAGRAMS...