- 20 -
Poor Temperature
Stability
The System III is designed to maximize heat removal with minimal facility
cooling water requirements. Under conditions of excessive cooling capacity,
instability may result. The condition may be aggravated by :
High temperature setpoint
Low facility water temperature
Small heat load
High facility water pressure
The situation can be remedied by limiting the available facility cooling water.
Facility water pressure can be reduced with a pressure regulator before the
System III. However, excessive restriction of facility water will reduce the
System III's capacity.
Service Assistance
If, after following these troubleshooting steps, your units fails to operate
properly, contact our Service Department for assistance (see Preface, After-
sale Support). Before calling please obtain the following information:
BOM number
Serial number
Voltage of unit
Voltage of power source
Temperature at which the problem occurs
Temperature, pressure and flow rate of cooling water supply
Software Version
Parts List
Our Service Department can provide you with a complete list of spare parts
for your unit (see Preface, After-sale Support). Before calling, please obtain the
following information:
BOM number
Serial number