Thermalec 24THR Скачать руководство пользователя страница 4

 
 
 

Thermalec Products 

– 24THR Instruction Manual (rev 2) 

 

Page 3 of 5 

Overcurrent protection must also be provided in the form of a Miniature Circuit Breaker (MCB).  Due to the 
continuous high load that will be drawn, MCBs should be rated at least 20% higher than of the current shown 
below. 

 
 

 
Specific Electrical Supply 

 

 

15kW 

 

18kW 

 

21kW 

 

24kW 

230V 

– Single Phase (UK) 

 

63 Amps 

75 Amps 

88 Amps 

100Amps 

400V 

– Three Phase (UK) 

 

21 Amps 

25 Amps 

29 Amps 

34Amps 

Two Phase / Split Phase  
 

L1 
L2 

 

31 Amps 
31 Amps 

38 Amps 
38 Amps 

42 Amps 
46 Amps 

50 Amps 
50 Amps 

220V 

– Single Phase (Euro) 

 

68 Amps 

82 Amps 

96 Amps 

109 Amps 

380V 

– Three Phase (Euro) 

 

23 Amps 

27 Amps 

32 Amps 

37 Amps 

 
The size and specification of the cable to the heater should be decided by consulting the regulations stated in 
section 2.  To minimise the effects of volt-drop, the plant room should be located as close as possible to the 
main electrical supply. 

 

The supply cable enters via the removable plate at the back of the heater. The plate should be drilled out to suit 
the size of cable gland used.  Under no circumstances should cable be installed through the metal plate without 
the use of a gland.  To access the terminals, remove the heater cover and the plastic terminal cover.   
 
All 24THR heaters are delivered configured for single-phase operation.  When connecting for single phase 
operation the Line conductor must be connected to the L1 terminal, which is physically larger and can accept 
cables up to 35mm.  The neutral and earth conductors must also be connected to the appropriate terminals. 
 
The heater may be modified for three-phase operation by removing the two brown wires linking the L1, L2 & L3 
terminals.  No modification can be made for split or two phase operation, this must be specifically ordered. 

 

It is vital that all wires are firmly terminated into each terminal; a 6mm spanner should be used to ensure that 
the clamps are pulled firmly down onto the incoming cable ends. Ensure that the cable is of sufficient diameter 
to ensure a good clamp is made and, if required, wind a length of copper strand around the other strands to 
increase the diameter.  After termination, check all the cables for tightness and replace both sets of covers. 
 
The heater will not operate without a pump interlock supply that switches 230V ON when the filter pump is 
running.  The live of this supply should be connected to terminal A and the neutral to terminal B of the heater.  
The supply must be taken from the last device switching the pump to ensure that the heater will switch off at 
the same time as the filter pump. 
 
This pump interlock supply can also be used to further control the operation of the heater.  A timeswitch can be 
fitted to interrupt the supply to terminal A; ensuring that it can only come on during specific periods of cheap 
electricity.  This is detailed on drawing APH 1319, together with arrangements for an override switch allowing 
the filter pump to be run continuously. 
 
Thermalec also produce a range of Pool Control Panels, which enable pumps, heating and all other pool items 
to be controlled from a single control box.  All panels are made to order, to match the specific equipment.  
Please contact the Sales office for more details. 

 
 

COMMISSIONING 

When using the heater for the first time (or after it has been isolated for the winter) it is vital that the heater is  
commissioned using the correct procedure.  

Failure to do so will result in serious damage to the heater.

 

g)  Check heater circuit breakers are all OFF; 

h)  Check main power supply  is OFF; 

i) 

Check filter pump is OFF; 

j) 

Check heater drain valve is closed; 

Отзывы: