installed in this line from the boiler to point
of discharge.
The condensate drain trap should be flushed
with water as part of your boiler maintenance
schedule to remove any debris that might
have accumulated over time.
A common condensate pump/sump may be
used. Run separate piping from each
condensate drain to the sump. A common
drain may be used to discharge condensate
from the sump. Consult pump/sump
materials of construction. If a common sump
is used, individual drain lines should be
connected such that one drain cannot back
feed into another drain. Use Table 2 for
sizing the pump / sump.
Table 2: Typical Condensate Flow Rate
Model
Max Condensate Flow (gph)
ARC1000
7
ARC1500
10.5
ARC2000
16
ARC2500
21.5
ARC3000
27
Consult local authorities regarding disposal of
flue gas condensate into public waste water
system. Some jurisdictions require that
condensate be buffered before discharge. This
buffering is commonly achieved by draining
the condensate through a limestone bed.
Consult Thermal Solutions or a chemical
treatment company for buffering system.
CAUTION
Failure to properly pipe the condensate
system will greatly reduce boiler life. Do
not install plugs, caps, or valves on
condensate piping.
Do not manifold boiler condensate and
vent drains together.
Do not crimp condensate lines or reduce
drain line inner diameter size.
3.2.5.1
ARC1000 Condensate Drain Trap
Ensure that the condensate drain trap is filled
with water prior to running the boiler to
prevent flue gas emission to the boiler room.
It is recommended that the personnel
responsible for running and maintaining the
boiler periodically check the water level in the
condensate drain trap bend, especially, when
the boiler is operating in a non-condensing
condition for an extended period of time.
Figure 4: ARC 1000 Condensate Drain
Trap
1. Union Connection to the boiler
condensate drain line
2. Removable cleaning plug
3. Condensate drain outlet connection
3.2.5.2
ARC1500 – 3000 Condensate Drain
Trap