Thermal Edge NE050 Series Скачать руководство пользователя страница 10

                                                                                                      

 

1751 Hurd Drive ● Irving, Texas 75038 ● (972) 580-0200 ● (888) 580-0202 ● Fax (972) 580-0277 

URL:  www.thermal-edge.com ● Email:  

[email protected]

 

SP-ENG-210-000-07 Rev 2.9        

10 

|

 

P a g e

                                                                                   

Options 

 

The NE050, NE060 & NE080 Series Air Conditioners may be ordered with the following options.  
Review the list below for the specifications and functions of the option(s) that apply to your unit. 
 
Built-in Heater 
 
This unit is configurable to include a Built-in Heater to increase the temperature of your enclosure in 
lower temperature conditions.  The digital controller is programmed with an individual heater set point 
to maintain your enclosure at your desired operating temperature.  
 
Heater capacities are available in 500 Watt and 1000 Watt. 

 
 

 

Default Settings: 

 

55°F Heat Set Point

 

 

3°F Differential

 

 
At the default settings the heater turns on at 52°F and operates until temperature has reached 55°F.  
Refer to Digital Temperature Controller Programming section for details on changing these 
parameters. 
 
Low Ambient 
 
This option consists of circuitry to protect the compressor in a low ambient temperature environment.  
The low ambient package is designed to provide an optimum constant low current in the compressor 
motor during the non cooling state.  This option provides internal heat to the compressor to protect it 
from stalls and hard starts during long periods of compressor off state. 
 
Dry Contact 
 
This option provides an early warning capability to your enclosure to aid in the protection of your 
expensive equipment.  The Dry Contact is programmed with an individual dry contact set point to 
monitor the enclosure temperature limit that you require.  When the enclosure temperature has 
exceeded the maximum limit, the Form C gold plated contact will activate to notify you that there is a 
problem in achieving your cooling set point. 
 

 

 

Default Settings: 

 

105°F Dry Contact High Temperature Alarm Set Point

 

 

2°F Recovery Differential

 

 

3min Temperature Alarm Delay

 

 

 
At the default settings the Dry Contact initial conditions are normally open and/or normally closed.  
When the unit is powered on and the temperature exceeds 105°F for a period longer than 3 minutes 
the Dry Contact will activate. At this time the normally open contact will close and the normally closed 
contact will open. This state will remain until the temperature has decreased to 103°F.   
 

Note:

 

The dry contact is not a power status indicator, rather a high temperature alarm alerting you that 

the unit is unable to meet the cooling set point.

 

 

Содержание NE050 Series

Страница 1: ...User Technical Manual NE050 NE060 NE080 Series Rev 2 9...

Страница 2: ...Slotnick Update Adjustable Temperature Probe length 2 3 04 03 14 B Slotnick Update email address 2 4 08 04 14 B Slotnick Delete Celsius programming flash drive key 2 5 01 22 15 B Slotnick Update produ...

Страница 3: ...Moving the Air Conditioner 5 Unit Label 5 Operation 6 Preliminary Testing 6 Mounting the Air Conditioner 7 Unit Specifications 8 Options 10 System Faults 13 Digital Temperature Controller Programming...

Страница 4: ...Inspecting the Equipment Thermal Edge air conditioning equipment is designed manufactured and packed to prevent damage from normal handling shock and vibration during shipment It is necessary to insp...

Страница 5: ...ree angle rotary compressors without damaging the compressor If air conditioner is to be shipped or transported at any time pack in original packaging and strap to pallet to prevent damage Air conditi...

Страница 6: ...ith a Condensate Removal System that changes the excess humidity liquid into a vapor which is then vented to the atmosphere In the event of excess water vapor where the enclosure door has been left op...

Страница 7: ...ount the air conditioner high on the enclosure in order to cool the hot air in the top of the enclosure Position the unit where the cold air can circulate across the width of the enclosure to cool it...

Страница 8: ...Model Operating Voltage Range Volts Inrush Current Start Up Current Amps Loading Current Running Current Amps SCCR Short Circuit Current Rating Amps Recommended Fuse Selection Amps KVA Rating Refriger...

Страница 9: ...ting 8 000 BTUH Standard Maximum Ambient 125 F Unit Weight 120VAC 102lbs 230VAC 103lbs 480VAC 142lbs Model Operating Voltage Range Volts Inrush Current Start Up Current Amps Loading Current Running Cu...

Страница 10: ...optimum constant low current in the compressor motor during the non cooling state This option provides internal heat to the compressor to protect it from stalls and hard starts during long periods of...

Страница 11: ...Watt 650 Watt 950 Watt Default Settings 55 F Heat Set Point 3 F Differential At the default settings the heater output turns on at 52 F and operates until the temperature has reached 55 F Refer to Ad...

Страница 12: ...y specific location of your enclosure Ethernet IP Controller Output This option provides the ability to communicate with the Thermal Edge Air Conditioner controller via the Ethernet IP protocol You ca...

Страница 13: ...time delay A thermal overload protects the compressor against faults In the event that the snowflake status LED is not flashing on the display and the compressor is not running an internal fault may...

Страница 14: ...ey to display its value 4 Use the UP or DOWN arrow key to change its value 5 Press SET to store the new value and move to the following parameter To exit Press SET UP arrow keys or wait 15 seconds wit...

Страница 15: ...min start up delay No Output 2 HA2 Condenser High Temperature Alarm P2 145 F for 3 minutes Compressor Off 2 LA2 Condenser Low Temperature Alarm P2 50 F for 3 minutes No Output 2 CA Evaporator Coil Al...

Страница 16: ...recommended to enhance air filter efficiency Replacement filters are readily available from THERMAL EDGE Customer Service DO NOT operate the air conditioner without the air filter Such operation will...

Страница 17: ...C Compressor Thermal Overload NE050 31530 2 for 120VAC 31011 2 for 230VAC 480VAC NE060 31020 2 for 120VAC 31011 2 for 230VAC 480VAC NE080 31020 2 for 120VAC 31025 2 for 230VAC 480VAC Gasket Installati...

Страница 18: ...s on position ON OFF Toggle Switch then Retry Verify input power meets voltage requirements as shown in the UL label YES If problem is still present contact technical support Unit Overheats Insufficie...

Страница 19: ...sor Use meter 3 Check for faulty evaporator fan 3 Measure Temperature at Evaporator Verify Heat Load Requirements Is unit capacity adequate for internal head load Possible low refrigerant Is compresso...

Страница 20: ...ind controller CA YES NO Check Low Pressure Switch Connections and Verify Pressure switch is closed Use meter 3 P1 or P2 NO YES Check probe connections potential faulty probe LA LA2 HA HA2 YES Refer t...

Страница 21: ...g e Physical Dimensions Water overflow excessive Check drain is it plugged YES NO Clean condensate pan and drain add 1 tbsp bleach to upper pan monthly to kill mold Is Air Conditioner sealed against...

Страница 22: ...1751 Hurd Drive Irving Texas 75038 972 580 0200 888 580 0202 Fax 972 580 0277 URL www thermal edge com Email support thermal edge com SP ENG 210 000 07 Rev 2 9 22 P a g e...

Страница 23: ...al edge com SP ENG 210 000 07 Rev 2 9 23 P a g e Electrical Schematics System Schematic Digital Controller Schematic Note Schematics apply to all voltages optional accessories wiring not provided in t...

Страница 24: ...repair or replacement of its own product This Warranty does not cover Labor or reimbursement of labor for evaluation removal installation repair or cost of any warranted part except at the Thermal Ed...

Страница 25: ...ddress Shipping method Pack unit in a suitable packing for shipment preferably the original packaging if available If suitable packing is not available arrange for packaging to be shipped to you Air C...

Страница 26: ...ower wires to air conditioners equipped with a Wago power terminal block 1 Remove cover from chassis using T25 Torx bit 2 The sequence of the connecting the wires is from LEFT TO RIGHT 3 Connect each...

Отзывы: