Troubleshooting Guide 

 

 

The following guide provides a flow chart to identify a problem, determine the root cause and identify  
the action needed to correct an issue. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Unit Will Not Run 

Is Unit 

Connected? 

YES 

 NO 

Please Connect 

Power 

Verify Power On/Off 

Switch is on position 

ON 

 OFF 

Toggle Switch 

then Retry 

Verify input power 

meets voltage 

requirements as 

shown in the UL label 

 YES 

If problem is still present contact 

technical support 

Unit Not Cooling 

Is Compressor 

On? 

YES 

 NO 

Is evaporator 

Fan on? 

YES 

 NO 

Measure Temperature at Evaporator 

& Verify Heat Load Requirements.  Is 

unit capacity adequate for internal 

head load? Possible low refrigerant. 

Unit Overheats / 
Insufficient Cooling 

Is Filter 

Clean? 

 NO 

Clean / Replace 

Filter 

YES 

Are Condenser & 

Evaporator Fans ON? 

 NO 

Check for Faulty 

Fan & replace 

YES 

Is Condenser 

Coil dirty? 

 YES 

Clean Coil 

 NO 

 NO 

Is Evaporator Coil 

Frozen / Iced? 

 YES 

Potential Bad 

Evaporator Fan, 

check for faulty 

fan. 

 NO 

Contact Qualified Refrigeration Service 

Technician to check Refrigerant Pressure.  Unit 

may have a refrigeration leak.  If problem is not 

resolved contact technical support. 

Содержание NE010 Series

Страница 1: ...User Technical Manual NE010 NE015 50 Hz Series Rev 1 9...

Страница 2: ...y unit specifications 1 7 02 19 19 B Slotnick Updated mounting instructions alarm settings RMA procedure 1 8 04 04 19 B Slotnick Added neutral power designation to schematic 1 9 06 19 19 B Slotnick Up...

Страница 3: ...4 Moving the Air Conditioner 5 Unit Label 5 Operation 6 Preliminary Testing 6 Mounting the Air Conditioner 7 Unit Specifications 8 Options 10 System Faults 13 Digital Temperature Controller Programmi...

Страница 4: ...pment Thermal Edge air conditioning equipment is designed manufactured and packed to prevent damage from normal handling shock and vibration during shipment It is necessary to inspect your equipment u...

Страница 5: ...l panel and wiring and to prevent personal injury assure that the power source is compatible with the equipment before operating When recharging refrigeration type and amount must be the same as shown...

Страница 6: ...proper circuit protection sizing Connect a power source to the air conditioner and turn on the power switch The evaporator fan will start and the digital controller will power up If cooling is called...

Страница 7: ...from inside the enclosure use the fasteners supplied to attach the air conditioner to the enclosure Screw all fasteners hand tight Then torque to 96 in lbs These fasteners should be checked periodical...

Страница 8: ...s SCCR Short Circuit Current Rating Amps Recommended Fuse Selection Amps KVA Rating Refrigerant Type Refrigerant Amount ounces Low High Unit Pressures psi NE010105 90 110 12 1 2 3 2 4 Amp Class CC CCM...

Страница 9: ...VA Rating Refrigerant Type Refrigerant Amount ounces Low High Unit Pressures psi NE015105 90 110 12 2 2 4 2 4 Amp Class CC CCMR Time Delay 0 3 R134a 7 75 76 178 NE015205 180 220 11 6 1 9 2 7 Amp Class...

Страница 10: ...Contact is programmed with an individual dry contact set point to monitor the enclosure temperature limit that you require When the enclosure temperature has exceeded the maximum limit the Form C gol...

Страница 11: ...onditioners have a Special Programming option for selecting unique pre in programmed settings for special requirements Although most parameters are accessible in our digital controller this option all...

Страница 12: ...refer to the Ethernet IP Option Specifications included with the Air Conditioner Remote Controller When having our Programmable Digital Controller mounted on the face of our Air Conditioner does not...

Страница 13: ...thermal overload protects the compressor against faults In the event that the snowflake status LED is not flashing on the display and the compressor is not running an internal fault may have occurred...

Страница 14: ...lue 5 Press SET to store the new value and move to the following parameter To exit Press SET UP arrow keys or wait 15 seconds without pressing a key Note The set value is stored even when the procedur...

Страница 15: ...mperature Alarm P2 171 F for 3 minutes Compressor Off 2 LA2 Condenser Low Temperature Alarm P2 50 F for 3 minutes No Output 2 CA Evaporator Coil Alarm Low Pressure for 2 minutes Compressor Off 2 noP I...

Страница 16: ...to enhance air filter efficiency Replacement filters are readily available from THERMAL EDGE Customer Service DO NOT operate the air conditioner without the air filter Such operation will allow the co...

Страница 17: ...ture Probe Mounting Clip 52126 250C Thermal Expansion Value TXV 32023 1 Compressor 31511 1 for 100VAC 31512 1 for 200VAC Gasket Installation Kit 71300 N115 Evaporator Fan NE010 41003 1 1 for 100VAC 41...

Страница 18: ...the UL label YES If problem is still present contact technical support Unit Not Cooling Is Compressor On YES NO Is evaporator Fan on YES NO Measure Temperature at Evaporator Verify Heat Load Requireme...

Страница 19: ...1 or P2 YES NO Check contactor circuit Does it have power 3 NO YES Refer to Alarm Signals in Digital Temperature Controller Programming Section Contact Customer Support NO YES Verify contact coil is b...

Страница 20: ...ical specification Verify proper recommended fuse has been selected Check compressor if excess heat present compressor may be faulty Contact Technical Support Water overflow excessive Check drain is i...

Страница 21: ...1800 Hurd Drive Irving Texas 75038 972 580 0200 888 580 0202 Fax 972 580 0277 URL www thermal edge com Email support thermal edge com SP ENG 210 001 09 Rev 1 9 21 P a g e Physical Dimensions...

Страница 22: ...1800 Hurd Drive Irving Texas 75038 972 580 0200 888 580 0202 Fax 972 580 0277 URL www thermal edge com Email support thermal edge com SP ENG 210 001 09 Rev 1 9 22 P a g e...

Страница 23: ...G 210 001 09 Rev 1 9 23 P a g e Electrical Schematics System Schematic Digital Controller Schematic Note Schematics apply to all voltages optional accessories wiring not provided in this document If y...

Страница 24: ...y in Dallas Texas Use of equipment for other than its designed purpose or operating conditions Operation in harsh oily corrosive or other abnormal environmental conditions without the proper filtratio...

Страница 25: ...Number Serial Number Customer name and contact info email phone number and address Shipping method Pack unit in a suitable packing for shipment preferably the original packaging if available Air Cond...

Страница 26: ...connect the wires by inserting them into the lower receptacles located on the front of connector in the following order NOTE If using stranded wires it may be difficult to insert into the receptacles...

Отзывы: