31
Figure 36 - Double Discharge Riser
Note: Discharge line sizing shown in Table 7 and Table 8 are listed per circuit and applies where leaving water
temperature (LWT) is 40°F or higher. For applications where LWT is below 40°F, size lines using the ASHRAE
Refrigeration Handbook or other suitable design guide.
Table 7 - Horizontal or Downflow Discharge Line Sizes for R410A (inches OD)
Circuit
Tons
Total Equivalent Length (Ft)
25
50
75
100
125
150
175
200
225
250
275
300
5
⅝
⅝
⅝
⅝
¾
¾
¾
¾
¾
¾
¾
⅞
7½
⅞
⅞
⅞
⅞
⅞
⅞
⅞
⅞
⅞
⅞
⅞
⅞
10
⅞
⅞
⅞
⅞
⅞
⅞
⅞
1⅛
1⅛
1⅛
1⅛
1⅛
15
⅞
⅞
1⅛
1⅛
1⅛
1⅛
1⅛
1⅛
1⅛
1⅛
1⅜
1⅜
20
⅞
1⅛
1⅛
1⅜
1⅜
1⅜
1⅜
1⅜
1⅜
1⅜
1⅝
1⅝
25
1⅛
1⅛
1⅛
1⅛
1⅜
1⅜
1⅜
1⅜
1⅜
1⅜
1⅝
1⅝
30
1⅛
1⅛
1⅛
1⅜
1⅜
1⅜
1⅜
1⅜
1⅜
1⅝
1⅝
1⅝
35
1⅜
1⅜
1⅜
1⅝
1⅝
1⅝
1⅝
2⅛
2⅛
2⅛
2⅛
2⅛
40
1⅝
1⅝
1⅝
1⅝
1⅝
1⅝
2⅛
2⅛
2⅛
2⅛
2⅛
2⅛
Table 8 - Upflow Discharge Line Sizes for R410A (inches OD)
Circuit
Tons
Total Equivalent Length (Ft)
25
50
75
100
125
150
175
200
225
250
275
300
5
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
B - ½
B - ½
B - ½
B - ½
B -⅝
B -⅝
B -⅝
B -⅝
B -⅝
B -⅝
B -⅝
B - ¾
7½
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
B - ¾
B - ¾
B - ¾
B - ¾
B - ¾
B - ¾
B - ¾
B - ¾
B - ¾
B - ¾
B - ¾
B - ¾
10
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
B - ¾
B - ¾
B - ¾
B - ¾
B - ¾
B - ¾
B - ¾
B - ⅞
B - ⅞
B - ⅞
B - ⅞
B - ⅞
15
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ⅜
A - ½
A - ½
B - ¾
B - ¾
B - ⅞
B - ⅞
B - ⅞
B - ⅞
B - ⅞
B - ⅞
B - ⅞
B - ⅞
B - 1⅛ B - 1⅛
20
A - ⅜
A - ⅜
A - ⅜
A - ½
A - ½
A - ½
A - ½
A - ½
A - ½
A - ½
A - ⅝
A - ⅝
B - ¾
B - ⅞
B - ⅞
B - 1⅛ B - 1⅛ B - 1⅛ B - 1⅛ B - 1⅛ B - 1⅛ B - 1⅛ B - 1⅜ B - 1⅜
25
A - ⅜
A - ⅜
A - ⅜
A - ½
A - ½
A - ½
A - ½
A - ½
A - ½
A - ½
A - ⅝
A - ⅝
B - ⅞
B - ⅞
B - ⅞
B - 1⅛ B - 1⅛ B - 1⅛ B - 1⅛ B - 1⅛ B - 1⅛ B - 1⅛ B - 1⅜ B - 1⅜
30
A - ½
A - ½
A - ½
A - ¾
A - ¾
A - ¾
A - ¾
A - ¾
A - ¾
A - ¾
A - ¾
A - ¾
B - ⅞
B - ⅞
B - ⅞
B - 1⅛ B - 1⅛ B - 1⅛ B - 1⅛ B - 1⅛ B - 1⅛ B - 1⅜ B - 1⅜ B - 1⅜
35
A - ¾
A - ¾
A - ¾
A - ¾
A - ¾
A - ¾
A - ¾
A - ¾
A - ¾
A - ¾
A - ¾
A - ¾
B - 1⅛ B - 1⅛ B - 1⅛ B - 1⅜ B - 1⅜ B - 1⅜ B - 1⅜ B - 1⅝ B - 1⅝ B - 1⅝ B - 1⅝ B - 1⅝
40
A - ¾
A - ¾
A - ¾
A - ¾
A - ¾
A - ¾
A - ¾
A - ¾
A - ¾
A - ¾
A - ¾
A - ¾
B - 1⅜ B - 1⅜ B - 1⅜ B - 1⅜ B - 1⅜ B - 1⅜ B - 1⅝ B - 1⅝ B - 1⅝ B - 1⅝ B - 1⅝ B - 1⅝
A
B
REDUCING
TEE
FROM
CHILLER
PITCH TO
CONDENSER
45 DEGREE
STREET ELBOWS
90 DEGREE
STREET ELBOWS