EXCEL-ARC 500, 6045
3-4
August 22, 2005
3.05 Welding Leads
Use Table 3-2 for selection of the proper size copper welding leads.
50 Feet
(15.2 M)
100 Feet
(30.5 M)
150 Feet
(45.7 M)
200 Feet
(61.0 M)
250 Feet
(76.2 M)
100
#4
#4
#4
#3
#2
150
#3
#3
#2
#1
#1/0
200
#2
#2
#1
#1/0
#2/0
250
#1
#1
#1/0
#2/0
#3/0
300
#1/0
#1/0
#2/0
#3/0
#4/0
350
#1/0
#1/0
#3/0
#4/0
#4/0
400
#2/0
#2/0
#3/0
#4/0
2 — #2/0
450
#2/0
#2/0
#4/0
2 — #2/0 2 — #3/0
500
#3/0
#3/0
#4/0
2 — #2/0 2 — #3/0
TOTAL LENGTH OF LEAD CIRCUIT IN FEET (AND METERS)
(ELECTRODE LEAD PLUS WORK LEAD)
Welding Current
Amperes
Table 3-2: Length of Lead Circuit
* For 60% duty cycle
NOTE
Lead size shown is for 90°C cable insulation, 30°C (86°F) ambient, and not over 4.5 volts lead drop.