
Page 1
INSTALLATION INSTRUCTIONS
VENTILATOR CUSTOM KIT
MODEL VCK1
PLEASE READ ENTIRE INSTRUCTIONS BEFORE PROCEEDING.
IMPORTANT:
Save these instructions for the Local Electrical Inspector’s use.
INSTALLER:
Please leave these Installation Instructions with this unit for the owner.
OWNER:
Please retain these instructions for future reference.
WARNING - TO REDUCE THE
RISK OF FIRE, ELECTRIC
SHOCK, OR INJURY TO PER-
SONS, OBSERVE THE FOLLOW-
ING:
A. Installation Work and Electri-
cal Wiring Must Be Done By
Qualified Person(s) In Accor-
dance With All Applicable
Codes & Standards, Including
Fire-Rated Construction.
and the local code authorities.
C. When cutting or drilling into
wall or ceiling, do not damage
electrical wiring and other
hidden utilities.
D. Ducted fans must always be
vented to the outdoors.
“WARNING”
To Reduce The Risk
Of Fire, Use Only Metal Ductwork.
IMPORTANT SAFETY INSTRUCTIONS
READ AND SAVE THESE INSTRUCTIONS
B . The combustion airflow
needed for safe operation of
fuel-burning equipment may
be affected by this unit’s
operation. Follow the heating
equipment manufacturers
guideline and safety standards
such as those published by
the National Fire Protection
Association (NFPA), and the
American Society for Heating,
Refrigeration and Air Condi-
tioning Engineers (ASHRAE),
➛
➛
7-7/8"
➛
9-1/8"
➛
➛
1/2"
12-7/8"
22"
26-15/16"
➛
➛
➛
➛
➛
➛
➛
➛
7/8"
3/4"
1-29/32"
9"
➛
➛
10-1/2"
➛
➛
➛
➛
18-3/16"
➛
➛
➛
9-5/16"
4-1/8"
FRONT VIEW
➛
Mounting
Surface
8-5/8"
TOP VIEW
➛
➛
➛
➛
➛
➛
Recommended for use over conventional gas and electric ranges and
cooktops.
When more than one cooking appliance is installed under a single hood two
(2) Ventilator Control Housings (Filters) should be installed, and centered
over each cooking appliance.
A separate ventilator must be used with each Ventilator Control Housing.
Use Ventilator Custom Kit in any custom hood or standard kitchen cabinet.
NOTES
: Items packed inside the carton are as follows:
2 - Eye-saving T bulbs (60 watts)
2 - Chrome Light Reflectors with 2 attachment screws
4 - Mounting Screws
COLD WEATHER
installations should have an additional backdraft damper
installed to minimize backward cold air flow and a non-metallic thermal
break to minimize conduction of outside temperatures as part of the duct
work. The damper should be on the cold air side of the thermal break. The
break should be as close as possible to where the ducting enters the heated
portion of the house.
◆
!
CAUTION:
VENT UNIT TO THE OUTSIDE.
Fig. 1
➛
➛
3-1/4"
➛
➛
➛ ➛
5-3/16"