The preferred method of installation is to create a separate 
return for the Ultra-Aire 65H in a central area of the structure. 
Duct the supply of the Ultra-Aire 65H  to the air supply of the 
existing HVAC system. 

4.4E Installation in a Structure with No Existing Forced 

Air HVAC System 

When installing the Ultra-Aire 65H in a structure that does 
not have a forced air HVAC system, a single return for the 
Ultra-Aire 65H should be installed in central open area of 
the structure. DO NOT locate the return in a bathroom or a 
kitchen. The supplies of the Ultra-Aire 65H should be located 
in the remote areas of the structure (such as bedrooms, 
den, etc.). By ducting this way, the air inside the structure 
will circulate through the Ultra-Aire 65H to be filtered 
and dehumidified. A 6" diameter duct is recommended 
for branches to the bedrooms. A 8" diameter duct is 
recommended for branches to larger areas.

4.4F Ducting for High Efficiency Filtration 

The Ultra-Aire 65H is equipped with a high efficiency MERV 
11 media filter (P/N 4027158). For optimal performance it is 
recommended that the filter be replaced every 3-6 months. 

4.5 Noise Abatement 

A length of 10 feet or more of  flex ducting on the outlet of 
the Ultra-Aire 65H will reduce air noise from the fan. A length 
of flexible ducting on all Ultra-Aire 65H duct connections is 
recommended to reduce noise transmitted to rigid ductwork 
in the structure. 

CAUTION 

Replacing the filter requires the return duct to be 

removed. Failure to use flex duct will prevent filter 

access. Three feet of flex duct should be adequate to 

access the filter.

4.6 Controls 

All control panels should be mounted in a central area of the 
4. Controls

The Ultra-Aire can be equipped with various accessories to 
enhance its operation. A remote control must be used with 
the Ultra-Aire. ThermaStor offers the DEH 3000 proprietary 
controller. The DEH 3000 allows homeowners the ability to 
monitor and control relative humidity levels in their home. 
This control is also offered witha remote sensing option.

WARNING: 

DO NOT 

allow the yellow lead from 

the unit to contact the red lead or the white lead from 
the unit or damage to the transformers will result. 

The UA dehumidifier is controlled using five color-coded wires.

Green (or brown)

 = Fan control

Blue 

= Dehumidification (fan and compressor) control

Red

 = 24volt AC power transformer neutral side (common with white)

White 

= 24volt AC power transformer neutral side (common with red)

Yellow

 = transformer high side 

Between the red/white lead and the yellow leads is a 40VA trans-
former. This low voltage power source powers the relay coils which 
control the fan and compressors. This 24VAC transformer can also 
be used to power HVAC assessories external to the dehumidifier.
•  To turn the dehumidifier on make contact between yellow and 

blue wires.

•  To turn the fan on make contact between yellow and green(or 

brown) wires.

•  To power an HVAC accessory, connect the accessory to the 

white (or red) wire and the yellow wire.

FOR HVAC INSTALLER ONLY

7

Ultra-Aire 65H Installer’s & Owner’s Manual

(P/N 4028539; with remote: P/N 4028407)

Содержание Ultra-Aire 65H

Страница 1: ...tandard MERV 14 optional n Compact design n 5 year warranty P O Box 8680 Madison WI 53708 TOLL FREE 1 800 533 7533 www thermastor com sales thermastor com TS 422c INSTALLER S OWNER S MANUAL HVAC INSTA...

Страница 2: ...4D Installation in an Attic 6 4 4E Installation in a Structure with No Forced Air HVAC System 7 4 4F Ducting for High Efficiency Filtration 7 4 5 Compressor Release and Noise Abatement 7 4 6 Controls...

Страница 3: ...edrooms den utility room or family room The ductwork of the existing heating system can be used to supply air to the home 2 Registrations The Ultra Aire 65H conforms to UL STD 474 and CSA Standard C22...

Страница 4: ...al electrical codes for any further information Therma Stor LLC offers a family of control devices for use with the Ultra Aire 65H The controls are to be located remotely from the unit and located in...

Страница 5: ...he isolated areas of the home like the bedrooms den utility room or family room The ductwork of the existing heating system can be used to supply air to the home If the existing supply goes to isolate...

Страница 6: ...stallation Install a separate 8 return for the Ultra Aire 65H in a central area of the structure Optional Duct the supply of the Ultra Aire to a 8 x 8 x 8 tee damper adjusted to 20 open to the basemen...

Страница 7: ...es the return duct to be removed Failure to use flex duct will prevent filter access Three feet of flex duct should be adequate to access the filter 4 6 Controls All control panels should be mounted i...

Страница 8: ...8 Ultra Aire 65H Installer s Owner s Manual ATTENTION INSTALLER...

Страница 9: ...ncy and may cause the compressor to cycle off and on unnecessarily on the defrost control DO NOT operate the unit without a filter or with a less effective filter Operating the unit without a filter o...

Страница 10: ...Optional Parts List Ultra Aire 65H Indoor Air Quality System Part No Description 4027158 Filter MERV 11 4028085 Pump Kit 4028111 Hang Kit 4023647 8 Gravity Damper 4020646 8 Butterfly Damper 4027415 8...

Страница 11: ...66 Defrost Timer 4027149 Indicator Light 4027151 Overflow Switch 4027161 Transformer FOR HOMEOWNER ROUTINE MAINTENANCE Part No Description 4027158 Air Filter MERV 11 4027422 4 Pack 4027427 12 Pack The...

Страница 12: ...t to a high pressure and temperature 10 2 Troubleshooting Neither fan nor compressor running Dehumidification is being called for No fan call 1 Unit unplugged or no power to outlet 2 Humidity control...

Страница 13: ...a new charge must be accurately weighed in If any of the old charge is left in the system it must be recovered before weighing in the new charge Refer to the unit nameplate for the correct charge wei...

Страница 14: ...y Range Accuracy 10 95 RH 5 Auxillary Relay Capacity 5 Amps 24VAC Temp Range Accuracy 30 90 F 2 Size 4 95 L x 1 06 W x 4 19 H Major Operations n Digital control of Relative Humidity Digital Set Point...

Страница 15: ...sts related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsibili...

Страница 16: ...n any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2008 Therma Stor LLC All rights reserved PO Box 8680 Madison WI 53708 Phon...

Отзывы: