1. Specifications
Part Number:
4029410
Power:
1.8 full load amps, 120 V / 60Hz
Blower:
950 CFM
Temperature
Set Point Range:
40ºF to 180ºF
Filter Box
(Option):
Filter Size: 16” X 16” X 2”
Hydronic
Connections:
3/4” ISO 7241 Series B couplings
Duct
Inlet: 16” Flex-Duct
Connections:
Supply: 14” Lay Flat-Duct
Warranty:
1 Year Parts and Labor
Dimensions:
Unit
Shipping
Width
20.25”
24”
Height
40”
45.25”
Depth
21.375”
25.5”
Weight
85 lb
110 lb
2. Operation
2.1 Transporting
The Phoenix Aquadry TX 80 may be transported and
operated upright or on its back. The unit features a high-
impact plastic skid plate which protects the unit while
navigating obstacles such as curbs, stairways, and while
loading into vehicles.
2.2 Electrical Requirements
The Phoenix Aquadry TX 80 requires 120VAC and features
a standard 120VAC inlet receptacle with ground. When
properly connected to a grounded outlet, it provides a
ground connection through the user-supplied cord in order
protect the operator from electric shock. Ensure that the
supply cord used is a 2-conductor with ground and that it
has no nicks or cuts in the insulation. The electrical inlet
is designed to accept a NEMA 5-15R (receptacle - 15 amp,
2 pole + ground).
2.3 Power Switch and Thermostat
Master POWER Switch: The master power switch located
on the side of the Phoenix Aquadry TX 80 can be used to
turn the unit ON, OFF.
When set to ON, the Phoenix Aquadry TX 80 will energize
the blower.
Temperature set point can be set by
using a flat-bladed screwdriver. The thermostat will
control only the blower motor - not the glycol fluid -
so the unit may be hot even when the blower is not
energized.
The blower will cycle on and off as needed to
maintain the selected temperature.
2.4 Glycol Line Connections
Hydronic (hot water/propylene glycol) connections are
made using 3/4 inch couplings that comply with the ISO
7241 Series B standard. These couplers minimize the
fluid loss on disconnection – but there is a small amount
lost (~1 tablespoon/16cc). The Phoenix Aquadry TX 80
has been designed to direct this loss away from the fan
inlet.
Ensure that the hydronic pump is off before attempting
connection of the hydronic couplers.
Heat transfer fluid temperatures can approach 200°F
(93C). Use gloves when handling hot couplers and working
around the unit’s hot surfaces.
2.4 Ducting
The Phoenix Aquadry TX 80 can be ducted at the
inlet, the outlet or both. The Phoenix Aquadry TX 80
comes equipped with a snap ring on the outlet that
accommodates 14” lay-flat duct. By adding the optional
ductable filter box assembly, 16” flex duct can be used
on the inlet. When ducting the TX 80, care must be taken
to ensure airflow is not choked off due to kinks or sharp
bends in the duct.
3 Maintenance
3.1 Cleaning
Coils should be checked periodically to ensure they are
free of dirt and debris. Remove debris from coil with
compressed air (preferred method). If coils become
contaminated, they can be washed down with water and
blown dry with compressed air.
If the Phoenix Aquadry TX 80 is operated in dirty
environments, the optional air filter kit should be installed
on the intake of the machine.