2022-05-16_309711 01
Manual for Training Case
KNX & KNX Programming
with ETS
Страница 1: ...2022 05 16_309711 01 Manual for Training Case KNX KNX Programming with ETS ...
Страница 2: ...3 4 Proper use 8 3 5 Cleaning device 8 4 The KNX bus system 9 4 1 How did KNX originate 9 4 2 What is a KNX system 9 4 3 KNX devices 10 4 4 What can KNX be used for 11 4 5 ETS software 11 4 6 KNX Secure 13 5 KNX devices used in the case 15 5 1 System devices 15 5 2 Terminal devices 16 6 Start up 28 6 1 KNX IP connection 28 6 2 XLR connection 28 6 3 Actual start up 29 7 Resetting devices to factory...
Страница 3: ...ng case KNX 3 1 Further information on Theben KNX is available at Further information on Theben KNX is available at https www theben de The functions of the operating controls of individual devices are described in the operating instructions provided at https www theben de ...
Страница 4: ...Case views Manual for the training case KNX 4 2 Case views ...
Страница 5: ...Case views Manual for the training case KNX 5 2 1 Case lid showing rooms functions 2 2 Case base with view of devices ...
Страница 6: ...igned with two hinges that lock into place so that the lid cannot fall down if someone inadvertently touches or knocks the case as they walk past thereby preventing people from being injured when they are working with the case Plug the power cable firmly and securely into the IEC socket inside the case The case is equipped with an internal fuse 1 25 A T right next to the IEC socket which can also ...
Страница 7: ...n Observe operating instructions Installations system extensions must not be carried out by LEARNING USERS 3 3 Technical Data Operating voltage 230 V AC 50 Hz 10 15 Input power 140 mA 23 W Ambient temperature 5 C 45 C Protection rating IP 40 Pollution degree 2 Protection class I if the device is used in a manner not specified by the manufacturer the protection provided by the device may be impaire...
Страница 8: ...ining case KNX 8 3 4 Proper use The case may only be used inside buildings may only be used at altitudes up to 2000 m may only be used in environments with a relative humidity up to 80 RH non condensing 3 5 Cleaning device Only clean the training case with a damp cloth when it is open ...
Страница 9: ...the data come where is it directed to Another important feature of the KNX bus system is its decentralised structure A central control device is not necessary The intelligence of the system is distributed across all participants However central devices are not excluded If required e g for very special applications central devices might be used as an option Each device or each bus sharing unit has ...
Страница 10: ...r twelve pin user interface AST Instead of the abbreviation AST the abbreviation PEI Physical External Interface is often used For bus coupling unit the first letters of the term BCU are often used as an abbreviation Bus coupling unit For bus coupling units permanently installed in devices manufacturers can use a ready made bus interface module BIM or a KNX chipset The basic structure of the bus c...
Страница 11: ...nsor or indirectly from a computer which controls time controlled circuits and other evaluations of sensor data depending on the programming and controls actuators accordingly If an actuator receives the command to supply voltage to the consumer it switches the mains voltage through to the device 4 5 ETS software A single manufacturer independent engineering tool software ETS allows planning confi...
Страница 12: ...ferent work windows main work window group address window topology window displaying the KNX installation to be edited in different ways 4 5 3 Configuration After installing the ETS on the computer a system cannot yet be configured First of all the manufacturer s product data have to be loaded into the ETS The manufacturers of KNX products provide these data free of charge They are available eithe...
Страница 13: ...device specific key is printed on the device label and can either be entered by keyboard or read by using a code scanner or notebook camera Example of FDSK on device label After entering the FDSK the ETS generates a device specific tool key The ETS sends the tool key to the device to be configured via the bus The transmission is encrypted and authenticated with the original and previously entered ...
Страница 14: ...ified by the Secure icon in the ETS Keep the FDSK key safe because if it is lost it is impossible or difficult to reproduce 4 6 2 Start up without KNX Data Secure Alternatively the device can also be put into operation without KNX Data Secure In this case the device is unsecured and behaves like any other KNX device without KNX Data Secure function To start up the device without KNX Data Secure se...
Страница 15: ...s www theben de de ps 160 ma t knx 9070956 Power supply 160 mA with auxiliary voltage of 30 V DC Supply and monitoring of KNX system voltage This voltage supplies the bus coupling units via which each KNX device communicates with the other networked KNX devices 5 1 2 KNX USB interface https www theben de de schnittstelle usb knx 9070397 For communication between PC and KNX system to be programmed ...
Страница 16: ...lines via a LAN IP as a fast backbone main line The device can also serve as a programming interface to connect a PC to the KNX bus e g for ETS programming 5 2 Terminal devices 5 2 1 RM 8 S KNX https www theben de de rm 8 s knx 4940220 The 8 way switch actuator from the FIX1 series switches electrical loads lamps Manual operation on the device even without bus voltage Links type of contact opening...
Страница 17: ...The 6 way binary input of the FIX1 series is used to connect 10 V 240 V AC DC contacts or similar 2 additional channels operable by buttons on the device but without input Manual operation on the device even without bus voltage All inputs can be operated with different voltages and at different potentials Free allocation of functions switch push button dimming blinds roller blinds counter repeat t...
Страница 18: ...witching status display for each channel 5 2 4 DMG 2 T KNX https www theben de de dmg 2 t knx 4930270 The 2 way universal dimmer actuator of the MIX2 series switches and dims the brightness of incandescent lamps high voltage and low voltage halogen lamps dimmable compact fluorescent lamps energy saving lamps or dimmable LED lamps for 230 V For extension to up to 6 channels Dimming range 0 100 Also...
Страница 19: ... cooling surfaces With 6 temperature controllers P PI for heating and cooling For extension to up to 18 channels With the modes comfort standby night as well as frost heating protection Up to 2 MIX or MIX2 extension modules can be connected to a base module Device and KNX bus module can be exchanged independently of each other Removable KNX bus module allows devices to be exchanged without reprogr...
Страница 20: ...p to 8 façades via 3 integrated brightness sensors 5 2 7 TA 8 S KNX https www theben de de ta 8 s knx 4969228 Binary input binary output push button interfaces With the 8 way push button interface the inputs can detect binary states via potential free contacts and control indicator lights LEDs via the outputs Free allocation of functions switch push button dimming blinds valuator sequences tempera...
Страница 21: ...functions to the individual buttons via the ETS application such as switching the light on off and dimming raising and lowering blinds triggering and saving scenes etc and assign different colours to the LEDs Raumcontroller iON 108 KNX https www theben de de ion 108 knx 4969238 The iON 108 KNX room controller with integrated temperature sensor can be used in residential buildings meeting rooms and...
Страница 22: ...brary for each of the 20 functions on the ION 108 KNX room controller The icon is supplemented by individual function names for example ceiling spots or terrace blinds and the current status on off dimming value position This makes the room controller easier to use and navigate The brightness of the LC display adjusts itself depending on the surrounding brightness If it is dark in the room the dis...
Страница 23: ...rites yes RTC Jump between favourites no F1 F20 Jump between favourites Room temperature controller RTC function If the room temperature controller is selected the measured actual temperature is displayed in this level Depending on the configuration in the ETS parameters the left right buttons can be used to go to the settings of setpoint temperature operating mode fan stage etc If required the re...
Страница 24: ...troller The iON is connected to the app on the smartphone using the buttons on the device The duration of the pairing can be set in the ETS Download the iONplay app from the App Store or Google Play Store Open iONplay app and press in the menu bar Update Edit change password name Delete Search for new devices ...
Страница 25: ...used in the case Manual for the training case KNX 25 Device list of available iON devices appears Select the device and confirm with OK Tap on displayed device Enter the PIN that appears on the iON display Press OK ...
Страница 26: ...utton Operate to switch dim raise or lower blinds etc or use the button Heating for comfort temperature temperature reduction at night etc or use Scenes to enter new lighting scenarios If the time set in the ETS application is exceeded the connection is not established automatically The devices must be paired again ...
Страница 27: ...ogramming the physical address is located on the back of the device the iON 104 KNX or iON 108 KNX devices may have to be dismounted from the base plate This is necessary if a master reset is carried out on the device or a new physical address is assigned to the device When dismounting the device must be pulled firmly but carefully out of the upper bracket and tilted slightly forwards Then it must...
Страница 28: ...be used as follows To connect a PC via Ethernet IP tunneling to the KNX IPsecure Router programming with the ETS via Ethernet possible To connect several cases with each other via KNX IP backbone IP This allows crossline KNX communication between different cases simulating communication between different floors for example The KNX IPsecure Router functions as a line coupler 6 2 XLR connection Furt...
Страница 29: ... connect the training case to the power supply by using the provided cable Recommendation Connect the PC to the training case using the provided USB cable Now the case or the devices inside can be configured via the ETS For programming via the ETS the KNX USB interface if necessary also the KNX IPsecure router is used ...
Страница 30: ...reset By pressing the BUS reset the bus line is short circuited and all connected devices change to the bus failure state When released the bus voltage is stabilised again and all connected devices will be restarted 7 2 Resetting devices Press and hold BUS reset With a pointed object also hold down the respective programming button Release BUS reset and after approx 3 seconds also release the devi...
Страница 31: ...ng devices to factory settings Manual for the training case KNX 31 7 2 1 The programming button of the devices used Push button interface TA 8 S KNX Actuators Weather station on the bottom KNX IPsecure Router ...
Страница 32: ...Resetting devices to factory settings Manual for the training case KNX 32 iON 4 iON 8 The device must be lifted disengaged at the top as shown On the back the programming button must be pressed ...
Страница 33: ...end the functions additional KNX devices can be connected to the BUS Input XLR socket by using a provided XLR adapter In KNX mode KNX devices from competitors can of course also be connected and operated Only devices complying with the safety extra low voltage guidelines for KNX bus and KNX auxiliary voltage may be connected ...
Страница 34: ...Support Manual for the training case KNX 34 9 Support If you require technical assistance our colleagues from the service would be happy to help you Hotline theben de Telephone 49 7474 692369 ...
Страница 35: ...r the training case KNX 35 10 Contact Theben AG Hohenbergstr 32 72401 Haigerloch GERMANY Tel 49 7474 692 0 Fax 49 7474 692 150 Hotline Tel 49 7474 692 369 hotline theben de Addresses telephone numbers etc www theben de ...