The following options are available with the individual sensors/contacts
Floor sensor:
Mode 1
no options, floor temperature control,
floor temperature is shown on screen
Mode 2
Floor temperature control, floor temperature level
can be set between 20 °C and 30 °C, room temperature
is shown on display; floor sensor (907 0 321)
Room sensor:
no options,
internal temperature sensor is switched off; external
temperature sensor (IP 65) (907 0 459)
Presence detector: Temperature selection
this temperature is controlled when the HVAC
output on the presence detector is switched on. If no
presence is detected, the set program is used.
Window switch:
no options,
provided the window switch is switched on, the thermostat controls to frost protection
temperature level; WINDOW SWITCH is shown in display.
28