6
6. Technical data
Operating voltage:
110–230 V AC, +10 % / –15 %
Frequency:
50–60 Hz
Standby:
0,8 W
Brightness range:
1–99.000 lx
On/off switch delay:
0–59 min
Switching capacity max.:
16 A (at 250 V, cos
ϕ
= 1)
Switching capacity:
10 A (at 250 V, cos
ϕ
= 0,6)
Min. switching capacity:
10 mA/230 V AC
100 mA/24 V AC/DC
Switch output:
Switching of any external conduc-
tor is permitted
Shortest switching time:
1 s
Switching accuracy:
to the second
Protection class:
II in accordance with EN 60730-1
subject to designated installation
Software:
class A
Rated impulse voltage:
4 kV
Pollution degree:
2
Contact:
Changeover contact
Incandescent lamp load:
2600 W
Halogen lamp load:
2600 W
Fluorescent lamps: uncorrected:
series-corrected:
parallel-corrected:
2600 VA
2600 VA
1300 VA (130 µF)
Compact fluorescent tubes (EVG):
1100 W
LED lamps (< 2 W):
50 W
LED lamps (> 2 W):
600 W
Bluetooth OBELISK top3:
– Protection rating:
– Temperature:
– Range:
IP 40
–30 °C … +55 °C
15 m on open air test site
Permissible ambient temperature:
–25 °C ... +55 °C,
–40 °C ... +70 °C (sensor)
Protection class:
II (light sensors III) if correctly
mounted
Protection rating:
device
Mounted light sensor
Installation light sensor
IP 20
IP 55
IP 66 (frontside)
IP 40 (backside)
L
The twilight switch display is only fully functional at tem-
peratures from +5 °C ... +55 °C.
7. Contact
Theben AG
Hohenbergstr. 32
72401 Haigerloch
GERMANY
Tel. +49 7474 692-0
Fax +49 7474 692-150
Hotline
Tel. +49 7474 692-369
Addresses, telephone numbers etc.