Designated use

The KNT OT box serves as an interface between the heating 
system in the OT bus (simple bus system in heating and ventila-
tion technology) and the KNX system.
It delivers the necessary data for heating control (heating etc.) 
and sends it to the heater.  The following functions are avail-
able with the KNT OT box:
– needs-driven advance control
– weather-dependent advance control
– control of domestic water heating
– energy maximisation with solar support of domestic  
   water heating
– minimum heating requirement/screed drying program
– legionell a protection program 
 
ETS (engineering tool) enables application programs to be 
selected, specific parameters and addresses to be assigned and 
transferred to the device.
The device is designed for installation on DIN top hat rails (in 
accordance with EN 60715). Only to be used in closed, dry 
rooms.

Installation

Connection

 Clip KNX OT box onto the distributor rail.

KNX bus module

KNX OT box and KNX bus module can be separated mechani-
cally.

 Unlock and remove KNX module 

 on the KNX OT box 

 

  or replace and lock it.

Description of LEDs

Please note the provisions of EN 50428 for switches or similar 
installation material for use in building systems technology 
with regard to the correct installation of bus lines and device 
start-up procedure.
Tampering with, or making modifications to, the device will 
invalidate the guarantee.

Safety advice

 Installation should only be carried out by a professional 

    electrician.

KNX OT box

  Connection terminals for OT

 

5 LEDs

 

KNX bus module

 

Programming keys and LED 

  for physical address

 

Manual push button  

Test

 

Bus connection: 

  Ensure correct polarity!

 

Slide for locking 

  KNX bus module

Description

7 8

OT

KNX

NOTE

LED 1 
green

Central heating (flashes when 
minimum heating require-
ment is active)

OT: CH enable

LED 2 
green

Domestic water heating

OT: DHW enable

LED 3 
green

Burner on/off

OT: flame state

LED 4 
green

OpenTherm active (flashes 
with OT telegram)

LED 5 
red

Error (flashes) 

OT: error

OT