Sensor module

compact office

Detection range: 

horizontal   

 

vertical

360°
120°

Recommended mounting height (Mh)

2.0 - 3.0m

Maximum range

6 x 6 m (H.mont. 2.5m)
8 x 8 m (H.mont. 3.5m)

Mixed light control
Light measurement deactivated

ca. 10 - 1500Lux
„on“

Switch off delay for light
Short pulse

10sec. - 20min.
0.5sec. „on“/ 10sec. „off“

Switch off delay for presence

10sec. - 120min.

Switch on delay for presence
Room surveillance

0sec.   - 10min.

Power module

compact power

Mains voltage

230V ±10%, 50Hz

Relay output A for light

Relais, 230V

Nominal voltage

230V ±10%

Max. switching capacity: 
 

incandescent lamps, halogen

1400VA
1200W

Max. number of electronic ballasts *)

A relay or contactor must be connec-ted in 
case of more powerful devices

10x (1x58W); 5x (2x58W)
16x (1x36W); 8x (2x36W)
16x (< 36W)

Relay output B for presence

Relay potential-free

Maximum voltage

220V DC / 250V AC

Maximum switching capacity

50W / 50VA

Recommended minimum load

0.5mV / 10mA

Depth
Diameter
Mounting plate

40mm
48mm
70 x 70mm

Screw-Terminals

max. 2x 2.5mm

2

Size of concealed housing  
(for flush-mounting)

Dim. 1, (NIS,PMI)

Ambient temperature

0° - 50°C

Degree of protection

IP 40

Article numbers

compact office complete

201 0 000

• Sensor module compact office
• Power module compact power
Surface frame for compact office

907 0 514 

Service remote control QuickSet plus

907 0 532 

User remote control clic

907 0 515 

Settings on the Compact Office

 (see figure above)

  Brightness threshold (Lux)

  Switch off delay for light/ activation of pulse function

  Switch off delay for presence (HVAC/surveillance)

  Switch on delay for HVAC/ 

 

activation of room surveillance function

 

DIP switches

:

 

DIP1 

Lighting control: fully/semi-automatic

 

DIP2 

Push button function: Room/Corridor

 

DIP3 

Push button/switch control

 

DIP6 

Operation mode: normal operation/test

 

 Mechanical safety lock

 

The mechanical lock serves to secure the sensor    

 

module firmly on the power module.

*) Use of T5-FL: When using T5-FL lamps with a comparable watta-
ge, the same number of electronic ballasts may be connected to the 
detector’s switching contact as for the T8-FL. When using the 80W-
FL, the number should be halved in comparison to the 58W-FL.

Technical Specifications for Presence Detector compact office

Sensor Module - Rear Side

Accessories

QuickSet plus Service Remote Control

For the start-up procedure, the QuickSet plus service re-

mote control is available for the installation personnel or 

the technical service. It allows convenient remote adjuste-

ment of all potentiometer values. Manual adjustement of 

the potentiometers directly on the device remains possible 

at all times.

Clic User Remote Control

The clic user remote control is available for the user 

enabling product-spreading, individual switching of up 

to two lighting groups. The user can choose between two 

programmable scenes. Adjoining groups can be demarca-

ted from each other.

Surface Frame

A suitable frame for surface mounting is also available.

Declaration of CE conformity

This device complies with the protection regulations of the EMC direc-
tives 89/336/EEC, of the Low Voltage directive 73/23/EEC and of the 
amending directives 92/31/EEC and 93/68/EEC.

SYSTEMS FOR TIME, LIGHT, CLIMATE

Содержание compact office

Страница 1: ...f learning characteristic i e the unit is able to automatically extend the switch off delay time to max 15min or reduce it to the minimum set time The switch off delay time will not be changed if it is set to 2 min or less Fully or Semi automatic Operation The compact office optionally allows fully automatic lighting control for more convenience or semi automatic control for better energy saving r...

Страница 2: ...are present all the time If the con tact is closed the switch off delay time 10s 120min is restarted at each detection of movement Room Surveillance If the switch on delay is set to Surveillance the sensi tivity of the switched output for presence is reduced The contact closes in case of distinct move ments only and thus reliably indicates the presence of persons The switch off delay time remains ...

Страница 3: ...rightness for indirect lighting on the site of installation must not exceed 2000Lux for brightness threshold 200Lux If the brightness threshold value is set to On the brightness measurement is deactivated no influence by brightness desired Suitable Lamps The compact office presence detector is designed for use with fluorescent lights FL PL as well as halogen incan descent lights The maximum number...

Страница 4: ...vation of pulse function Switch off delay for presence HVAC surveillance Switch on delay for HVAC activation of room surveillance function DIP switches DIP1 Lighting control fully semi automatic DIP2 Push button function Room Corridor DIP3 Push button switch control DIP6 Operation mode normal operation test Mechanical safety lock The mechanical lock serves to secure the sensor module firmly on the...

Отзывы: