Theben AG

Presence detector compact office

 Mixed light measurement

 Presence detection

 Artificial light

 Push button/switch for manual  

   lighting control

 HVAC/surveillance

 

Incident daylight

compact office

compact office Product Features

Passive infrared presence detector for ceiling mounting
Square 360° detection range
Automatic HVAC and lighting control 

 

as well as room surveillance
Mixed light measurement
Switched output for light (relay, 230V)

 

Lighting control with brightness threshold value 

 

and self-learning switch off delay time

 

Fully or semi-automatic operation switch-selectable

 

Push button or switch connection for manual control
Push button function: room/corridor
Pulse function for staircase lighting timer
Switched output for presence (potential-free relay)

 

HVAC control with switch on delay and 

 

switch off delay time

 

reduced response characteristic for room surveillance
Service remote control QuickSet plus (optional)
User remote control clic (optional)

Switched Output for Light

The switching behavior is controlled by presence and 

brightness. The contact closes in case of darkness

 and

 pres-

ence, and opens in case of brightness

 or 

absence 

(see “Fully or Semi-automatic Operation” below).
The minimum switch off delay time (10s - 20min) and the 

desired brightness switching threshold (10 - 1500Lux) are 

adjustable. The switch off delay time automatically adapts 

to the occupant’s behavior (self-learning characteristic), 

i.e. the unit is able to automatically extend the switch off 

delay time to max. 15min or reduce it to the minimum set 

time. The switch off delay time will not be changed if it is 

set to 2 min. or less. 

Fully or Semi-automatic Operation

The compact office optionally allows fully automatic 

lighting control for more convenience, or semi-automatic 

control for better energy-saving results.
In the “fully automatic” operation mode, the lighting is 

switched on and off automatically depending on the pres-

ence and brightness in the room.
In the “semi-automatic” operation mode, the light must 

always be switched on manually. Switching off however, is 

done automatically. In both operation modes, the light can 

always be switched manually by means of push buttons (or 

switches). Multiple push buttons can be connected to one 

control input (illuminated push buttons may only be used 

with neutral conductor connection).

Switching Behavior in Fully Automatic Mode

If the lighting is switched on manually, it remains on for 

at least 30min if persons are present and is automati-cally 

switched off afterwards if the brightness is sufficient. If the 

room is vacated (earlier) the light is definitely switched off 

after the set switch off delay time. The lighting can always 

be switched off manually. The light remains off as long as 

persons are present in the room. If the room is vacant for 

a longer period (switch off delay time elapsed) the manual 

off status is deactivated, and the lighting returns to auto-

matic switching. 







Lighting

Push button/
switch

HVAC/surveillance

SYSTEMS FOR TIME, LIGHT, CLIMATE

Содержание compact office

Страница 1: ...f learning characteristic i e the unit is able to automatically extend the switch off delay time to max 15min or reduce it to the minimum set time The switch off delay time will not be changed if it is set to 2 min or less Fully or Semi automatic Operation The compact office optionally allows fully automatic lighting control for more convenience or semi automatic control for better energy saving r...

Страница 2: ...are present all the time If the con tact is closed the switch off delay time 10s 120min is restarted at each detection of movement Room Surveillance If the switch on delay is set to Surveillance the sensi tivity of the switched output for presence is reduced The contact closes in case of distinct move ments only and thus reliably indicates the presence of persons The switch off delay time remains ...

Страница 3: ...rightness for indirect lighting on the site of installation must not exceed 2000Lux for brightness threshold 200Lux If the brightness threshold value is set to On the brightness measurement is deactivated no influence by brightness desired Suitable Lamps The compact office presence detector is designed for use with fluorescent lights FL PL as well as halogen incan descent lights The maximum number...

Страница 4: ...vation of pulse function Switch off delay for presence HVAC surveillance Switch on delay for HVAC activation of room surveillance function DIP switches DIP1 Lighting control fully semi automatic DIP2 Push button function Room Corridor DIP3 Push button switch control DIP6 Operation mode normal operation test Mechanical safety lock The mechanical lock serves to secure the sensor module firmly on the...

Отзывы: