background image

1103019405 / 04.2010 © 

Theben HTS

Art. Nr. 201 4 000
Art. Nr. 201 4 001

Presence detector

compact office 24V

compact office 24V Lux

Bedienungsanleitung 

2

Notice d´utilisation 

22

Installation manual 

42

Manual de instrucciones 

62

Istruzioni per l'uso 

82

Gebruikershandleiding 

102

Bruksanvisning 

122

Bruksanvisning 

142

Käyttöohje 

162

Betjeningsvejledning 

182

DK

D

F

GB

E

I

NL

S

N

FIN

Содержание compact office 24V

Страница 1: ...pact office 24V compact office 24V Lux Bedienungsanleitung 2 Notice d utilisation 22 Installation manual 42 Manual de instrucciones 62 Istruzioni per l uso 82 Gebruikershandleiding 102 Bruksanvisning 122 Bruksanvisning 142 Käyttöohje 162 Betjeningsvejledning 182 DK D F GB E I NL S N FIN ...

Страница 2: ...x Table of contents 1 Safety 43 2 Function and performance characteristics 44 3 Fitting and connection 45 4 Start up 48 5 Parallel circuit operation 52 6 Use of the user remote control clic 53 7 Test Operation 54 8 Technical specifications 55 9 Warranty declaration 57 10 Troubleshooting 58 ...

Страница 3: ...reading this operating instructions IMPORTANT The unit requires no maintenance Opening the unit or inserting foreign bo dies into it will invalidate the warranty Proper use The presence detector serves exclusively for the purpose contractually ag reed between the manufacturer and the user Any other use is regarded as improper The manufacturer is not responsible for any resulting damage ...

Страница 4: ...tector against unauthorised removal The switching contact A Light switches on the lighting in case of presence and insufficient brightness and off in case of absence or sufficient brightness Switching contact Light potential free relay Adjustable brightness threshold and switch off delay Suitable for fluorescent and compact energy saving lamps as wells as for halogen and incandescent lamps Pulse f...

Страница 5: ...ctor s light sensor as an analog signal The output can be used like a light sensor and functions independently from the presence detector Analog output 0 10V Linear or logarithmic output of brightness 3 Fitting and connection 3 1 Presence detection The ideal mounting height is 2 0 3 0m The sensitivity of the detector decreases with increasing mounting height In order to ensure proper detection of ...

Страница 6: ... 8 3 5 Lux 3 5 3 5 3 2 1 1 2 3 0 o M height Seated persons Walking persons 2 0m 9 m2 3 0m x 3 0m 20 m2 4 5m x 4 5m 0 5m 2 5m 16 m2 4 0m x 4 0m 36 m2 6 0m x 6 0m 0 5m 3 0m 20 m2 4 5m x 4 5m 49 m2 7 0m x 7 0m 1 0m 3 5m 64 m2 8 0m x 8 0m 1 0m seated persons walking persons ...

Страница 7: ...ghting levels With indirect lighting the artifi cial light at the detector s mounting location should not exceed 2000 Lux Brightness value 2000 Lux 3 3 Connection A concealed housing should be used for flush mounted fitting of the presence detector A surface frame is available for surface mounting See the technical data 24V compact power 24V A1 A2 B1 B2 compact power 24V Lux A1 A2 24V 0 10V 0 10V ...

Страница 8: ... A Light Potentiometer Brightness threshold LUX Scale Transfer zones no working area approx 2 Working areas office conference room approx 4 Activities requiring good visibility laboratory drawing etc 5 Deactivation of brightness measurement on Depending on the installation location natural light intensity furniture reflection characteristics of the room and the furni ture it may be necessary to co...

Страница 9: ...c off DIP switch Light measurement adaptive or fixed hysteresis the light measurement is in adaptive mode if the lighting is continuously overridden by a superordinate logic the adaptive mode can be deactivated 4 2 Settings for analog output 0 10V compact office 24V Lux only Linear or logarithmic output of brightness 0 10V lin linear output of brightness 0 10V log logarithmic output of brightness ...

Страница 10: ...unchanged no self learning effect Switch on delay time for presence In case of presence the contact does not close before the set switch on delay has elapsed 0 Contact closes immediately in case of presence Room surveillance function the contact closes only in case of dis tinct movements effective protection against false alarms 10s ...

Страница 11: ...and presence on In case of absence both contacts open after 30sec 2 Service phase 10min The Light contact reacts instantaneously on brightness in order to check the brightness threshold If the brightness is insufficient the lighting is switched on LED on and if the brightness is sufficient the lighting is switched off LED off The service phase can be terminated earlier by actuating the clic user r...

Страница 12: ...issible The total permissible load does not increase Presence detection and brightness measurement by all detectors together The brightness threshold value and switch off delay time must be adjusted individually for each detector The user remote control clic can only be used subject to certain restrictions see section 6 See the technical data 24V compact power 24V A1 A2 B1 B2 compact power 24V A1 ...

Страница 13: ...e more details Two devices Device 1 Group adress A or C Device 2 Group adress B or D clic Group adresses A B or C D The ON and OFF commands switch the lighting on and off respectively Three and more devices The user remote control clic cannot be used Please note that the user remote control clic can only be used to a limited extent with a number of detectors connected in parallel ...

Страница 14: ...ent LED on both contacts close In case of absence LED off both contacts open after 10sec NOTE no brightness measurement The detector remains permanently in the test mode 7 2 Setting the test mode with QuickSet plus While setting the test mode with the service remote control QuickSet plus the detector jumps the start up phase and changes directly into the test mode Test mode ceases automatically af...

Страница 15: ...sec off Switch off delay for presence 10sec 120min Switch on delay for presence Room surveillance 0sec 10min Power modules compact power 24V compact power 24V Lux Nominal voltage 24V AC DC 20 Relay output A1 A2 for light Relais potential free Type of contact potential free micro contact 24V AC DC 20 Switching capacity minimal maximal 1V 1mA 50W 460VA A load of more than 60V or 100mA on the switchi...

Страница 16: ...istor 10kΩ Mixed light measurement linear logarithmic approx 10 1500 Lux approx 10 5000 Lux Depth Diameter Mounting plate 40mm 48mm 70 x 70mm Screw terminals max 2x 2 5mm2 Size of concealed housing for flush mounting Dim 1 NIS PMI Ambient temperature 0 50 C Degree of protection IP 40 Article numbers compact office 24V 201 4 000 compact office 24V Lux 201 4 001 Surface frame for compact 907 0 514 S...

Страница 17: ...u or third parties undertake alterations to the units If the presence detector is connected to a software controlled system the war ranty for this connection is only valid provided the stated interface specification is adhered to We undertake to repair or replace as quickly as possible all supplied components which have become defective or unusable as a result of demonstrably bad material faulty d...

Страница 18: ...s not switch off or switches on spontaneously in case of absence Wait until the switch off delay time has elapsed self learning effect Disturbing heat sources within the detection range heaters incandescent lamp halogen lamp moving objects e g curtains due to open windows Lighting keeps switching on and off during the service phase Too much artificial light is falling on the detector increase lux ...

Страница 19: ...59 GB Subject to change without prior notice Errors and omissions excepted 48 40 66 33 78 46 76 102 5 26 27 102 5 15 5 Dimensions compact office 24V compact office 24V Lux ...

Страница 20: ... 74 74 692 150 Hotline Tel 49 0 74 74 692 369 Fax 49 0 74 74 692 207 hotline theben de Switzerland Theben HTS AG Im Langhag 11 CH 8307 Effretikon Tel 41 0 52 355 17 00 Fax 41 0 52 355 17 01 www theben hts ch Please find the contact addresses for additional countries on www theben de ...