PlanoSpot 360 DALI-2 S DE manual
22
The assignment of the memory banks to the light sensors is as follows:
•
Instance 2 provides integral brightness values: Memory bank 3
•
Instance 3 provides interior brightness values: Memory bank 4
•
Instance 4 provides middle brightness values: Memory bank 5
•
Instance 5 provides window brightness values: Memory bank 6
9.3
Memory bank 7–11 – button instance
The IR group addresses of button instances 6 to 13 are stored in memory banks 7–11.
Memory bank 7
The value range for the "IR group address button instance 6–7" instance variables is I (0x01) to
VIII (0x80) and All (0xFF), see also section 7.1.1 Parameters.
Memory bank 8
The value range for the "IR group address button instance 8–9" instance variables is I (0x01) to
VIII (0x08) and All (0xFF), see also section 7.1.1 Parameters.
Address
Description
Default
value
(factory)
RESET
value
Memory
type
0x00
Address of last position
in this MB
0x03
no change
ROM
0x01
Indicator byte (defined
by manufacturer) –
version of the memory
bank
0x01
no change
ROM
0x02
Memory bank lock byte
0xFF
0xFF
NVM
0x03
IR group address button
instance 6–7
0x01
0x01
NVM
0x04-0xFF
Not implemented /
Reserved
Respons
e NO
no change
ROM
Address
Description
Default
value
(factory)
RESET
value
Memory
type
0x00
Address of last position
in this MB
0x03
no change
ROM
0x01
Indicator byte (defined
by manufacturer) –
version of the memory
bank
0x01
no change
ROM
0x02
Memory bank lock byte
0xFF
0xFF
NVM
0x03
IR group address button
instance 8–9
0x02
0x02
NVM
0x04-0xFF Not implemented /
Reserved
Respons
e NO
no change
ROM