![Theben 201 9 290 Скачать руководство пользователя страница 10](http://html.mh-extra.com/html/theben/201-9-290/201-9-290_installation-manual_1101172010.webp)
54
54
If setting values for switch-off delay time light <= 2 min
and
brightness <= 2.5:
faster response to changes in actual brightness when in operating mode
switching of one lighting row.
Stand-by time
If stand-by time is activated, the light-
ing is not switched off on expiry of the
switch-off delay time but remains in
the stand-by mode (approx. 10% light
output). This reduces the number of
switching operations.
● Individual office
(inactive)
●
Transfer zones
approx. 15 min
●
Transfer zones with continuous light
”on”
Lighting remains continuously in stand-by mode without presence. If the
room brightness is above the desired value, the lighting switches off; if it
falls below, the lighting switches automatically to stand-by mode, even if
no one is present.
4.4 Presence settings
Switch-off delay time presence
The settings remain unchanged (no self-learning effect).
Switch-on delay time presence
When switch-on delay is activated, the telegram sent when movement is de-
tected is delayed by the set value.