User’s Manual & Safety Instructions
Clearances and Installation
Ensure that the mouth of the flame is positioned a minimum of 1500mm
[59.1in] away from curtains, flammable materials, and other sources of
ignition. Be aware of drafts. The floor must be level and the Burner
positioned on a flat surface. The Burner must only be placed into non-
combustible materials and must be installed in accordance with the
outlined safety requirements and clearances. Please send drawings to
your
local representative to confirm the setting complies with the
manufacturer’s requirements prior to installation.
Burner Clearances
Bio Flame Burners can be installed into two (2) types of settings:
A. T hose that are encased by non-combustible materials similar to that
which you would find in a traditional masonry set-up. We refer to this
installation type as “WITHIN A FIREBOX SETTING”
B. T hose that are not encased by non-combustible materials and set
up in a more modern setting without sides or a top. We refer to this
installation type as “WITHOUT A FIREBOX SETTING”. This type of
setting is not C-UL US approved.
A. INSERTING Within a firebox setting
BURNERS
WIDTH – DEPTH - OVERHEAD HEIGHT – REAR - FRONT
60” 1800mm [70.9in] 350mm [13.8in] 500mm [19.5in] 40mm [1.6in] 50mm [2.0in]
48” 1500mm [59.1in] 350mm [13.8in] 500mm [19.5in] 40mm [1.6in] 50mm [2.0in]
38” 1200mm [47.2in] 350mm [13.8in] 500mm [19.5in] 40mm [1.6in] 50mm [2.0in]
24” 1000mm [39.4in] 350mm [13.8in] 500mm [19.5in] 40mm [1.6in] 50mm [2.0in]
16” 800mm [31.5in] 350mm [13.8in] 500mm [19.5in] 40mm [1.6in] 50mm [2.0in]
13” 725mm [28.5in] 350mm [13.8in] 500mm [19.5in] 40mm [1.6in] 50mm [2.0in]
B. INSERTING WithOUT a firebox setting