Pagina 26 di 35
AD1100TE-STD.EN-00 - Subject to change without notice
TFT DryAir
Description of adjustment control
TERMINAL BUILT
Increase a value, go to the label or the next page.
Decrease a value, go to the label or previous page.
Exit without saving setting, returns to the previous level.
Press for 3 seconds to RESET alarm
.
Confirm value/exit and save new settings.
Move to next level (open folder, subfolder, parameter, value).
Access to Status Menu
.
+
[Prg] press esc + set simultaneously.
Access to Programming Menu.
+
[F5] press UP+DOWN simultaneously.
Skip from BIOS Menu to Application Menu.
Symbol Display Description
General alarm indication (fixed = active alarm, flashing = reset alarm)
Indication unit running (flashing it indicates unit runing automatic, fixed it indicating unit in
operation manual)
Indication advanced function (flashing it indicates absolute humidity or value DewPoint
calculated, fixed it indicates absolute humidity or DewPoint value read by the probe)
Indication cooling air pre and/or post-treatment
Indication heating air pre and/or post-treatment
Electric version (CF02=1, 2, 3): Indication first stage reactivation resistors
Steam version (CF02=5): Indication valve opening to 33%
Gas version (CF02=6, 7): on/off burner
Electric version (CF02=1, 2, 3): Indication second stage reactivation resistors
Steam version (CF02=5): Indication valve opening to 66%
Gas Version (CF02=6, 7): Maximum flame burner or closing valve with regulation 3P
Electric version (CF02=3): Indication third stage reactivation resistors
Steam version (CF02=5): Indication valve opening to 100%
Gas Version (CF02=6, 7): Minimum flame burner or opening valve with regulation 3P
Electric version (CF02=4): Indication reactivation resistances with PWM control
Indication reactivation fan (flashing, it indicates the post-cooling reactivation)
Indication process fan