TFT DryAir
Specifications for the channels of process air and dry air in case the dehumidifier is installed
outside the room to be dehumidified
In this case normally the inlet and outlet are channeled.
When the suction of air takes place from the outside, the outlet of the air duct must be at a sufficient
height above ground level in order to prevent the suction of slag and dust.
The air intake must be
protected from possible contaminants, such as exhaust gas, vapor or harmful emissions.
To prevent the ingress of moist air in the air intake of process or reactivation, the intake of the outside
air must be positioned at least 2 meters from the exhaust duct of the moist air.
The ducts must be designed so as to prevent the infiltration of rain or snow in the dehumidifier.
The dehumidifier aspires the dehumidified air by the environment or by a system of air pre-treatment
(pre-cooling or pre-heating). The dry air produced can be sent to dehumidified environment or to a
system of post-treatment.
A control damper can be installed to regulate the flow of dry air.
Electrical connections
In this regard, see the attached wiring diagrams.