3. Technical parameters 

 

TFortis SG-Switch lightning protection device 

  Dust and moisture protection 

– IP66. 

  Number of modules 

– 6. 

  Number of cable glands 

– 13 (PG9). 

  Grounding pin 

– M4 

  Dimensions 240x160x90 mm. 

  Maximum weight 

– 2 kg. 

 

Ethernet lightning protection module (ESG) 

  Supports 10/100/1000Base-T 

  Supports IEEE802.3af/at (including 60W) 

  All conductors are protected by the twisted pair 

  Protects Ethernet ports of TFortis PSW switches from powerful pulse 

interferences 

– 4 kV, 6.5/700 µs based on the «wire-ground» scheme 

with performance criterion B (GOST R 51317.4.5) 

 

230V power supply lightning protection module (PSG) 

  Protects  230  VAC  power  supply  circuits  of  TFortis  PSW  switches 

from powerful pulse interferences 

– 4 kV, 1/50 µs based on the «wire-

wire

»  and  «wire-ground»  scheme  with  performance  criterion  B 

(GOST R 51317.4.5) 

  Terminal block for the screw 

  Maximum cable section is 2.5 sq. mm. 

 
 

 

Содержание SG-Switch

Страница 1: ...1 Operating Manual TFortis SG Switch Surge protection unit for TFortis PSW switches Version 3...

Страница 2: ...Switches The specified technical parameters are guaranteed for the protection of TFortis PSW switches manufactured starting 07 2017 Grounding of the switch is obligatory It is recommended to check the...

Страница 3: ...ose 4 2 Description 5 3 Technical parameters 7 4 Operating conditions 8 5 Installation 8 5 1 Housing installation 8 5 2 Connecting power supply 9 5 3 Connecting the twisted pair 10 6 Supply scope 11 7...

Страница 4: ...f TFortis PSW switches up to class 5 according to GOST R 51317 4 5 Figure 1 Typical application scheme Features High level of protection against lightning interferences class 5 All weather performance...

Страница 5: ...R 51317 4 5 performance criterion B Since July 2017 all TFortis PSW switches are manufactured with improved lightning protection class 4 according to GOST R 51317 4 5 TFortis SG Switch increases the...

Страница 6: ...of parallel installation of power cables and signal cables Class 4 Electromagnetic environment in case of installation of connecting cables outdoors in the proximity of power cables and using multi wi...

Страница 7: ...uctors are protected by the twisted pair Protects Ethernet ports of TFortis PSW switches from powerful pulse interferences 4 kV 6 5 700 s based on the wire ground scheme with performance criterion B G...

Страница 8: ...n and immediately after the storm 5 Installation 5 1 Housing installation The housing has four attachment points at the edges Marking of the attachment points is shown in Figure 3 Figure 3 Attachment...

Страница 9: ...of the terminals when connecting the power cable to 230 VAC protection module Terminal IN 230 VAC input for connecting the power supply cable Terminal OUT 230 VAC output for connecting to TFortis PSW...

Страница 10: ...6 Connection of the Ethernet cable When the lightning protection device SG Switch is located in the same cabinet wit TFortis PSW switch it is allowed to use a non shielded twisted pair between these...

Страница 11: ...ial number on the housing is missing or if the serial number has been changed removed or is illegible if there are internal of external mechanical damages chipping cracking deformation damaged power s...

Отзывы: