To open the configuration menu, first touch the transmitter ON/OFF button to turn the display off (touch 
any button to ‘wake-up’ the transmitter, then touch the ON/OFF button to turn off), then touch the SET and 
UP buttons at the same time for 5 seconds: 

You will be viewing the first of 15 options which can be configured to adjust the operation of the OPTIMUM 
VIBE, to best suit the installation and the user’s requirements. 

Touch the UP or DOWN arrows to adjust the parameter, and touch SET to move sequentially through the 
options.  Changes will be saved by pressing the ON/OFF button.  If no button is touched for 10 seconds, the 
display will ‘time-out’, but your changes will still be saved. 

Transmitter and receiver display / controls 

Assuming the receiver response is O.K., proceed to the rest of the setting-up procedure. 

SET 

Parameter setting — how to configure the way your Optimum Vibe thermostat works:              + 

Option 

Description 

Range 

Default value 

01 

Temperature calibration 

-8

0

C  ~  +8

0

0

0

02 

Maximum temperature setting 

5

0

C  ~  35

0

35

0

03 

Minimum temperature setting 

5

0

C  ~ 35

0

5

0

05 

Frost-protection temperature 

OFF (- - in config. Screen), or 5

0

C ~ 15

0

5

0

09 

Hysteresis (differential) 

0.5

0

C ~ 3.5

0

0.5

0

> 10 

Display setting 

0 ~ 1 

17 

Reset (reset all values to       
factory default) 

Change to 1. Then touch Power button 

for 5 seconds 

18 

Firmware code 

Non adjustable * 

5091 

19 

Firmware code 

Non adjustable * 

0202 

50 

Backlight 

0: OFF    1: AUTO 

> 51 

Programme mode 

76: 7 days / 6 periods                            

526: Weekday / Weekend / 6 periods 

526 

> 52 

Temperature regulation mode 

NOr: Normal (ON/OFF) 

OPs: Optimum Start 

tPi: Time Proportional / Integral 

NOr 

Power 

Heating on 

OVERRIDE 
(short press) 
RF LINK 
(long press) 

 

ON/OFF 

Receiver  

      VIBE 

ON/OFF 

UP 

 

PROGRAM 

DOWN 

 

SETTINGS 

BACK 

   PROG 

   SET 

Transmitter  

See additional notes about these configuration options on Page 4 

Firmware is pre-loaded in the factory, and visible for reference but cannot be changed.   