HOW TO USE IT

Test the Ammeter battery
and display by pressing
the ON button. Verify
that each digit in turn
displays 8. If needed,
replace the 9V battery
with a lithium
or alkaline type.

The Ammeter measures
and displays current
in two modes:

The initial factory default mode is
Peak Hold, which displays the peak
RMS current measured while the Ammeter
is placed on a conductor. Peak Hold
mode allows a user to capture and store
the peak current over the period of time
the Ammeter is applied to a conductor.

The second available mode is Real
Time which displays the current as
it normally rises or falls. Real Time mode
allows the user to see changes in load
current as they occur.

The measurement mode can be viewed or changed after the HVA High Voltage
Ammeter is turned on. Simply press the ON button again to display 

PH

for

Peak Hold, the initial factory default, or 

rt

for Real Time, as shown above.

The selected measurement mode will be saved when the Ammeter shuts
off. To switch between measurement modes, press the ON button again.

The measurement mode can be displayed and changed any time after the
Ammeter is turned on but before current measurements are made by pressing
the ON button. Press it once to display the measurement mode and press
it again to change the mode. If current measurements have already been
made, the memory must be cleared before the measurement mode can be
changed. To clear the memory, press and hold the ON button until zero is
shown on the display. Then proceed to display or change the measurement
mode by pressing the ON button. 

Содержание HDE HVA-2000

Страница 1: ...ing Instruction Manual HIGH VOLTAGE DIGITAL AMMETER HVA 2000 1475 Lakeside Drive Waukegan Illinois 60085 U S A 847 473 4980 fax 847 473 4981 website www HDElectricCompany com Making the Invisible Visi...

Страница 2: ...and underground secondary voltage distribution voltage and transmission voltage distribution systems up to 500kV The HVA 2000 measures current from 1 Amp up to 2000 Amps and current is displayed in th...

Страница 3: ...rior to using inspect the instrument for any physical damage cleanliness and check for proper working order by pressing and holding the ON button Do not proceed if the display does not indicate all 8...

Страница 4: ...The measurement mode can be viewed or changed after the HVA High Voltage Ammeter is turned on Simply press the ON button again to display PH for Peak Hold the initial factory default or rt for Real T...

Страница 5: ...ngs The Ammeter will shut off automatically four minutes after the last reading All stored readings are cleared when the unit shuts off All stored readings can also be cleared by pressing and holding...

Страница 6: ...mmeter can be placed over small drain wires but the cable shield wires should not go inside the U of the HVA HighVoltage Ammeter CARE MAINTENANCE STORAGE It is recommended for protection of the HVA Hi...

Страница 7: ...CATEGORY IV DIMENSIONS 4 H x 6 6 W x 11 5 L 10 cm x 17 cm x 29cm WEIGHT 1 8 lbs 0 8 kg LED HEIGHT 1 5 3 8 cm ACCURACY 50 60Hz RANGE ACCURACY 1 10A 1 2 counts 11 100A 1 3 counts 101 500 1 6 counts 501...

Страница 8: ...of life In the event that a Product cannot be repaired or replaced due to unavailability of parts HD Electric Company will use commercially reasonable efforts to obtain substitute parts or conduct wor...

Отзывы: