9
CMT-90
Operation
Electric shock hazard:
Contact with live circuits could result in severe injury or death.
1. The meter automatically selects the proper measurement according to the
following table.
Priority
Display
Conditions
1
AC volts or DC volts,
whichever is greater
Input at terminals is
1.3 to 999.9 VAC
2.1 to 999.9 VDC
-0.7 to -999.9 VDC
2
Resistance and
continuity
Input at terminals is
0 to ∞ Ω
0 to 0.9 VAC
1.0 to 2.0 VDC
-0.2 to -0.4 VDC
3
Diode test
Input at terminals is
0.4 to 0.8 VDC
4
AC amps
AC current through jaw is
0.9 to 600.0 A
2. Refer to “Typical Measurements” for specific measurement instructions.
3. Test the unit on a known functioning circuit or component of the type you intend
to measure.
• If the unit does not function as expected on a known functioning circuit,
replace the battery.
• If the unit still does not function as expected, send the unit to Greenlee for
repair. Refer to the instructions under the Warranty.
4. Take the reading from the circuit or component to be tested.