![Textron 783310076353 Скачать руководство пользователя страница 18](http://html1.mh-extra.com/html/textron/783310076353/783310076353_instruction-manual_1098005018.webp)
18
Measurements on Three-Phase Circuits
(cont’d)
Three-Phase Four-Wire Circuits: Settings Table
* A positive (+) PF indicates an inductive load. A negative (–) PF indicates a capacitive load.
Power factor value is correct for balanced loads only.
** Jaw should be closed and removed from circuit whenever DCA/W ZERO is pressed.
Notes:
• The + sign on the jaw must face the power source.
• All three power measurements (W
R
, W
S
and W
T
) should be positive. Check test lead
connection and clamping of jaw if any power measurement is negative.
Measurement:
True Power, Power Factor*, Apparent Power and Reactive Power
(W, PF, KVA and KVAR)
Type of Circuit:
3ø4W
Selector Setting: 3ø4W
Instructions
Red Lead
Black Lead
Clamp
Connection Connection Location
“R” will flash on the display. Press
DCA/W ZERO
**.
Connect the leads and position the clamp as shown
R
N
R
to take the first measurement (W
R
/ PF
R
).
After the measurement stabilizes, press
READ NEXT
.
“S” will flash on the display. Remove clamp from wire.
Press
DCA/W ZERO
** and connect the leads and
S
N
S
position the clamp as shown to take the final
measurement (W
S
/ PF
S
).
After the measurement stabilizes, press
READ NEXT
.
“T” will flash on the display. Remove clamp from wire.
Press
DCA/W ZERO
**
and connect the leads and
T
N
T
position the clamp as shown to take the final
measurement (W
T
/ PF
T
).
After the final measurement stabilizes, press
READ NEXT
. The CMP-200 will calculate and
display the power factor (PF) and true power (W). Press
3ø KVAR KVA
to display the
reactive power (KVAR) and apparent power (KVA).
www.calcert.com
1.888.610.7664
0
5
10
15
20
25
30