TL-QUAD-LOOP & TL-DUAL-LOOP Transmitter Manual (d0108)
Pinout Diagram
The TL Series Transmitter uses plug-in type screw terminal con-
nectors for all input and output connections. The power supply
connections have a unique plug and socket outline to prevent cross
connection�
!
WARNING
:
AC and DC input signals and power supply
voltages can be hazardous. Do Not connect live wires to
screw terminal plugs, and do not insert, remove or handle
screw terminal plugs with live wires connected.
Connector Pinouts
Connector Pinouts
Connector Pinouts
Input Select
Installation Guidelines
Installation
1� Install and wire transmitter per local applicable codes
regulations, the particular application, and good instal-
lation practices�
2� Install transmitter in a location that does not exceed the
maximum operating temperature and that provides good air
circulation�
3� Separate input/output leads from power lines to protect
the transmitter from external noise� Input/output leads
should be routed as far away as possible from contactors,
control relays, transformers and other noisy components�
Shielding cables for input/output leads is recommended
with shield connection to earth ground near the meter pre-
ferred�
!
4� A circuit breaker or disconnect switch is required to dis-
connect power to the meter. The breaker/switch should be
in close proximity to the meter and marked as the discon-
necting device for the meter or meter circuit. The circuit
breaker or wall switch must be rated for the applied voltage
(e�g�, 120VAC or 240VAC) and current appropriate for the
electrical application (e�g�, 15A or 20A)�
5� See
Connector Pinouts section
for wiring�
6� Use 28-12 AWG wiring, minimum 90˚C (HH) temperature
rating� Strip wire approximately 0�3 in� (7-8 mm)�
7� Recommended torque on all terminal plug screws is 4�5
lb-in (0�51 N-m)�
POWER
INPUT
Neutral
(–)
Line
(+)
!
4-20mA
0-5V
1-5V
0-10V
Test +
–
Test +
–
Test +
–
Test +
–
Zero
Span
CH1 out CH2 out CH3 out CH4 out
CH1
Zero
Span
CH2
Zero
Span
CH3
Zero
Span
CH4
24V Exc.
Signal Grd
85 to 265 VAC
2W
nom.
50-400 Hz
95 to 300 VDC
2W
nom.
15 to 48 VAC
2W
nom.
50-400 Hz
10 to 72 VDC
2W
nom.
Input range is normally set by the factor per your
order, but you may change that by following these
directions.
1� WARNING: Disconnect the power from the meter
and disconnect any equipment attached to the outputs before
attempting this procedure� Dangerous voltages may be present�
2� Remove the four screws from the top panel (label side), nuts
are in the bottom panel. Open the case.
3. To select 4-20mA input, move the Voltage/Current jumper to
CURRENT, move the range selection jumper to 4-20mA.
4. To select a voltage input, move the Voltage/Current jumper to
VOLTAGE, move the range selection jumper to the desired volt-
age range (0-5V, 1-5V, 0-10V)�
5� Reassemble the case�
6� It is best to place a small label at the input connector indicating
the required input signal�
NOTE: Input signal calibration is not required in the
TL-DUAL-LOOP and TL-QUAD-LOOP meters.
!