   TL-QUAD-LOOP & TL-DUAL-LOOP Transmitter Manual (d0108)

Pinout Diagram

The TL Series Transmitter uses plug-in type screw terminal con-

nectors  for  all  input  and  output  connections.  The  power  supply 

connections have a unique plug and socket outline to prevent cross 

connection� 

!

WARNING

AC and DC input signals and power supply 

voltages can be hazardous. Do Not connect live wires to 

screw terminal plugs, and do not insert, remove or handle 

screw terminal plugs with live wires connected.

Connector Pinouts

Connector Pinouts

Connector Pinouts

Input Select

Installation Guidelines

Installation

1� Install and wire transmitter per local applicable codes  

regulations, the particular application, and good instal- 

lation practices�   

2� Install transmitter in a location that does not exceed the 

maximum operating temperature and that provides good air 

circulation�

3� Separate input/output leads from power lines to protect 

the transmitter from external noise�  Input/output leads 

should be routed as far away as possible from contactors, 

control relays, transformers and other noisy components�  

Shielding cables for input/output leads is recommended 

with shield connection to earth ground near the meter pre-

ferred�

!

4� A circuit breaker or disconnect switch is required to dis-

connect power to the meter.  The breaker/switch should be 

in close proximity to the meter and marked as the discon-

necting device for the meter or meter circuit.  The circuit 

breaker or wall switch must be rated for the applied voltage 

(e�g�, 120VAC or 240VAC) and current appropriate for the 

electrical application (e�g�, 15A or 20A)�

5� See 

Connector Pinouts section

 for wiring�

6� Use 28-12 AWG wiring, minimum 90˚C (HH) temperature 

rating�  Strip wire approximately 0�3 in� (7-8 mm)�

7� Recommended torque on all terminal plug screws is 4�5 

lb-in (0�51 N-m)�

POWER

INPUT

Neutral

 (–)

Line

 (+)

!

4-20mA

0-5V

1-5V

0-10V

Test +

Test +

Test +

Test +

Zero

Span

CH1 out CH2 out CH3 out CH4 out

CH1

Zero

Span

CH2

Zero

Span

CH3

Zero

Span

CH4

24V Exc.

Signal Grd

85 to 265 VAC 

2W

 nom.

50-400 Hz

95 to 300 VDC 

2W 

nom.

15 to 48 VAC 

2W

 nom. 

50-400 Hz

10 to 72 VDC 

2W

 nom.

Input range is normally set by the factor per your 

order, but you may change that by following these 

directions.

            1� WARNING: Disconnect the power from the meter 

and disconnect any equipment attached to the outputs before 

attempting this procedure�  Dangerous voltages may be present�

  2� Remove the four screws from the top panel (label side), nuts 

are in the bottom panel.  Open the case.

  3. To select 4-20mA input, move the Voltage/Current jumper to 

CURRENT, move the range selection jumper to 4-20mA.

  4. To select a voltage input, move the Voltage/Current jumper to 

VOLTAGE, move the range selection jumper to the desired volt-

age range (0-5V, 1-5V, 0-10V)�

  5� Reassemble the case�

  6� It is best to place a small label at the input connector indicating 

the required input signal�

NOTE:  Input signal calibration is not required in the 

TL-DUAL-LOOP and TL-QUAD-LOOP meters.

!