Texmate DL-40JANUS-DCA Скачать руководство пользователя страница 7

Texmate, Inc. Tel. (760) 598-9899  •  www.texmate.com

DL-40JANUS-DCA/DCV manual (d0114)

Page 7

The Modbus/RS-485 communication settings sub-menu allows 

you to set the following parameters:
a) Baud Rate – this is the baud rate of the RS-485 serial communi-

cation between the meter (slave) and Modbus master. Options are 

9600 (default, meter shows “96”) and 19200 (meter shows “192”).
b) Address – this is the meter’s Modbus address on the RS-485 

loop. Typically, RS-485 limits the number of devices on the loop to 

32, but the DL-40 supports the full Modbus address range of 1-247. 

Address 1 is the default value.

c) Parity – this is the parity setting for the RS-485 serial commu-

nication between the meter (slave) and Modbus master. Options 

are: None (display shows “0”; Odd (display shows “1”); Even 

(default, display shows “2”).
The meter’s response time to a read command from the master is 

40-45msec (typically 42msec). The response time for a write com-

mand is 70-75msec (typically 72msec). This is due to the module 

having to communicate to the meter’s core firmware to complete 

the desired command. Exception responses are handled directly 

by the module and typically have a response time of 3msec.

Modbus RTU & RS-485 Communication Settings

The DL-40 Modbus communication module supports the following 

Modbus commands:

a) Read Holding Register (0x03)
b) Write Single Register (0x06)

Modbus addresses for DL-40JANUS registers are shown on 

the next page

The following are some things to note about particular registers:
a) Modicon address 40001 RELAY has the bit values for Sp3 & 

Sp4 and LED3 & LED4 reversed. There is an historical reason 

for this, and we have chosen to maintain backward compatibili-

ty in case customer’s want to send their meters in for a Modbus 

upgrade (at a nominal fee).

b) Modicon addresses 40002 INP, 40026 PEAK, 40027 VALY, 

40029 ZERO, 40029 SPAN return a 2 byte hexadecimal value 

of the meter’s display (in counts) and does not include the deci-

mal point. If you need the decimal value with decimal point, you 

will need to read the register, convert it to decimal, read 40024 

(see below) to determine decimal location, then combine the 

two. Display counts are in Two’s Complement notation.

   

a. Hex values for 0 to 9999 are 0x0000 to 0x270F.

   

b. Hex values for -1 to -1999 are 0xFFFF to 0xF831.

   

c. Over-range is indicated by a returned value of 9999  

 

   (0x270F).

   

d. Under-range is indicated by a returned value of -1999  

 

   (0xF831).

c) In order for Sp3 and Sp4 set point settings to work, the DL-40 

must have the optional Output Carrier Board installed (P/N 

SA-DL/OM-CB).

d) All Delay on Make (DoM), Delay on Break (DoB) and Hysteresis 

values are in units of whole seconds.

e) Modicon address 40023 RLYMOD uses the following values 

to set the relay activation mode (letter sequence is SP1, SP2, 

SP3, SP4):

   

a. 0 for HHHH

   

b. 1 for HLHL

   

c. 2 for LHLH

   

d. 3 for LLLL

   

e. H means relay is energized if input is equal to or  

             exceeds setpoint; L means relay is energized if input 

                  is less than setpoint.
   

f.  Note that the meter will not show the last two letters if 

                  the Output Carrier Board option is not installed.
f)  Modicon address 40023 DP uses the following values to set the 

display decimal point location:

   

a. 0 for XXXX (none)

   

b. 1 for XXXX.

   

c. 2 for XXX.X

   

d. 3 for XX.XX

   

e. 4 for X.XXX

g) Modicon address 40025 BRIGHT must be a value between 1 

(most dim) to 4 (most bright).

h) Modicon addresses 40028 and 40029 will have different mean-

ings depending on the Auto calibration or Manual rescaling 

operational selection (see Auto Calibration Mode or Manual 

Rescaling Mode above).  These are explained in the register 

table below.

i) Modicon addresses 40030 IZERO and 40031 ISPAN return 

hexadecimal values related to the Auto Mode calibration of the 

meter. They do not necessarily match expected values due vari-

ations and tolerances in the measurement circuit components, 

e.g., calibrating with a value of zero volts for the ZERO value 

may return a value of 0xFFFE (-2).  These registers have no 

meaning in Manual Rescaling Mode).

Modbus RTU Implementation

Содержание DL-40JANUS-DCA

Страница 1: ... Features 1 Software Logic Tree 3 Specifications 1 Two Point Analog Output Range Setting and Calibration 6 General Features Specifications Software Features Index LEOPARD FAMILY DL 40JANUS DCA 20 50 100 200mV DC Full Scale DL 40JANUS DCV 2 20 200V DC Meter Two scaling methods MANUAL no external sig nal source required and AUTO requied an exter nal signal source Optional Modbus RS 485 serial analog...

Страница 2: ...ted by pressing and releasing the or buttons When there are more than two display selec tions they are shown in brackets below the first display and are also selectable by press ing and releasing the or buttons A dotted box indicates these functions are omitted or bypassed when the related hard ware is not present To explain software programming procedures logic diagrams are used to visually assis...

Страница 3: ...IMAL POINT AND BRIGHTNESS SELECTION See Page 6 Setpoint 3 SP3 Setpoint 4 SP4 Valley Offset Scale Factor Calibrate Analog Output Lo Calibrate Analog Output Hi X XXX XX XX XXX X XXXX XXXX 2 3 4 Decimal Point dp Display Brightness br TWO POINT ANALOG OUTPUT CALIBRATION SEE PAGE 6 MANUAL RESCALING MODE See Page 4 SELECTION FOR ANALOG RANGE OUTPUT See Page 6 confirm SP4 confirm confirm confirm This men...

Страница 4: ... out STEP B Select Between Calibration of Input or Output Note If the analog output option is not present Step B is skipped and the program goes directly from Step A to Step C 1 Press the or button to select the display toggling from CAL to inPt 2 Press the P button Display toggles between oFSt and the previous offset setting STEP C Set the Offset on the Digital Display 1 Using the and buttons adj...

Страница 5: ...Two Point Analog Output Note If the analog output option is not present Step B is skipped and the program goes directly from Step A to Step C 1 Press the or button to select the display toggling from CAL to inPt input calibration 2 Press the P button Display toggles between ZErO and the previous zero setting STEP C Set the Meter s Low Input Signal Reading on the Digital Display 1 Apply a zero or l...

Страница 6: ...Press the P and buttons at the same time Display toggles between CAL and oFF 2 Press the P button Display shows previous dP selection STEP E Set the Decimal Point 1 Using the and adjust the display to the desired decimal point setting 2 Press the P button Display toggles between br and the previous br setting STEP F Set the Display Brightness 1 Using the and buttons adjust the display to the desir...

Страница 7: ... counts and does not include the deci mal point If you need the decimal value with decimal point you will need to read the register convert it to decimal read 40024 see below to determine decimal location then combine the two Display counts are in Two s Complement notation a Hex values for 0 to 9999 are 0x0000 to 0x270F b Hex values for 1 to 1999 are 0xFFFF to 0xF831 c Over range is indicated by a...

Страница 8: ...9 HYST2 Setpoint 2 Hysteresis setting 40019 0x0012 SINT16 R W 1999 9999 PRES3 Setpoint 3 setting 40020 0x0013 UINT16 R W 0 9999 HYST3 Setpoint 3 Hysteresis setting 40021 0x0014 SINT16 R W 1999 9999 PRES4 Setpoint 4 setting 40022 0x0015 UINT16 R W 0 9999 HYST4 Setpoint 4 Hysteresis setting 40023 0x0016 UINT16 R W 0 3 RLYMOD Relay activation polarity H L disabled e g HHHH 40024 0x0017 UINT16 R W 0 4...

Страница 9: ...he SP2 Delay on Make doM Delay Time Setting STEP H Set the SP2 Delay on Break dob Delay Time Setting STEP I Set the Hysteresis Setting for Setpoint 2 1 Using the and buttons adjust the display to the desired hysteresis HYSt value 2 Press the P button Display toggles between SP3 and the previous SP4 setting STEP J Set Setpoint 3 SP3 No doM or dob 1 Using the and buttons adjust the display to the de...

Страница 10: ...ng with external signal OFF 17 16 19 19 18 MANUAL rescaling ON AUTO scaling OFF ON SP1 NO SP1 NO SP2 NO SP2 NO Pins 14 and 15 AC DC Power Input Auto sensing AC DC power supply For voltages between 85 265 V AC 95 370 V DC PS1 or 18 48 V AC 10 72 V DC PS2 Pin 14 AC DC Neutral Neutral power supply line Pin 15 AC DC line Live power supply line Analog and RS 485 Output Board Pins Pins 16 and 17 Analog ...

Страница 11: ...ood air circulation 3 Separate input output leads from power lines to protect the meter from external noise Input output leads should be routed as far away as possible from contactors control relays transformers and other noisy components Shielding cables for input output leads is recommended with shield connection to earth ground near the meter preferred 4 A circuit breaker or disconnect switch i...

Страница 12: ...Span Pot ID05 ID01 Zero Offset Pot Zero Offset Pot Input Range Header Input Range Header ID01 DC Volts 2 20 200V Custom w 24V DC Exc Custom 200V 20V 2V ON OFF 24V Exc 24V Exc Decrease Span Increase SPAN DC VOLTS PIN 1 PIN 2 PIN 3 Custom 200V 20V 2V ON OFF 24V Exc 24V Exc Decrease Span Increase SPAN ZERO DC VOLTS PIN 1 PIN 2 PIN 3 ID05 DC Volts 2 20 200 Custom V DC with Offset and 24V Exc 0 _ Offse...

Страница 13: ...o be offset 5 of full scale 100 to 100 counts Input Module Component Glossary 96 mm 3 78 48 mm 1 89 3 9 mm 0 15 typical FRONT VIEW 1 8 DIN 96x48mm These dimensions are increased by 1 6mm 0 06 when the metal surround case is installed The 96x48mm case is particularly suitable for mounting in mosaic panels or insulative panels up to 2 thick They can also stack mount 2 up in existing cutouts for 1 4 ...

Страница 14: ...c case is made from fire retardant polycar bonate A metal surround case can be ordered to enhance the meter s fire retardant capabilities and also provide shielding against electromagnetic interference EMI The metal case slides over the polycarbonate case and is held firmly in place by spring type non return clips The Metal Surround Case must be factory installed on the polycarbonate case and once...

Страница 15: ...NPUT MODULES ANALOG OUTPUT RELAY OUTPUT OPTIONS ACCESSORIES OA____ DL 40JANUS DCA Add to the basic model number the order code suffix for each standard option required The last suffix is to indicate how many different special options and or accessories that you may require to be included with this product Please see our website www texmate com to configure a meter and see current pricing Ordering ...

Отзывы: