General Configurations
9
SLVUAV3A – August 2016 – Revised February 2017
Copyright © 2016–2017, Texas Instruments Incorporated
TPS26600-02EVM: Evaluation Module for TPS2660x
4.4.4
Current Limit and Fault Responses Test
Follow the instructions to verify the current limit and various fault response modes like auto-retry, latch and
circuit breaker with auto-retry:
1. Set up the oscilloscope as listed in
.
Table 9. TPS26600-02EVM Oscilloscope Setting for the Current Limit Test
Oscilloscope Setting
CH1 Probe Points
CH2 Probe Points
Channel 1 = 10V / div
VOUT1 (TP3)
VOUT2 (TP12)
Channel 2 = 10V / div
VIN1 (TP2)
VIN2 (TP11)
Channel 4 = 2 A / div
Input current into T1 +Ve wire
Input current into T3 +Ve wire
Trigger source = Channel 2
Trigger level = 12 V ±1V
Trigger polarity = Rising
Trigger mode = Single
Time base
100 ms / div
NOTE:
Note : Measuring the current limit value on the oscilloscope can easily cause ±10% error
from the typical expected values as listed in
2. Set the current limit to 2.23 A by installing the J5/J12 jumper in position 1-2.
3. The jumper setting for different current limits is shown in
.
4. Set the current limit response to auto-retry by installing the J4/J11 jumper in position 2-3.
Table 10. TPS26600-02EVM Jumper Setting for Current Limits
CH1, CH2 Jumper Positions (J5, J12)
Load Current Limit (A)
1-2
2.23
3-4
1.5
5-6
1
7-8
0.2