76
Menu
No.:
Menu - name
Menu – description-meaning
Settings - values
Alloved
MAIN MENU
unit
KP 12S,
KP 12 - ES
KP 22S,
KP 22 - ES
KP 62S,
KP 62 - ES
3.3.2
Ignition
Menu for ignition parameters setting
Use electrical ignition
Button for activation of electrical ignition (If set OFF boiler is working in Stand By mode)
-
ON
ON
ON
service
Ignition feeding time
Ignition feeding time (feeder F1) – fuel for ignition
Sec
90
90
40
producer
Fan delay after start
Time electrical ignition (preheating) without fan
Sec
60
60
60
producer
Primary fan level in ignition
Primary fan level in ignition
%
30
30
32
producer
Control temperature
Minimum temperature difference exhaust and boiler water in the end ignition
°C
10
10
10
producer
Reignition enable
Permit
repetition
ignition in case wrong ignition - button
-
OFF
OFF
OFF
service
Exhaust fan enable
Exhaust fan enable - button
-
OFF
OFF
OFF
service
Exhaust fan level in ignition
Exhaust fan level in ignition - button
%
-
-
-
service
Maximum ignition time
Maximum ignition time (activation electrical heating elements)
Min
15
15
15
producer
Burn on time after ignition
Time for stabilization of fire
Min
2
2
2
producer
Feeding time in burn on
Feeding time (feeder F1) for stabilization of fire
Sec
5
5
5
producer
Ignition is running in burn on state Time spiral activation - during stabilisation of fire
Min
1
1
1
producer
Stabilization time after burn on
Time for prolong of stabilization of fire
Min
2
2
3
producer
Aplication time during burn on
Aplication time during burn on – additional fuel for burn on
Min
0
0
0
producer
Start program after ignition
Start program after ignition
-
3
3
3
producer
3.3.3
Standby mode
Menu Standby mode parameters setting
Standby time
Time period, in which automatic boiler is not actively burning
Min
45
45
15
producer
Time fire life
Time fire life
Min
0
0
0
producer
Boiler standby temperature
Temperature - desired output
°C
in accordance with
the settings
in accordance with
the settings
in accordance with
the settings
user
Feeder 2 run out in standby
Feeder 2 run out in standby
Sec
60
60
60
producer
Maximal burnout time fan
Maximal burnout time fan
Min
1
1
1
producer
Stop the fan in burnout at
Stop the fan in burnout at
%
25
25
25
producer
Feeding worktime in standby
Feeding workintime in standby
Sec
5
7
5
producer
Feeding breaktime in standby
Feeding breaktime in standby
Sec
60
60
38
producer
Number of cycles
Number of cycles
-
2
2
3
producer
Primary fan if feeding in standby
Primary fan if feeding in standby
%
30
30
30
producer
Exhaust fan if feeding in standby
Exhaust fan if feeding in standby
%
0
0
0
producer
3.3.4
Programs
Menu programs parameters setting
Program number
Button – No. Program for setting parameters
Program No.1
30% of nominal boiler power
Feeder 1 on
Time for feeding of fuel (feerder 1)
Sec
5
5
4
producer
Feeder 1 off
Breaktime of feeder 1
Sec
90
60
30
producer
Primary fan
Primary fan settings
%
30
30
30
producer
Exhaust fan
Exhaust fan settings
%
0
0
0
producer
Содержание KP 12-ES
Страница 13: ...Automatic boiler for wood pellets 12 Picture No 4 HZS 532 1 HZS533 HZS533 HZS535 Picture No 5 Other modules ...
Страница 21: ...Automatic boiler for wood pellets 20 Picture No 15 Jacketing KP 22S KP 22 ES ...
Страница 22: ...Automatic boiler for wood pellets 21 Picture No 16 Jacketing KP 62S KP 62 ES ...
Страница 43: ...Automatic boiler for wood pellets 42 9 3 1 2Menu users settings ...
Страница 45: ...Automatic boiler for wood pellets 44 Cleaning an ash removeing Skin Time window setting ...
Страница 48: ...Automatic boiler for wood pellets 47 Actual values Configuration ...
Страница 54: ...Automatic boiler for wood pellets 53 Cleaning Ash removing USB Time window setting ...
Страница 55: ...Automatic boiler for wood pellets 54 Load from USB Save on USB ...
Страница 58: ...Automatic boiler for wood pellets 57 Funkcion for setings of parameters Funkcion for manual control of pump ...
Страница 60: ...Automatic boiler for wood pellets 59 ...
Страница 62: ...Automatic boiler for wood pellets 61 ...
Страница 63: ...Automatic boiler for wood pellets 62 i ...
Страница 70: ...69 Picture No 31 Principle of the modulation ...
Страница 71: ...70 Picture No 32 Dim Req for the placement of KPx2 in boiler room exam of using collecting troughs ...
Страница 72: ...71 Picture No 33 Directory information consuption wood pellets for boiler family KP ...
Страница 73: ...72 Picture No 34 Circuit diagram control unit ...
Страница 74: ...73 Picture No 35 Circuit diagram modul HZS 533 ...
Страница 75: ...74 Picture No 36 Circuit diagram HZS 533 HZS 535 ...