![TESTO 6721 Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/testo/6721/6721_instruction-manual_1092446010.webp)
10
testo 6721 - Commissioning
3
Solder ends of lines to the pins in the bottom
part of the connector
➍
:
Two separate switching points can be created
using the two switching contacts which can
each be configured as either a NC contact
(1-3, 9-5) or NO contact (1-2, 9-6)
➎
.
Assignment of the pins
1
Root/pin for switching contact 1
2
NO contact for switching contact 1
3
NC contact for switching contact 1
4
Supply -
5
NC contact for switching contact 2
6
NO contact for switching contact 2
7
Functional earth
8
9
Root/pin for switching contact 2
4
Fasten top part of connector to bottom part
of connector (screw cap) and close line fixture
(screw cap/union nut).
➣
Feeding wiring through with accessories cable 0554 6720:
Shorten length of line (5 m) if necessary.
Connect the ends of the line according to the colour assignment:
Two separate switching points can be created using the two switching
contacts which can each be configured as either a NC contact (grey-pink,
brown-green) or NO contact (grey-yellow, brown-white).
Colour
Assignment
grey
root/pin for switching contact 1
yellow
NO contact for switching contact 1
pink
NC contact for switching contact 1
red
green
NC contact for switching contact 2
white
NO contact for switching contact 2
black
Functional earth
blue
supply -
brown
root/pin for switching contact 2
Содержание 6721