background image

 

Chapter 7 – Maintenance 

 

 

TestEquity 1016H & 1027H Temperature/Humidity Chamber 

Page 7-11

 

Refrigeration System

 (non-humidity mode) 

In non-humidity mode, cooling is accomplished by a cascade refrigeration system. A cascade 

refrigeration system consists of two interdependent refrigeration systems. The low-stage 

provides cooling to the chamber interior through a finned evaporator coil, which is located in the 

air plenum. The high-stage provides cooling to the cascade condenser. The cascade condenser is 

a heat exchanger that has one circuit which is the evaporator of the high-stage, and another 

circuit which is the condenser of the low-stage. 

 

The high-stage uses refrigerant R-404A or R-449A. High pressure liquid refrigerant is fed from 

the condenser through the liquid line, filter-drier, and sight glass to the thermostatic expansion 

valve. The thermostatic expansion valve controls the feed of liquid refrigerant to the evaporator 

circuit of the cascade condenser and, by means of an orifice, reduces the pressure of the 

refrigerant to the evaporating or low side pressure. The reduction of pressure on the liquid 

refrigerant causes it to boil or vaporize, absorbing heat which provides a cooling effect. The 

refrigerant vapor travels through the suction line to the compressor suction inlet. The compressor 

takes the low pressure vapor and compresses it, increasing both the pressure and the temperature. 

The hot, high pressure vapor is forced out of the compressor discharge valve and into the 

condenser. As the high pressure vapor passes through the condenser, it is cooled by a fan, which 

blows ambient air across the finned condenser surface. The vapor condenses into a liquid and the 

cycle is repeated.  

 

The Low-Stage uses refrigerant R-508B. High pressure liquid refrigerant is fed from the 

condenser circuit of the cascade condenser, through the filter-drier and liquid-line solenoid valve 

to the thermostatic expansion valve. The thermostatic expansion valve feeds the finned 

evaporator coil, which is located in the air plenum where heat is absorbed to provide a cooling 

effect within the chamber. The refrigerant vapor travels through the suction line to the 

compressor suction inlet. The compressor takes the low pressure vapor and compresses it, 

increasing both the pressure and the temperature. The hot, high pressure vapor is forced out the 

compressor discharge valve and into the desuperheater. The desuperheater removes some of the 

heat of compression. Next, the vapor goes through the oil separator, which returns any entrained 

oil back to the compressor’s crankcase. The vapor flows through the condenser circuit of the 

cascade condenser, where it is condensed back into a liquid. 

 

The F4T/F4 controller cycles the low-stage liquid-line solenoid valve (SV1) ON/OFF to control 

the chamber temperature. When SV1 is ON, liquid refrigerant flows through the thermostatic 

expansion valve and evaporator to cool the chamber. When SV1 is OFF, the flow stops. The hot 

gas bypass solenoid valve (SV2) is ON whenever SV1 is OFF. SV2 feeds high pressure vapor to 

the hot gas regulator, which meters a precise amount into the suction line to maintain a minimum 

load on the system and keep it out of a vacuum. The hot gas regulator is adjusted to keep the 

suction pressure at 8 PSIG when SV1 is OFF. This is also called “bypass mode”. The 

temperature controller alternately cycles SV2 and SV1 through cool relay CR1. Pilot Light PL2 

provides an indication on the front panel when SV1 is ON. 

 

During a high temperature pulldown or a continuous bypass condition, it is possible for 

excessive hot gas to return to the compressor. A suction line cooling thermostatic expansion 

valve (on both high- and low-stages) senses the suction line temperature and injects liquid 

refrigerant to cool the hot gas within safe limits. 

 

Содержание 1016H

Страница 1: ...019 Model 1016H 1027H Temperature Humidity Chamber Operation and Service Manual TestEquity LLC 6100 Condor Drive Moorpark CA 93021 Technical Support 877 512 3457 Toll Free 805 480 0638 Corporate 800 7...

Страница 2: ......

Страница 3: ...Switch EVENT 1 Mode_________________________________________________ 3 2 LIGHT Switch_________________________________________________________________________ 3 2 HEAT Light __________________________...

Страница 4: ...to Drain the Humidifier _____________________________________________________________ 7 7 How to Verify the Temperature Calibration __________________________________________________ 7 8 How to Verif...

Страница 5: ...eration in a conditioned laboratory environment Operation above 30 C 85 F or below 16 C 60 F ambient room temperature is NOT recommended CAUTION The Input Voltage label on the back of the chamber indi...

Страница 6: ...the setup values unless you thoroughly understand what you are doing The correct values are documented in the EZ Zone Limit Controller Setup Parameters section of this manual CAUTION Always verify th...

Страница 7: ...f you need to open the door while the chamber is operating wear safety goggles to prevent the high velocity airflow from blowing particles or objects into your eyes WARNING This chamber operates at ex...

Страница 8: ......

Страница 9: ...ration machinery compartment c Check the low stage refrigeration charge e Verify the chamber performance Installation Location The chamber will produce a significant amount of heat during normal opera...

Страница 10: ...hange the input voltage from one configuration to another CAUTION This chamber must be properly configured for either 208 V or 230 V nominal input 208 V and 230 V are NOT the same Do NOT guess Do NOT...

Страница 11: ...d side of the Main Disconnect Switch are individually fused However your local electrical code may require a separate disconnect switch within sight of the chamber Power Source Connection 1 Turn the D...

Страница 12: ...dity system using ordinary tap water Condensate from the chamber is returned back to the water tank The water pump runs continuously when the humidity system is enabled keeping the supply line pressur...

Страница 13: ...ceptacle on the back of the chamber The drain tube from the chamber must not be submerged in the water Use the supplied clamp on each end of filter and the water inlet fitting to prevent leaking Do no...

Страница 14: ......

Страница 15: ...the Main Disconnect Switch must be ON for 3 hours prior to operating the chamber Although it may be safe to use the chamber immediately this procedure ensures the longest possible life for the high st...

Страница 16: ...ocedure ensures the longest possible life for the high stage compressor if the chamber has been removed from the power source for more than 24 hours CONDITIONING Switch ON Mode The CONDITIONING Switch...

Страница 17: ...ion mode If the Humidity mode is disabled the chamber will cool in cascade refrigeration mode and there will be no humidity control HUMIDITY Light The HUMIDITY Light will illuminate when the F4T F4 Co...

Страница 18: ...ber s refrigeration system fails This chamber has a set of contacts that can be used to remove power to your test sample if the Limit Controller s temperature limits are exceeded CAUTION To prevent da...

Страница 19: ...use the humidity system to control moisture at low temperatures The humidity system is disabled below 7 C However if you have a source of GN2 gaseous nitrogen or Dry Air you can use the optional Purge...

Страница 20: ...a clean dry chamber For extended low humidity range below 6 C a dew point condition see Purge Option which follows The F4T F4 will automatically disable the humidity system below 7 C and above 90 C to...

Страница 21: ...essed air to the 3 8 inch FPT shutoff valve of Dry Air system Connect the power cord from the Dry Air system to the DRY AIR POWER socket on the rear panel This plug must be twisted clockwise to lock i...

Страница 22: ...H 1027H Temperature Humidity Chamber Relief Vent Excess pressure in the chamber workspace is vented through a pressure relief check valve which is located on the top of the chamber behind the fan shro...

Страница 23: ...l manual and is written by the manufacturer Watlow for a wide variety of applications and configurations Not all features or functions are applicable Only the capabilities of a model PM6L1AJ AAAABAA a...

Страница 24: ...er than your actual chamber temperature set point to prevent nuisance tripping 5 Press the RESET Key to return to the Home Page 6 The upper display will show the actual chamber temperature while the l...

Страница 25: ...n be used to remove power to your test sample if the Limit Controller s temperature limits are exceeded The safety contacts are rated as follows Resistive 10 A 250 VAC or 10 A 28 VDC Inductive 7 A 250...

Страница 26: ......

Страница 27: ...our installation be determined by a qualified electrician who is familiar with industrial plant wiring I need to send the chamber outside North America Will it work with their power Outside North Amer...

Страница 28: ...ample the temperature set point may be 25 0 C The actual temperature varies between 25 4 C and 24 5 C This corresponds to 0 4 C and 0 5 C or a total of 0 9 C of RELATIVE variations These specification...

Страница 29: ...he high stage compressor if the chamber has been removed from the power source for more than 24 hours Can the person who services our air conditioning also service the chamber Probably not Most air co...

Страница 30: ......

Страница 31: ...th an instantaneous step change in Set Point without a controlled ramp rate Does not include the effect of proportional band when approaching setpoint Performance is reduced by 17 with 50Hz input powe...

Страница 32: ...neous step change in Set Point without a controlled ramp rate Does not include the effect of proportional band when approaching setpoint Performance is reduced by 17 with 50Hz input power Input Power...

Страница 33: ...interior and exterior Listen for abnormal noise or vibration Inspect the demineralizer cartridge if provided Every 3 Months Inspect the door seal Inspect the refrigeration machinery compartment Check...

Страница 34: ...noises Being able to recognize changes from normal operating noises can be a valuable way to identify problems and prevent further damage Examples of noises to be aware of include Circulator motor and...

Страница 35: ...the two low stage gauges marked R 508B on the left side of the rear of the chamber 3 The two gauges have different scales However they should read the same value of pressure This indicates that the sy...

Страница 36: ...lowly increase and stabilize to 85 C It should NOT overshoot beyond 85 C by more than a few tenths of a degree and the compressors should NOT need to turn ON to maintain 85 C 5 After stabilization the...

Страница 37: ...ntrolling Heat Light cycles ON OFF within 7 minutes 5 The chamber temperature should slowly increase and stabilize to 85 C It should NOT overshoot beyond 85 C by more than 1 0 C and the compressor sho...

Страница 38: ...u may be able to clean the condenser less frequently if the chamber is in a very clean environment How to Drain the W100 Water Recirculation System Reservoir 1 This procedure drains the water in the r...

Страница 39: ...t the chamber from the power source 4 Remove the lower rear panel 5 Open the Drain Valve by turning its handle 90 degrees counter clockwise Water will come out of the Drain fitting on the back of the...

Страница 40: ...ts in the chamber and adjusting the temperature controller s calibration to correct for these errors is incorrect The correct way to adjust what the temperature controller displays compared to what is...

Страница 41: ...sor calibration at all humidity conditions that the chamber is capable of achieving For the F4 Controller If calibration of the controller is necessary refer to the F4 Temperature Humidity Controller...

Страница 42: ...both the Conditioning Switch the safety relay CR1 and the phase control relay PCR1 CR1 is controlled by the temperature limit controller TCR2 If either the high or low temperature safety limits are e...

Страница 43: ...er circuit of the cascade condenser through the filter drier and liquid line solenoid valve to the thermostatic expansion valve The thermostatic expansion valve feeds the finned evaporator coil which...

Страница 44: ...ystem is disabled The Humidity mode is enabled through Event 2 Digital Output 2 in the F4T F4 Controller Also the chamber workspace must be between 7 C and 90 C If the chamber is outside this temperat...

Страница 45: ...bar is 100 F4 controller light 1B is ON F4T Compressor Output F4 DigitalOut 8 is ON the Cool light on front panel is OFF both compressors are OFF 2 Setpoint is low than chamber temperature but F4T Co...

Страница 46: ...ive Compressors turn on and off too frequently 1 If compressor control parameters in F4T F4 Controller were changed 2 If compressor control parameters in F4T F4 Controller are as shipped from TestEqui...

Страница 47: ...lined in How to verify the chamber performance NOTE If the F4 Controller is cycling Cool Light cycles on off the sightglass may appear 1 2 to 2 3 full This is normal R 508B Low Stage Charge 1 Repair a...

Страница 48: ...k being out of service for even one day then you should purchase critical spare parts in advance Although most parts are standard and available from a variety of local distributors some parts are eith...

Страница 49: ...Peltec 256 240S PCR1 222292 1 ea Indicator Panel 240V Neon SoLiCo S412 2 1 N2 PL1 2 200026 2 ea Indicator Panel 120V Neon SoLiCo S412 2 1 N1 PL3 4 200025 2 ea Resistor 1 kohm 25W Vishay Dale RH0251K0...

Страница 50: ...oss 068U3317 28 100487 1 ea Expansion Valve Suction Cool HS Sporlan SBFJ AA C 25 100077 1 ea Expansion Valve Suction Cool LS Sporlan SBFS B ZP 3 8 x 5 8 odf 26 100507 1 ea Filter Drier Sporlan C 083 S...

Страница 51: ...ge L Sd Limit Sides both Alt high High only or LoW Low only L hY Limit Hysteresis 2 Change not recommended A ty Alarm Type oFF Do Not Change PAr1 Upper Display ACPu Alt none PAr2 Lower Display Lst Alt...

Страница 52: ......

Страница 53: ...d for labor if they initiate service on their own without prior approval from TestEquity Replacement parts must be supplied by TestEquity for in warranty claims Purchaser will not be reimbursed for pa...

Страница 54: ......

Страница 55: ...Chapter 9 Drawings TestEquity 1016H 1027H Temperature Humidity Chamber Page 9 1 Chapter 9 Drawings...

Страница 56: ......

Страница 57: ......

Отзывы: