SUPERCHARGER EMERGENCY RESPONSE GUIDE 

 

WARNING: Regardless of the disabling procedure you use, ALWAYS ASSUME THAT ALL HIGH 

VOLTAGE COMPONENTS ARE ENERGIZED! Cutting, crushing or touching high voltage components can 

result in serious injury or death.

 

 

SUPERCHARGER DEPLOYMENT 

 

How to Disconnect Power to a Single Supercharger Cabinet 

 

Locate electrical switchgear for Supercharger Cabinets, typically inside an enclosure similar 
to what is pictured below. This enclosure is usually located within 100 feet of the station.  

 

 

Enter the locked enclosure. Enclosures are 
typically locked with padlocks or a locked 
door handle. The use of bolt-cutters will 
typically be needed. 

 

Electrical switchgear enclosures are locked 
with padlocks and can be removed using 
bolt-cutters. Switchgear usually consists of 
two or three separate bays, each with its 
own door. Switchgear configurations may 
vary by site. 

 

To disconnect power to a specific 
Supercharger Cabinet, locate the bay of 
the switchgear that contains the branch 
circuit breakers for each Supercharger 
Cabinet. Branch breakers are labeled with 
corresponding Supercharger Cabinets that 
are connected to them. Supercharger 
Cabinets are labeled in a similar manner.  

 

Switch the breaker handle to the OFF 
position. Do not attempt to reset the 
breaker to disconnect. 

 

This will disconnect all power to the 
specific Supercharger Cabinet, as well as its corresponding Supercharger posts. 

 

If both the main breaker and branch breakers are inoperable or have major damage, contact 
the utility company to disconnect power from the grid. 
 

 

Содержание V2 SUPERCHARGER

Страница 1: ...la Supercharger equipment in an emergency situation It describes how to identify Supercharger equipment and provides the locations and descriptions of its high voltage components This guide includes t...

Страница 2: ...crushing or touching high voltage components can result in serious injury or death 2 SUPERCHARGER DEPLOYMENT Table of Contents Physical Damage to Electrical Switchgear or Transformer 3 How to Disconne...

Страница 3: ...ght Contact local utility company to disconnect grid power coming into equipment Treat all wires as dangerous and energized at high voltage Do not attempt to move exposed power cables Do not spray wat...

Страница 4: ...adlocks and can be removed using bolt cutters Switchgear usually consists of two or three separate bays each with its own door Switchgear configurations may vary by site To disconnect all power to the...

Страница 5: ...DE WARNING Regardless of the disabling procedure you use ALWAYS ASSUME THAT ALL HIGH VOLTAGE COMPONENTS ARE ENERGIZED Cutting crushing or touching high voltage components can result in serious injury...

Страница 6: ...tchgear enclosures are locked with padlocks and can be removed using bolt cutters Switchgear usually consists of two or three separate bays each with its own door Switchgear configurations may vary by...

Страница 7: ...crushing or touching high voltage components can result in serious injury or death 7 SUPERCHARGER DEPLOYMENT General Site Layout A typical site layout is shown below No two sites are identical but th...

Страница 8: ...or death 8 SUPERCHARGER DEPLOYMENT Firefighting Extinguish small fires that do not involve a high voltage battery using a CO2 or ABC extinguisher During overhaul do not make contact with any high volt...

Страница 9: ...its licensors Additional information is available upon request and MODEL S are registered trademarks of Tesla in the United States TESLA is a trademark of Tesla in the United States and other countri...

Отзывы: