Troubleshooting & FAQ

6.2 - Basic Usage/Operation Questions 

1. What’s the best position to place the unit for use vertical or horizontal?

Preferred position is horizontal for stability and airfl ow considerations. When charging, the preferred position is horizontal.  
The Turbo Start™ can be put in any position while it is being used as there is nothing to spill inside the system.

2. Does the unit have to be plugged in all the time?

No, but for maximum performance and cell longevity, keep the unit plugged in while not in use.

3. What happens if I don’t keep it plugged in?

Unit will eventually lose its charge and cell life is shortened.

4. How do I check the status of the charge?

Press the “Push to Test”  LED bar indicator on the unit’s faceplate. A fully charged unit will have one green LED light 
showing.

5. Why is the cooling fan always running when I am plugged into ac power?

Constant cooling fan operation ensures proper and consistent ventilation of the unit.

6. Why does the cooling fan slow down?

Cooling fan rpm varies for better temperature regulation.

7.  Why does my LED fl icker when the unit is plugged in?

Older Turbo Starts™ indicated a full charge with a fl ickering LED readout.  Newer models feature the illumination of one 

green bar on the LED readout when the unit is fully charged.

8.  What do I do if a circuit breaker trips?

The AC Input Circuit Breaker is located above the AC Input Connector.  When the circuit breaker has been tripped, either of 

the red buttons will pop out.  In the event that the breaker trips:

Disconnect the ac and dc connectors. (Unplug ac line cord on military unit.)

1. 

Wait for a minimum of 60 seconds.

2. 

Reset breaker by pressing red button.

3. 

Reconnect ac and dc connections to the unit.  (Plug in  ac line cord on military unit.)

4. 
The unit should power up automatically.  If the breaker continues to trip, return the unit  to Tesla™ Industries for repair.

Содержание TI3000 GPU-24 UAV

Страница 1: ...nual Built Smart Proven Tough Power Anytime Anywhere Tesla TI3000 GPU 24 UAV Tesla Industries Inc 101 Centerpoint Blvd New Castle DE 19720 302 324 8910 Phone 302 324 8912 Fax www teslaind com www tesl...

Страница 2: ...pened or disassembled for any reason Always protect the unit from short circuit Shipping Hazards The unit contains sealed dry cell rechargeable batteries that do not pose a shipping hazard 09 23 20 Al...

Страница 3: ...oors or in a well ventilated area Causes damage to central nervous system blood and Contact with internal components may cause irritation or severe burns Avoid contact with internal acid kidneys throu...

Страница 4: ...bicarbonate lime etc Wear acid resistant clothing boots gloves and face shield Do not allow discharge of unneutralized acid to sewer Acid must be managed in accordance with local state and federal req...

Страница 5: ...ensions 6 2 6 Airflow Ports 6 2 7 Operating Position 7 2 8 AC Input Circuit Breakers 8 2 9 24 Vdc Output Connector 8 2 10 Push to Test Button and LED Status Indicator 9 Section 3 Operating Procedures...

Страница 6: ...y Asked Questions 22 23 6 2 Basic Usage Operation Questions 24 6 3 Basic Troubleshooting 25 26 Section 7 Performance Data 27 7 1 Purpose 27 7 2 General 27 7 3 Data Basis 27 7 4 Specific Conditions 27...

Страница 7: ...enheit dc Direct Current EFF Efficiency ft Feet FWD Forward GPU Ground Power Unit Hr Hour Hz Hertz kg Kilograms kHz Kilohertz kW Kilowatts LED Light Emitting Diode max Maximum M megaohm min Minimum MP...

Страница 8: ...rd WARNING Indicates a condition operating procedure or practice which if not adhered to could result in serious injury or death CAUTION Indicates a condition or operating procedure which if not stric...

Страница 9: ...per Ground Adapter with Grounding Mechanism Secured to Outlet Figure 1 3 3 Improper Ground Plug with No Grounding Pin The use of unapproved ac power will damage the unit Check the Input Voltage Select...

Страница 10: ...e of procedures limitations and performance criteria ensures peak operating efficiency and maximizes operational capabilities and life of the TI3000 GPU 24 UAV This manual contains the complete operat...

Страница 11: ...acity Meter 3 Indicates the 24V battery charge state power output status Air Intake Ports 4 Provide airflow for cooling internal electronics AC Input Circuit Breaker 5 Trips if over current fault cond...

Страница 12: ...dc 1525 Watts when plugged into ac power 96 amp hours 2449 watt hours with 100 260 Vac power 46 amp hours 1024 watt hours of rechargeable battery power without 100 260 Vac Recharge Rate 60 minutes fro...

Страница 13: ...100 260 Vac 50 60 Hz ac power the internal cooling system will efficiently regulate unit temperature regardless of load At room temperature 77 F the exhaust air will not exceed the ambient temperatur...

Страница 14: ...ted in both the horizontal Figure 2 7 1 and vertical Figure 2 7 2 positions as shown Make sure that the airflow is not obstructed from air intake figure 2 7 3 and outlet Figure 2 7 4 Figure 2 7 2 Vert...

Страница 15: ...tput Connector 2 8 AC Input Circuit Breaker The ac input circuit breaker is located above the AC Input Connector When the circuit breaker has been tripped the red button will pop out In the event that...

Страница 16: ...sures a correct reading Without ac power input or dc power output simply press the Push to Test button on the faceplate 2 and hold for approximately 2 to 3 seconds The LED bar graph should light up in...

Страница 17: ...t Consideration must be given to changes in performance resulting from variations in ambient temperature mode of operation state of charge with or without ac power and aircraft dc bus system inefficie...

Страница 18: ...or air conditioning when possible Perform a full function test prior to use after the unit has been allowed to cool 3 6 Temperature Specifications Cold Hot Soaked Temperature Exposing the unit for on...

Страница 19: ...0 76 cm or continuously between 0 30 and 0 10 inch per hour OK OPERATION NOT RECOMMENDED Light rain drizzle or sleet Precipitation falling on a continuous basis between 0 10 inch and less than 1 50 in...

Страница 20: ...gital multimeter an example is shown in Figure 3 7 1 capable of measuring dc and ac voltage and resistance will be required to perform some of the tests These functional test procedures should become...

Страница 21: ...ate ac power source When the unit is not plugged into an ac power source the multimeter display should read approximately 25 5 Vdc Check Unit Internal Resistance Test for Shorts Figure 3 7 2 Set multi...

Страница 22: ...m air intake and outlet See Section 2 6 3 Check that all connections are secure and free from water 4 Figure 3 8 1 TI3000 GPU 24 UAV 3 9 Transporting Unit The TI3000 GPU 24 UAV has a telescoping handl...

Страница 23: ...ng DC Power Cable to Unit Low Power Demand Low power demand is defined by a requirement of 50 amps or less Connect dc power to aircraft ground power receptacle DC bus power should come on and aircraft...

Страница 24: ...g the unit into a wall socket to charge the batteries Until the unit is fully charged the LED status will read half or no charge Plug the TI3000 GPU 24 UAV into ac power to keep the cells charged when...

Страница 25: ...ckcharge feature that enables the unit to be recharged from the vehicle once the engine is started and the starter generator is running This feature will enable you to start multiple vehicles without...

Страница 26: ...be damaged if recharged by NiCad or Lithium Ion battery chargers Power cells should only be charged by either the TI3000 GPU 24 UAV s internal charger and the ac power cord furnished with the equipme...

Страница 27: ...t cloth to remove dust dirt etc Protect Cables from Damage Do not cut crush or drag the input or output power cables when handling the unit Always inspect cables prior to use If no damage is evident p...

Страница 28: ...al the crate on all sides and return it to Tesla at the address listed below Please contact Tesla Customer Service at 302 324 8910 with any questions or concerns TESLA INDUSTRIES INCORPORATED 101 CENT...

Страница 29: ...tart aboard your aircraft You may take the Turbo Start anywhere you travel ensuring that you will always have power 4 How much power will my Turbo Start provide Depending on the system the Turbo Start...

Страница 30: ...get my Turbo Start serviced Contact Tesla We can be reached at 302 324 8910 Ask for customer service You can also email us at tesla1 teslaind com Once we receive the unit at our facility we will exam...

Страница 31: ...lways running when I am plugged into ac power Constant cooling fan operation ensures proper and consistent ventilation of the unit 6 Why does the cooling fan slow down Cooling fan rpm varies for bette...

Страница 32: ...ac outlet AC line cord is damaged or bad A Is ac line cord fully plugged into unit B and wall outlet AC circuit breaker has been tripped C No ac power at outlet D Do a continuity test on the ac line c...

Страница 33: ...put out 28 5 volts dc power Unit is not plugged in A Plug unit into ac power source to A maintain 28 5 Stand alone Vdc is 24 Volts B unplugged 9 Unit stand alone voltage is less than 23 volts Cells di...

Страница 34: ...nce chart under DATA BASIS The applicable report and date of the data are also given The data provided generally are based on one of three categories Derived From Actual Controlled Testing Controlled...

Страница 35: ...66 2 52 0 125 6 46 0 50 8 13 0 8 6 20 0 68 0 53 0 127 4 45 0 49 0 12 0 10 4 21 0 69 8 54 0 129 2 44 0 47 2 11 0 12 2 22 0 71 6 55 0 131 0 43 0 45 4 10 0 14 0 23 0 73 4 56 0 132 8 42 0 43 6 9 0 15 8 24...

Страница 36: ...0 25 30 25 C Temp 29 C Temp Calculations based on actual test data at Pratt Whitney Canada on 30 March 1992 SECONDS AMPS MAXIMUM OUTPUT CURRENT 0 0 TI3000 Maximum Output Current TI3000 Output Voltage...

Страница 37: ...be custom ordered to fit your needs Tesla specializes in outfitting cables with a variety of connectors and junction boxes Contact Tesla customer service to find out more about our selection of cords...

Страница 38: ...ous customer mobility needs TI21000 203 Flat Free Tire A solid foam rubber tire The stan dard tire for ground power units TI21000 400 Anti FOD Flat Free Tire Rugged puncture proof foam filled tire For...

Страница 39: ...ean Line Cord Burma Now Myanmar 230 50 TI25000 005 United Kingdom Line Cord Burundi 220 50 TI25000 003 Continental European Line Cord Cambodia 220 50 TI25000 003 Continental European Line Cord Cameroo...

Страница 40: ...rd Guadeloupe 220 50 TI25000 003 Continental European Line Cord Guam 110 120 60 TI25000 001 North American Line Cord Guatemala 120 60 TI25000 001 North American Line Cord Guinea 220 50 TI25000 003 Con...

Страница 41: ...n Line Cord Montseurrat 230 60 TI25000 005 United Kingdom Line Cord Morocco 220 50 TI25000 003 Continental European Line Cord Mozambique 220 50 TI25000 003 Continental European Line Cord Namibia W S A...

Страница 42: ...5000 004 Old British Line Cord Sweden 220 50 TI25000 003 Continental European Line Cord Switzerland 220 50 TI25000 006 Switzerland Line Cord Syria 220 50 TI25000 003 Continental European Line Cord Tah...

Страница 43: ...6000 19 AND MUST BE ORDERED WITH THE ORIGINAL PROCUREMENT OF UNIT S UNIT S MAY BE RETURNED TO TESLA INDUSTRIES FOR A NOMINAL COST AND MODIFIED TO ALLOW OPERATION WITH THE UNIVERSAL AC LINE CORD KIT TE...

Страница 44: ...Email _______________________________________________________________________________________ Purchase Order ______________________________________________________________________________ Model ______...

Страница 45: ...Tesla 101 Centerpoint Blvd New Castle DE 19720 USA Tel 302 324 8910 Fax 302 324 8912 9475 Double R Blvd Suite 2 Reno NV 89521 Tel 775 622 8801 Fax 775 622 8810 www teslaind com www tesla1 com...

Отзывы: