Removal and Vacuum Pumping
1. Make sure there is no ignited fire source near the outlet of the vacuum pump and the ventilation is well.
2. Allow the maintenance and other operations of the refrigeration circuit should be carried out according to the
general procedure, but the following best operations that the flammability is already taken into consideration are
the key. You should follow the following procedures:
• Remove the refrigerant.
• Decontaminate the pipeline by inert gases.
• Evacuation.
• Decontaminate the pipeline by inert gases again.
• Cut or weld the pipeline.
3. The refrigerant should be returned to the appropriate storage tank. The system should be blown with oxygen
free nitrogen to ensure safety. This process may need to be repeated for several times. This operation shall not
be carried out using compressed air or oxygen.
4. Through blowing process, the system is charged into the anaerobic nitrogen to reach the working pressure
under the vacuum state, then the oxygen free nitrogen is emitted to the atmosphere, and in the end, vacuumize
the system. Repeat this process until all refrigerants in the system is cleared. After the final charging of the
anaerobic nitrogen, discharge the gas into the atmosphere pressure, and then the system can be welded. This
operation is necessary for welding the pipeline.
Procedures of Charging Refrigerants
Scrap and Recovery
As a supplement to the general procedure, the following requirements need to be added:
- Make sure that there is no contamination among different refrigerants when using a refrigerant charging device.
The pipeline for charging refrigerants should be as short as possible to reduce the residual of refrigerants in it.
- Storage tanks should remain vertically up.
- Make sure the grounding solutions are already taken before the refrigeration system is charged with refrigerants.
- After finishing the charging (or when it is not yet finished), label the mark on the system.
- Be careful not to overcharge refrigerants.
Scrap
:
Before this procedure, the technical personnel shall be thoroughly familiar with the equipment and all its features,
and make a recommended practice for refrigerant safe recovery. For recycling the refrigerant, shall analyze the
refrigerant and oil samples before operation. Ensure the required power before the test.
1.Be familiar with the equipment and operation.
2.Disconnect power supply.
3.Before carrying out this process, you have to make sure:
• If necessary, mechanical equipment operation should facilitate the operation of the refrigerant tank.
• All personal protective equipment is effective and can be used correctly.
• The whole recovery process should be carried out under the guidance of qualified personnel.
•The recovering of equipment and storage tank should comply with the relevant national standards.
4. lf possible, the refrigerating system should be vacuumized.
5. If the vacuum state can’t be reached, you should extract the refrigerant in each part of the system from many
places.
6. Before the start of the recovery, you should ensure that the capacity of the storage tank is sufficient.
7. Start and operate the recovery equipment according to the manufacturer’s instructions.
8. Don’t fill the tank to its full capacity (the liquid injection volume does not exceed 80% of the tank volume).
9. Even the duration is short, it must not exceed the maximum working pressure of the tank.
10. After the completion of the tank filling and the end of the operation process, you should make sure that the
tanks and equipment should be removed quickly and all closing valves in the equipment are closed.
11. The recovered refrigerants are not allowed to be injected into another system before being purified and tested.
Note
: The identification should be made after the appliance is scrapped and refrigerants are evacuated. The
identification should contain the date and endorsement. Make sure the identification on the appliance can reflect
the flammable refrigerants contained in this appliance.
Содержание TC26P4-0932IA
Страница 61: ...61 BG R32 5m 2 1 7 R32 R32...
Страница 63: ...63 BG 3 0 mm 30 mA 1 5 80 T1 T3 ISO 5151 43 C T1 52 C T3 18 C 24 C 7 C 27 C 1 2 3 3 15A 250V AC...
Страница 64: ...64 BG 5 12 1 2 1 2 1 2...
Страница 65: ...65 BG...
Страница 66: ...66 BG 5 40 C 1 2 45 C 1 2 3 4 5 1...
Страница 67: ...67 BG 1 2 3 4 3 5...
Страница 68: ...68 BG...
Страница 69: ...69 BG R32 R32 R32 5 m2 R32 4 200 kg...
Страница 71: ...71 BG 1 1 2 1 1 1 2 1 1 1 15 20 20 200 260cm...
Страница 72: ...72 BG 1 2 3 1 5 10 2 60mm 80mm 1 1 2 2 1...
Страница 74: ...74 BG 1 2 3...
Страница 76: ...76 BG 1 E 2 3 4 5 E To power To power To power To power E parts cover...
Страница 77: ...77 BG Gas R32 R32 R32 1 2 3 Lo 15 O IMPa 76 cmHg 4 5 76cmHg Hi Lo 25 1 2 3 1 2 3 4 5 t 1 2...
Страница 78: ...78 BG 1 2 COOL HEAT SWING R32 R32 1 2 R32 1 2...
Страница 79: ...79 BG 3 CO2 4 5 6 7...
Страница 80: ...80 BG R32 R32 25 OFN 1 2 3 4...
Страница 81: ...81 BG 1 2 3 4 5 6 7 8 80 9 10 11 1 2 3 R32 II 4 5 R32 a 6 R32...
Страница 82: ...82 BG 1 2 8 3 4 5 6 7 7 8 9 10...
Страница 83: ...83 BG 1 1 11 LCD 2 LCD 3 LCD 16 32 C 61 90 F ECO 2 1 2 25 C...
Страница 87: ...87 24 13 12 TESLA 1 2 2 1 2 2 TESLA 2 3 2 4 2 5 2 6 2 7 2 8 2 9 2 10 2 11...
Страница 88: ...88 2 12 3 4 5 6 7 8 112 115 119 112 1 2 1 2 3 113 1 2 3 2 114 4 5 114 1 113 1 2 2 3...
Страница 89: ...89 115 4 115 1 2 1 3 1 1 10 02 9700970 02 9700971 9 30 19 00 10 00 16 00...
Страница 90: ...90...
Страница 91: ...91 GR R32 O 5m2 1 7kg R32 R32...
Страница 92: ...92 GR 8 CE CE 1 GWP GWP GWP 675 1 kg 675 1kg CO2 100 1 2 3 3 15A 250V AC...
Страница 93: ...93 GR 3 0 mm 30 mA 1 5 80 T1 T3 ISO 5151 43 C T1 52 C T3 18 C 24 C 7 C 27 C...
Страница 94: ...94 GR 5 12 1 swing 2 swing 1 2 1 2...
Страница 95: ...95 GR swing...
Страница 96: ...96 GR 5 40 C 1 2 45 C 1 2 3 4 5 1...
Страница 97: ...97 GR 1 2 3 4 3 5 Mode wind speed Mode...
Страница 98: ...98 GR Strong wind Strong wind...
Страница 99: ...99 GR R32 R32 R32 5m2 R32 4 200 kg...
Страница 101: ...101 GR H 1 Set 1 PC 7 2 PC 1 Set 1 PC 1 Set 2 PC 1 ROLL 1 PC 1 PACKET 15cm 20cm 20cm 200 260cm...
Страница 102: ...102 GR 1 2 3 1 5 10 2 60mm 80mm 1 1 2 2 1...
Страница 103: ...103 GR 1 2 1 2 3 mm Nm 6 6 35 15 88 9 9 52 35 40 12 12 7 45 60 15 88 73 78 19 05 75 80 1 2...
Страница 104: ...104 GR 1 2 3...
Страница 106: ...106 GR 1 2 3 4 5...
Страница 107: ...107 GR R32 R32 R32 1 2 3 15 0 1MPa 76cmHg 4 5 76cmHg Charge hose 25 1 2 3 1 2 3 4 5...
Страница 108: ...108 GR 1 ON OFF 2 COOL HEAT SWING 1 2 R32 R32 after sales service 1 2 R32 1 2...
Страница 109: ...109 GR R32 R32 25 OFN 3 CO2 4 5 6 7...
Страница 110: ...110 GR 1 2 3 4 1 2 3 4 5 6 7 8 80 9 10 11...
Страница 111: ...111 GR 1 2 3 R32 4 5 R32 6 R32 1 2 8m 3 4 5 6 7 7 8 9 10...
Страница 112: ...112 GR ECO Turbo Timer Sleep 1 1 1 11 LCD 2 LCD 3 LCD 16 32 C 61 90 F TURBO ECO 2 1 1 1...
Страница 116: ...116 7 service TESLA TESLA 8 9 TESLA 10 email warranty gr comtrade com...
Страница 117: ...117 1 Service 2 Service 3 Service 4 Service 5 Service 6 Service 7 Service 8 Service 9 Service...
Страница 146: ...146 MKD R32 5m2 1 7kg R32 R32...
Страница 147: ...147 MKD 8 AC CE AC CE 1m A GWP GWP GWP 675 1 kg 675 1 kg CO2 100 1 2 3 3 15A 250V AC...
Страница 148: ...148 MKD 3 0 mm RCD 30 mA 1 5 80 T1 T3 ISO 5151 43 C T1 52 C T3 18 C 24 C 7 C 27 C...
Страница 149: ...149 MKD 5 12 1 swing 2 swing 1 2 1 2...
Страница 150: ...150 MKD WiFi swing...
Страница 151: ...151 MKD 5 40 C 1 2 45 C 1 2 3 4 5 o 1...
Страница 152: ...152 MKD 1 2 3 4 3 5 A OPREZ...
Страница 153: ...153 MKD Strong wind Strong wind T...
Страница 154: ...154 MKD R32 R32 R32 5m2 R32 200...
Страница 156: ...156 MKD 1 1 7 2 1 1 1 2 1 1 1 15cm 20cm 20cm 200 260cm...
Страница 157: ...157 MKD 1 2 3 1 5o 10o 2 60mm 80mm 1 1 2 Pipe protection ring 2 Putty 1...
Страница 158: ...158 MKD 1 2 1 2 3 mm Nm 6 6 35 15 88 9 9 52 35 40 12 12 7 45 60 15 88 73 78 19 05 75 80 1 2...
Страница 159: ...159 MKD 1 2 3...
Страница 161: ...161 MKD 1 2 3 Dijagram instalacije E...
Страница 162: ...162 MKD Gas R32 R32 R32 1 2 3 15 0 1 MPa 76 cmHg 4 5 76cmHg Hi Lo 25 1 2 3 1 2 3 4 5 Chassis Outdoor drain elbow...
Страница 163: ...163 MKD 1 ON OFF 2 COOL HEAT SWING 1 2 R32 R32 1 2 R32...
Страница 164: ...164 MKD 1 2 3 CO2 4 5 6 7...
Страница 165: ...165 MKD R32 R32 25 OFN 1 2 3 4...
Страница 166: ...166 MKD 1 2 3 4 5 6 7 8 80 9 10 11 1 2 3 R32 4 5 R32 6 R32...
Страница 167: ...167 MKD 1 2 8 3 4 5 6 2 7 7 8 9 10...
Страница 168: ...168 MKD T 1 1 11 LCD 2 LCD 3 LCD 16 32 C 61 90 F 2 ON OFF Mode 1...
Страница 171: ...171 MKD WiFi https tesla info wp content uploads pdf TeslaTCWiFiapp pdf...
Страница 173: ...173 1 30 2 3 3 12 12 12...
Страница 174: ...174...
Страница 175: ...175 Customer signature m C C V 15 1 2 3 C C V C C V...
Страница 177: ...177 070 503 855 078 213 502 070 218 860 078 522 660 Te a Te 075 650 888 078 213 502 078 213 502 078 522 660...
Страница 264: ...www tesla info...